POWR-GARD® FusesMediumVoltage  
MEDIUM VOLTAGE FUSES  
2,400-38,000 VAC • Current-Limiting  
Current-limiting E- and R-rated  
fuses are equipped with a  
mechanical indicator or striker pin  
that protrudes through the fuse cap  
upon operation of the fuse. This  
provides visual identification of a  
blown fuse and can be used as a  
trigger for external devices.  
Note: Extension distance 1 2” minimum;  
/
extension force 2 lb. minimum.  
General Information  
The terms “Medium Voltage” and “High Voltage” have been  
used interchangeably by many people to describe fuses  
operating above 600 volts. Technically speaking, medium  
voltage fuses are those intended for the voltage range from  
2,400 to 38,000 VAC. High voltage fuses are for circuits  
carrying voltages greater than 38,000 VAC.  
E-rated fuses are considered to be general purpose fuses and  
can be used to protect against low and high values of fault  
current. R-rated fuses are designed for back-up protection.  
They must be used in series with other devices such as motor  
overload relays in order to achieve both overload and short-  
circuit protection.  
Description  
Littelfuse® offers a selection of E- and R-rated medium voltage  
fuses for the protection of transformers, potential transformers,  
feeders, and motor circuits. Single, double, and triple barrel  
designs are available to cover a wide range of current, voltage,  
and interrupting ratings. Conventional ferrule type, clip lock,  
and bolt-in mounting configurations are available for virtually  
any application. Hermetically sealed fuses for use in hazardous  
environments are also offered.  
Medium voltage fuses are not intended to provide overload  
protection in the same sense as fuses rated 600 volts or less.  
Medium voltage fuse current ratings do not have the same  
meanings as the ampere ratings of low voltage fuses.  
All medium voltage fuses are limited in their ability to interrupt  
low value overcurrents, especially those between 100%  
and 200% of the fuse’s continuous current rating. They are  
designed to carry their rated current without exceeding the  
temperature rise permitted by NEMA and ANSI standards.  
Contact the factory or your local Littelfuse representative for  
additional fuse ratings or custom mounting configurations.  
24-Hour Emergency Service is available. Call 800-227-0029,  
Option 6.  
Applications  
•ꢀ PowerTransformer Protection  
•ꢀ PotentialTransformer Protection  
•ꢀ Motor Controller Back-up Protection  
•ꢀ Fused Switches  
•ꢀ Feeder Circuits  
1
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
R-RATED MEDIUM VOLTAGE FUSES  
Current-Limiting  
Description  
Characteristics  
R-rated fuses provide required short-circuit protection for medium  
voltage motors, motor controllers and associated circuitry. These  
components have limited ability to absorb the energy of large  
short-circuit currents. Medium voltage motor controllers contain  
overload relays which provide both overload protection and locked  
rotor protection to the motor. The controllers are also intended to  
interrupt low value short-circuits within the capability of the motor  
controller. This protects the medium voltage fuse from sustained  
overcurrents which are less than their minimum interrupting rating.  
Voltage Ratings:  
Current Range:  
2,750 V – 8,250 V  
2R – 36R  
Options  
•ꢀ Hermetically sealed for use in hazardous locations  
(add “S” suffix to part number)  
•ꢀ Bolt-in mounting configurations  
NEMA Standards for R-rated medium voltage power fuses  
require they operate within 15-35 seconds when subjected to  
an rms current 100 times the R rating. For example, a fuse with  
a 2R rating will open within 15 to 35 seconds on an applied  
current of 2 x 100 = 200 amperes.  
Hookeye Feature*  
For hookeye attachment; add “W” suffix  
to part number  
Part Number System 130-4R-1C-5.5  
*See web for Bolt Mount, Inverted Bolt Mount, and Bolt-W dimensions  
Max Voltage (KV)  
Style:  
C (Cartridge)  
B (Bolt Mount)  
IB (Inverted Bolt Mount)  
BI (Bolt-In Mount)  
No. of Barrels  
Rating (size)  
Medium Voltage  
Fuse Protection  
POWR-GARD® medium  
Continuous Current  
voltage fuses provide  
short-circuit protection  
for motors and  
transformers rated  
Dimensions  
6.38"  
9.75"  
3"DIA  
2,400 to 38,000 volts AC.  
