DRA-40-24 [MEANWELL]
UNIVERSAL AC INPUT/FULL RANGE;型号: | DRA-40-24 |
厂家: | MEAN WELL ENTERPRISES CO., LTD. |
描述: | UNIVERSAL AC INPUT/FULL RANGE 输入元件 |
文件: | 总5页 (文件大小:167K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
40W Single Output Switching Power Supply
DRA-40 series
Bauart gepruft
Sicherheit
egelma ge
o s
od
be wac
g
www.tuv.com
ID 2000000000
LPS
■ Features
■ Applications
ꢀUniversal AC input / Full range
ꢀProtections: Short circuit / Overload / Over voltage
ꢀCan be installed on DIN rail TS-35/7.5 or 15
ꢀOutput Voltage adjustable through internal potentiometer
ꢀOutput Current adjustable through external 1~10Vdc, PWM
signal or resistance
ꢀMachine vision inspection system
ꢀPlant cultivation system
ꢀCooling by free air convection
ꢀPass LPS
ꢀLED indicator for power on
ꢀ100% full load burn-in test
ꢀ3 years warranty
■ Description
DRA-40 is one 40W AC/DC DIN rail power supply, featuring the adjustable output current. Users are
able to easily change the constant output current level, via 1~10Vdc, PWM signal or resistance.
DRA-40 can be mounted on DIN rail TS-35/7.5 or 15; in addition, the width of the unit is only 40mm that
it is well suited for the installation in a limited spacing. DRA-40 accepts the universal AC input between
90VAC and 264VAC; the efficiency is up to 87% that the entire series can operate, under free air convection,
from -30℃ through 70℃.
■ Model Encoding
DRA - 40 - 12
Output voltage
Output wattage
Series name
File Name:DRA-40-SPEC 2015-06-11
40W Single Output Switching Power Supply
DRA-40 series
SPECIFICATION
MODEL
DRA-40-12
DRA-40-24
DC VOLTAGE
12V
24V
CONSTANT CURRENT REGION 3~12V
3~24V
1.7A
RATED CURRENT
CURRENT RANGE
RATED POWER
3.34A
0 ~ 3.34A
40.08W
0 ~ 1.7A
40.8W
150mVp-p
24 ~ 30V
1.0%
RIPPLE & NOISE (max.) Note.2 120mVp-p
OUTPUT VOLTAGE ADJ. RANGE
12 ~ 15V
1.0%
VOLTAGE TOLERANCE Note.3
LINE REGULATION
0.5%
0.5%
LOAD REGULATION
0.5%
0.5%
SETUP, RISE TIME Note.4 400ms, 90ms/230VAC
800ms, 90ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC
90 ~ 264VAC
47 ~ 63Hz
85%
10ms/115VAC at full load
127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
87%
INPUT
0.8A/115VAC
0.6A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC
60A/230VAC
95 ~ 108% rated output power
OVERLOAD
Protection type : Constant current limiting, recovers automatically after fault condition is removed
14.49 ~ 18.63V
28.98 ~ 37.26V
PROTECTION
ENVIRONMENT
OVER VOLTAGE
Protection type : Shut down o/p voltage, re-power on to recover
-30 ~ +70℃ (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-40 ~ +85℃, 10 ~ 95% RH
0.03%/℃ (0 ~ 55℃) on output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1, TUV EN60950-1 approved
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
SAFETY &
EMC
(Note 5)
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/ 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61204-3, light industry level, criteria A
439.3K hrs min. MIL-HDBK-217F (25℃)
MTBF
40*90*100mm (W*H*D)
OTHERS DIMENSION
PACKING
0.3Kg; 42pcs/13.6Kg/0.82CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
NOTE
4. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed
that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power
supplies. (as available on http://www.meanwell.com)
6. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded
permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
File Name:DRA-40-SPEC 2015-06-11
40W Single Output Switching Power Supply
DRA-40 series
Block Diagram
RECTIFIERS
RECTIFIERS
+V
-V
POWER
EMI
I/P
&
&
SWITCHING
FILTER
FILTER
FILTER
DIM+
O.C.P.
DIM-
DETECTION
CIRCUIT
FG
CONTROL
O.L.P.
O.V.P.
Derating Curve
Static Characteristics
100
90
80
70
60
50
40
100
80
230VAC
Input only
60
40
20
-30
-20
0
15
30
40
50 55 60
70
(VERTICAL)
90 100 125 135 145 155 165 175 180 200 230 264
INPUT VOLTAGE (V) 60Hz
AMBIENT TEMPERATURE (℃)
OUTPUT CURRENT ADJUSTMENT OPERATION
※ Built-in 3 in 1 current adjustment function . Output constant current level can be adjusted by applying 1 ~ 10Vdc, 10V PWM
signal or resistance between DIM+ and DIM-.
※ Please DO NOT connect "DIM-" to "-V".
※ Reference resistance value for output current adjustment (Typical)
Single Power supply
10KΩ 20KΩ 30KΩ 40KΩ 50KΩ 60KΩ 70KΩ 80KΩ 90KΩ 100KΩ
10KΩ/N 20KΩ/N 30KΩ/N 40KΩ/N 50KΩ/N 60KΩ/N 70KΩ/N 80KΩ/N 90KΩ/N 100KΩ/N
OPEN
-----
Resistance
value
Multiple Power supplies
(N=Power supply quantity for simultaneous
current adjustment control)
Percentage of rated current
10%
20%
30%
40%
50%
60%
70%
80%
90%
100% 102%~108%
※ 1 ~ 10Vdc for output current adjustment (Typical)
Applied Source
1V
2V
3V
4V
5V
6V
7V
8V
9V
10V
OPEN
Percentage of rated current
10%
20%
30%
40%
50%
60%
70%
80%
90% 100% 102%~108%
※ 10V PWM signal for output current adjustment (Typical): Frequency range :100Hz ~ 3KHz
Duty value
10%
10%
20%
20%
30%
30%
40%
40%
50%
50%
60%
60%
70%
70%
80%
80%
90% 100%
OPEN
Percentage of rated current
90% 100% 102%~108%
File Name:DRA-40-SPEC 2015-06-11
40W Single Output Switching Power Supply
DRA-40 series
Using the current adjustment function can not adjust the output current to 0A. Please refer to the connection method below to a
djust the output
※
current to 0A.
10K~100K Ohms resistance
1~10V DC Voltage
LOAD
10V PWM Signal
Adjuster
+V +V -V -V
DC OK
Switch
+
+V ADJ
Relay
N
L
L
FG N
DRIVING METHODS OF APPLICATIONS
The power supply may either work in "constant voltage mode or constant current mode"
In the constant current region, the highest voltage at the output of the driver
Rated
output
voltage
depends on the configuration of the end systems.
Should there be any compatibility issues, please contact MEAN WELL.
(B)
Constant
Current area
(A) Constant
Voltage area
3V
(C)
Hiccup
Protection
50
100
Io (%)
File Name:DRA-40-SPEC 2015-06-11
40W Single Output Switching Power Supply
DRA-40 series
Mechanical Specification
Case No.962A Unit:mm
100
40
5
5
5
5
5
+V +V -V -V
DC OK
+
+V ADJ
N
L
7.5 7.5
Installation Instruction
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the USER MANUAL on
http://www.meanwell.com/search/DRA-40/DRA_manual.pdf
(This diagram is for reference. The rail is not included with unit.)
Back View
File Name:DRA-40-SPEC 2014-10-22
相关型号: