10EHZ-32Z/C03 [MSYSTEM]

High-density Signal Conditioners 10-RACK;
10EHZ-32Z/C03
型号: 10EHZ-32Z/C03
厂家: M-SYSTEM    M-SYSTEM
描述:

High-density Signal Conditioners 10-RACK

文件: 总3页 (文件大小:97K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MODEL: 10EHZ  
E: 0 – 16 mA DC (Load resistance 750 Ω max.)  
High-density Signal Conditioners 10-RACK  
F: 0 – 10 mA DC (Load resistance 1200 Ω max.)  
G: 0 – 1 mA DC (Load resistance 12 kΩ max.)  
J: 0 – 5 mA DC (Load resistance 2400 Ω max.)  
Z: Specify current (See OUTPUT SPECIFICATIONS)  
Voltage  
FREQUENCY TRANSDUCER  
Functions & Features  
• Providing a DC output signal in proportion to deviation (±5  
Hz) from center frequency (50 Hz or 60 Hz)  
• DC output containing little ripple is ideal for computer  
input  
1: 0 – 10 mV DC (Load resistance 10 kΩ min.)  
2: 0 – 100 mV DC (Load resistance 100 kΩ min.)  
3: 0 – 1 V DC (Load resistance 1000 Ω min.)  
4: 0 – 10 V DC (Load resistance 10 kΩ min.)  
5: 0 – 5 V DC (Load resistance 5000 Ω min.)  
6: 1 – 5 V DC (Load resistance 5000 Ω min.)  
0: Specify voltage (See OUTPUT SPECIFICATIONS)  
• Isolation up to 2000 V AC (input)  
Typical Applications  
• Centralized monitoring and control of power management  
system in manufacturing facility or building  
• Measuring frequency for UPS  
POWER INPUT  
DC Power  
R: 24 V DC  
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)  
[4] OPTIONS  
blank: none  
/Q: With options (specify the specification)  
SPECIFICATIONS OF OPTION: Q  
COATING (For the detail, refer to M-System's web site.)  
/C01: Silicone coating  
MODEL: 10EHZ–[1][2][3]–R[4]  
/C02: Polyurethane coating  
/C03: Rubber coating  
ORDERING INFORMATION  
• Code number: 10EHZ-[1][2][3]-R[4]  
Specify a code from below for each [1] through [4].  
(e.g. 10EHZ-11A-R/Q)  
GENERAL SPECIFICATIONS  
Construction: Rack-mounted; terminal access via screw  
terminals at the front and via card-edge connector at the  
rear; terminal cover provided  
• Special output range (For codes Z & 0)  
• Specify the specification for option code /Q  
(e.g. /C01)  
Connection  
Input: M3.5 screw terminals (torque 0.8 N·m)  
Output: Card-edge connector and M3.5 screw terminals  
(torque 0.8 N·m)  
[1] FREQUENCY  
1: 45 – 55 Hz  
Power input: Supplied from card-edge connector  
Screw terminal: Nickel-plated steel  
2: 55 – 65 Hz  
Housing material: Flame-resistant resin (black)  
Isolation: Input to output to power  
3: 45 – 65 Hz  
Overrange output: Approx. -10 to +120 % at 1 – 5 V  
Zero adjustment: -5 to +5 % (front)  
[2] INPUT  
1: 110 V AC  
2: 220 V AC  
Span adjustment: 95 to 105 % (front)  
INPUT SPECIFICATIONS  
Input burden: 1 VA max.  
[3] OUTPUT  
Current  
Operational range: 85 – 120 % of rating  
Overload capacity: 150 % of rating for 10 sec., 120 %  
continuous  
A: 4 – 20 mA DC (Load resistance 600 Ω max.)  
D: 0 – 20 mA DC (Load resistance 600 Ω max.)  
http://www.m-system.co.jp/  
10EHZ SPECIFICATIONS  
ES-0844 Rev.2 Page 1/3  
MODEL: 10EHZ  
OUTPUT SPECIFICATIONS  
■ DC Current: 0 – 20 mA DC  
Minimum span: 1 mA  
Offset: Max. 1.5 times span  
Load resistance: Output drive 12 V maximum  
DC Voltage: 0 – 12 V DC  
Minimum span: 5 mV  
Offset: Max. 1.5 times span  
Load resistance: Output drive 1 mA max.; at ≥ 0.5 V  
OPERATION DIAGRAM (example)  
OUT  
20mA  
OUT  
10V  
12  
4
5
0
45  
55  
65 Hz  
45  
55  
65 Hz  
Remark: When there is no input voltage,  
the transducer outputs as negative (–) overrange.  
INSTALLATION  
Current consumption: Approx. 80 mA  
Operating temperature: -5 to +55°C (23 to 131°F)  
Operating humidity: 30 to 90 %RH (non-condensing)  
Mounting: Standard Rack 10BXx  
Weight: 400 g (0.88 lb)  
PERFORMANCE in percentage of span  
Accuracy: ±1.0 %  
Temp. coefficient: ±0.1 %/°C (±0.06 %/°F)  
Response time: ≤ 1 sec. (0 – 90 %)  
Ripple: 0.5 %p-p max.  
Line voltage effect: ±0.1 % over voltage range  
Insulation resistance: ≥ 100 MΩ with 500 V DC  
Dielectric strength: 2000 V AC @ 1 minute  
(input to output or power to ground)  
500 V AC @ 1 minute (output to power)  
CONNECTION DIAGRAM  
SOURCE  
VT  
FUSE  
U
u
v
+
1
2
14  
15  
OUTPUT  
V
OUTPUT  
POWER  
LOAD  
http://www.m-system.co.jp/  
10EHZ SPECIFICATIONS  
ES-0844 Rev.2 Page 2/3  
MODEL: 10EHZ  
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)  
Terminals 8 through 11 are deleted.  
8 (.31)  
15–M3.5 SCREW  
2–4.3 (.17) dia.  
MTG HOLE  
TERMINAL COVER  
1
8
2
9
3
4
5
6
7
10 11  
12 13 14 15  
26 (1.02)  
50 (1.97)  
3 (.12)  
51 (2.01)  
130 (5.12)  
Specifications are subject to change without notice.  
http://www.m-system.co.jp/  
10EHZ SPECIFICATIONS  
ES-0844 Rev.2 Page 3/3  

相关型号:

10EHZ1

High Performance Power Line Filter for Medical Applications
TE

10EJH1

Enhanced Performance Compact Medical RFI Filter IEC Connector Package
TE

10EJH2

Enhanced Performance Compact Medical RFI Filter IEC Connector Package
TE

10EJH8

Enhanced Performance Compact Medical RFI Filter IEC Connector Package
TE

10EJHP

Enhanced Performance Compact Medical RFI Filter IEC Connector Package
TE

10EJHS1

Enhanced Performance Compact Medical RFI Filter IEC Connector Package
TE

10EJHS8

Enhanced Performance Compact Medical RFI Filter IEC Connector Package
TE

10EJM1

Cost-effective Medium Performance Power Inlet Filter
MACOM

10EJM8

Cost-effective Medium Performance Power Inlet Filter
MACOM

10EJMS1

Cost-effective Medium Performance Power Inlet Filter
MACOM

10EJMS8

Cost-effective Medium Performance Power Inlet Filter
MACOM

10EJS1

Enhanced Performance Snap-In Compact RFI Filter IEC Connector Package
TE