Visit www.littelfuse.com/technicalcenter  
for additional protection tables, sizing  
recommendations, and applications.  
Dim.A  
Clip  
Dim.B  
Center  
Figure 1  
Figure 2  
Figure 3  
Cartridge “C”  
Inverted-Bolt “IB”  
Bolt Mount “B”  
Sample Part #: 130-4R-1B-5.5  
Bolt-In Mount “BI”  
Sample Part #: 130-4R-1IB-5.5  
Sample Part #: 130-4R-1BI-5.5  
2
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
R-RATED MEDIUM VOLTAGE FUSES  
Current-Limiting  
MAxIMUM  
MINIMUM  
MAxIMUM  
SySTEM/  
CONTINUOUS  
CURRENT @  
DIM. A  
(INChES)  
DIM. B  
(INChES)  
INTERRUPTING INTERRUPTING  
FIGURE  
NUMBER  
R
CATALOG  
NUMBER  
SIzE  
RATING RMS  
AMPS  
RATING RMS  
(ASyM)  
RATED  
40 DEGREES C°  
702R1C2.75  
1003R1C2.75  
1304R1C2.75  
1505R1C2.75  
1706R1C2.75  
2009R1C2.75  
23012R1C2.75  
39018R2C2.75  
45024R2C2.75  
2R  
3R  
70  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
170  
250  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
1
1
1
1
1
1
1
2
2
100  
130  
150  
170  
200  
230  
390  
450  
4R  
340  
5R  
390  
6R  
500  
9R  
760  
12R  
18R  
24R  
1000  
1500  
1950  
MAxIMUM  
CONTINUOUS  
CURRENT @  
MINIMUM  
MAxIMUM  
SySTEM/  
CATALOG  
NUMBER  
DIM. A  
(INChES)  
DIM. B  
(INChES)  
INTERRUPTING INTERRUPTING  
FIGURE  
NUMBER  
R
SIzE  
RATING RMS  
AMPS  
RATING RMS  
(ASyM)  
RATED  
40 DEGREES C°  
702R1C5.5  
1003R1C5.5  
1304R1C5.5  
1505R1C5.5  
1706R1C5.5  
2009R1C5.5  
23012R1C5.5  
39018R2C5.5  
45024R2C5.5  
48026R2C5.5  
55030R2C5.5  
60032R2C5.5  
65036R2C5.5  
55030R3C5.5  
60032R3C5.5  
65036R3C5.5  
2R  
3R  
4R  
5R  
6R  
70  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
170  
250  
340  
390  
500  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
1
1
1
1
1
1
1
2
2
2
2
2
2
3
3
3
100  
130  
150  
170  
200  
230  
390  
450  
480  
550  
600  
650  
550  
600  
650  
9R  
760  
12R  
18R  
24R  
26R  
30R  
32R  
36R  
30R  
32R  
36R  
1000  
1500  
1950  
2100  
2400  
2600  
2900  
2400  
2600  
2900  
MAxIMUM  
CONTINUOUS  
CURRENT @  
MINIMUM  
MAxIMUM  
SySTEM/  
CATALOG  
NUMBER  
DIM. A  
(INChES)  
DIM. B  
(INChES)  
INTERRUPTING INTERRUPTING  
FIGURE  
NUMBER  
R
SIzE  
RATING RMS  
AMPS  
RATING RMS  
(ASyM)  
RATED  
40 DEGREES C°  
702R1C5.5X  
1003R1C5.5X  
1304R1C5.5X  
1505R1C5.5X  
1706R1C5.5X  
2009R1C5.5X  
23012R1C5.5X  
39018R2C5.5X  
45024R2C5.5X  
55030R2C5.5X  
2R  
3R  
4R  
5R  
6R  
70  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14”  
17.875"  
17.875"  
17.875"  
17.875"  
17.875"  
17.875"  
17.875"  
17.875"  
17.875"  
17.875”  
170  
250  
340  
390  
500  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
1
1
1
1
1
1
1
2
2
2
100  
130  
150  
170  
200  
230  
390  
450  
550  
9R  
760  
12R  
18R  
24R  
30R  
1000  
1500  
1950  
2400  
MAxIMUM  
CONTINUOUS  
CURRENT @  
MINIMUM  
MAxIMUM  
SySTEM/  
CATALOG  
NUMBER  
DIM. A  
(INChES)  
DIM. B  
(INChES)  
INTERRUPTING INTERRUPTING  
FIGURE  
NUMBER  
R
SIzE  
RATING RMS  
AMPS  
RATING RMS  
(ASyM)  
RATED  
40 DEGREES C°  
702R1C8.25  
1003R1C8.25  
1304R1C8.25  
1505R1C8.25  
1706R1C8.25  
2009R1C8.25  
23012R1C8.25  
39018R2C8.25  
45024R2C8.25  
2R  
3R  
4R  
5R  
6R  
70  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
190  
225  
330  
440  
500  
740  
955  
1440  
1910  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
1
1
1
1
1
1
1
2
2
100  
130  
150  
170  
200  
230  
390  
450  
9R  
12R  
18R  
24R  
For hookeye attachment; add “W” suffix to part number  
3
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
E-RATED MEDIUM VOLTAGE FUSES  
Current-Limiting  
Description  
Characteristics  
E-rated fuses have time current characteristics designed to  
provide current-limiting protection for power transformers,  
potential transformers, power centers, feeder centers, and unit  
sub stations. When properly applied, they can protect against  
high and low fault currents.  
Voltage Ratings:  
Current Range:  
2,750 V – 38,000 V  
10E – 600E  
Options  
•ꢀ Hermetically sealed for use in hazardous locations  
NEMA Standards for E-rated medium voltage fuses require that  
fuses rated 100E or less open within 300 seconds  
(add “S” suffix to part number)  
•ꢀ Clip-lock (CL) and bolt-in styles available.  
(5 minutes) when subjected to an RMS value of 200-240% of  
the fuse continuous current rating; and fuses with an  
E rating larger than 100E must open within 600 seconds  
(10 minutes) when subjected to an RMS current of 220-240%  
of the fuse’s continuous current rating. These values establish  
one point on the time-current curve.  
Dimensions  
6.38"  
9.75"  
3"DIA  
Application Note  
Since these fuses are used for the protection of general  
purpose circuits which may contain transformers, motors, and  
other equipment producing in-rush and/or overload currents,  
fuses should generally be rated at 140% of the normal full load  
current, and circuits should be analyzed  
Dim.A  
Clip  
Center  
Dim.B  
to ensure that system load currents will not exceed the current  
rating of the fuse.  
Figure 4  
Figure 5  
Figure 6  
SySTEM/CATALOG  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
NUMBER  
E
SIzE  
DIM. A (INChES) DIM. B (INChES)  
NUMBER  
RATED  
10E1C2.75  
15E1C2.75  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
125E  
150E  
200E  
125E  
150E  
200E  
225E  
250E  
300E  
350E  
400E  
450E  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
7"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
10.875"  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
5
20E1C2.75  
25E1C2.75  
30E1C2.75  
40E1C2.75  
50E1C2.75  
65E1C2.75  
80E1C2.75  
100E-1C2.75  
125E1C2.75  
150E1C2.75  
200E1C2.75  
125E2C2.75  
150E2C2.75  
200E2C2.75  
225E2C2.75  
250E2C2.75  
300E2C2.75  
350E2C2.75  
400E2C2.75  
450E2C2.75  
4
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
E-RATED MEDIUM VOLTAGE FUSES  
Current-Limiting  
SySTEM/CATALOG  
MAx INTERRUPTING  
RATING RMS (ASyM)  
E
SIzE  
DIM. A (INChES) DIM. B (INChES)  
FIGURE NUMBER  
NUMBER  
RATED  
10E1C5.5  
15E1C5.5  
20E1C5.5  
25E1C5.5  
30E1C5.5  
40E1C5.5  
50E1C5.5  
65E1C5.5  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
125E  
150E  
175E  
200E  
125E  
150E  
175E  
200E  
250E  
300E  
350E  
400E  
450E  
500E  
550E  
600E  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
15.875"  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
5
5
6
6
6
80E1C5.5  
100E1C5.5  
125E1C5.5  
150E1C5.5  
175E1C5.5  
200E1C5.5  
125E2C5.5  
150E2C5.5  
175E2C5.5  
200E2C5.5  
250E2C5.5  
300E2C5.5  
350E2C5.5  
400E2C5.5  
450E2C5.5  
500E3C5.5  
550E3C5.5  
600E3C5.5  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
E
SIzE  
DIM. A (INChES) DIM. B (INChES)  
FIGURE NUMBER  
RATED  
7
8
5NLE10E  
5NLE15E  
5NLE20E  
5NLE25E  
5NLE30E  
5NLE40E  
5NLE50E  
5NLE65E  
5NLE80E  
5NLE100E  
5NLE125E  
5NLE150E  
5NLE175E  
5NLE200E  
5NLE2225E  
5NLE2250E  
5NLE2300E  
5NLE2350E  
5NLE2400E  
5NLE2450E  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
125E  
150E  
175E  
200E  
225E  
250E  
300E  
350E  
400E  
450E  
14”  
14”  
14”  
14”  
14”  
14”  
14”  
14”  
14”  
14”  
14“  
14”  
14”  
14”  
14”  
14”  
14”  
14”  
14”  
14”  
17 ⁄ "  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
4
4
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
5
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
E-RATED MEDIUM VOLTAGE FUSES  
Current-Limiting  
SySTEM/CATALOG  
MAx INTERRUPTING  
RATING RMS (ASyM)  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
FIGURE NUMBER  
NUMBER  
RATED  
7
8
10E1C8.25  
15E1C8.25  
20E1C8.25  
25E1C8.25  
30E1C8.25  
40E1C8.25  
50E1C8.25  
65E1C8.25  
80E1C8.25  
100E1C8.25  
125E1C8.25  
150E1C8.25  
125E2C8.25  
150E2C8.25  
200E2C8.25  
250E2C8.25  
300E2C8.25  
350E3C8.25  
400E3C8.25  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
125E  
150E  
125E  
150E  
200E  
250E  
300E  
350E  
400E  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
12"  
15 ⁄ "  
80,000,  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
4
4
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
6
6
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
7
8
15 ⁄ "  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
FIGURE NUMBER  
RATED  
7
8
8NLE10E  
8NLE15E  
8NLE20E  
8NLE25E  
8NLE30E  
8NLE40E  
8NLE50E  
8NLE65E  
8NLE80E  
8NLE100E  
8NLE2100E  
8NLE2125E  
8NLE2150E  
8NLE2200E  
8NLE2250E  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
100E  
125E  
150E  
200E  
250E  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
14"  
17 ⁄ "  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
7
8
17 ⁄ "  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
FIGURE NUMBER  
RATED  
10E1C15.5  
15E1C15.5  
20E1C15.5  
25E1C15.5  
30E1C15.5  
40E1C15.5  
50E1C15.5  
65E1C15.5  
80E1C15.5  
100E1C15.5  
65E2C15.5  
80E2C15.5  
100E2C15.5  
125E2C15.5  
150E2C15.5  
175E2C15.5  
200E2C15.5  
200E3C15.5  
250E3C15.5  
300E3C15.5  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
15"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
18.875"  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
5
6
6
6
100E  
65E  
80E  
100E  
125E  
150E  
175E  
200E  
200E  
250E  
300E  
6
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
E-RATED MEDIUM VOLTAGE FUSES  
Current-Limiting  
SySTEM/CATALOG  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
NUMBER  
NUMBER  
RATED  
7
8
15GSE65E  
15GSE80E  
65E  
80E  
18"  
18"  
18"  
18"  
18"  
18"  
18"  
21 ⁄ "  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
4
4
4
5
5
5
5
7
8
21 ⁄ "  
7
8
15GSE100E  
15GSE2125E  
15GSE2150E  
15GSE2175E  
15GSE2200E  
100E  
125E  
150E  
175E  
200E  
21 ⁄ "  
7
8
21 ⁄ "  
7
8
21 ⁄ "  
7
8
21 ⁄ "  
7
8
21 ⁄ "  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
NUMBER  
RATED  
7
8
15NLE10E  
15NLE15E  
15NLE20E  
15NLE25E  
15NLE30E  
15NLE40E  
15NLE50E  
15NLE65E  
15NLE80E  
15NLE100E  
15NLE280E  
15NLE2100E  
15NLE2125E  
15NLE2150E  
15NLE2175E  
15NLE2200E  
15NLE3150E  
15NLE3175E  
15NLE3250E  
15NLE3300E  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
20"  
23 ⁄ "  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
4
4
4
4
4
4
4
4
4
4
5
5
5
5
5
5
6
6
6
6
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
100E  
80E  
23 ⁄ "  
7
8
23 ⁄ "  
7
8
100E  
125E  
150E  
175E  
200E  
150E  
175E  
250E  
300E  
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
7
8
23 ⁄ "  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
NUMBER  
RATED  
5
8
15E1C25.8  
20E1C25.8  
25E1C25.8  
30E1C25.8  
40E1C25.8  
50E1C25.8  
65E2C25.8  
80E2C25.8  
100E2C25.8  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
21"  
21"  
21"  
21"  
21"  
21"  
21"  
21"  
21"  
24 ⁄ "  
40,000  
40,000  
40,000  
40,000  
40,000  
40,000  
40,000  
40,000  
40,000  
4
4
4
4
4
4
5
5
5
5
8
24 ⁄ "  
5
8
24 ⁄ "  
5
8
24 ⁄ "  
5
8
24 ⁄ "  
5
8
24 ⁄ "  
5
8
24 ⁄ "  
5
8
24 ⁄ "  
5
8
24 ⁄ "  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
NUMBER  
RATED  
5
8
3E1C38.0  
7E1C38.0  
3E  
7E  
27"  
27"  
27"  
27"  
27"  
27"  
27"  
27"  
27"  
27"  
27"  
30 ⁄ "  
20,000  
20,000  
20,000  
20,000  
20,000  
20,000  
20,000  
20,000  
20,000  
20,000  
20,000  
4
4
4
4
4
4
4
4
5
5
5
5
8
30 ⁄ "  
5
8
10E1C38.0  
15E1C38.0  
20E1C38.0  
25E1C38.0  
30E1C38.0  
40E1C38.0  
50E2C38.0  
65E2C38.0  
80E2C38.0  
10E  
15E  
20E  
25E  
30E  
40E  
50E  
65E  
80E  
30 ⁄ "  
5
8
30 ⁄ "  
5
8
30 ⁄ "  
5
8
30 ⁄ "  
5
8
30 ⁄ "  
5
8
30 ⁄ "  
5
8
30 ⁄ "  
5
8
30 ⁄ "  
5
8
30 ⁄ "  
7
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
E-RATED MEDIUM VOLTAGE FUSES  
Current-Limiting  
Dimensions in inches  
4.75  
7.94  
11.56  
Clip Lock Design  
1.25  
1.25  
A
B
The clip lock type designs ensures a positive contact between  
the fuse and the connection cam. The fuse’s clip lock tab slides  
in between the clip casting and the cam to prevent the fuse  
from slipping or blowing out of the holder. This positive contact  
improves heat dissipation and allows fuses to run cooler.  
.25  
3.0  
Figure 7  
Figure 8  
Figure 9  
SySTEM/CATALOG  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
NUMBER  
NUMBER  
RATED  
10E1CL5.5  
15E1CL5.5  
20E1C5.5  
10E  
15E  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
16.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
15.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
7
7
7
7
7
7
7
7
7
7
7
7
8
8
8
8
8
8
9
9
9
20E  
25E1CL5.5  
30E1CL5.5  
40E1CL5.5  
50E1CL5.5  
65E1CL5.5  
80E1CL5.5  
100E1CL5.5  
125E1CL5.5  
150E1CL5.5  
225E2CL5.5  
250E2CL5.5  
300E2CL5.5  
350E2CL5.5  
400E2CL5.5  
450E2CL5.5  
500E3CL5.5  
550E3CL5.5  
600E3CL5.5  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
125E  
150E  
225E  
250E  
300E  
350E  
400E  
450E  
500E  
550E  
600E  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
NUMBER  
RATED  
10E1CL8.25  
15E1CL8.25  
20E1C8.25  
10E  
15E  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
17.38"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
16.13"  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
80,000  
7
7
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
9
20E  
25E1CL8.25  
30E1CL8.25  
40E1CL8.25  
50E1CL8.25  
65E1CL8.25  
80E1CL8.25  
100E1CL8.25  
125E2CL8.25  
150E2CL8.25  
175E2CL8.25  
200E2CL8.25  
225E2CL8.25  
250E2CL8.25  
300E2CL8.25  
350E3CL8.25  
25E  
30E  
40E  
50E  
65E  
80E  
100E  
125E  
150E  
175E  
200E  
225E  
250E  
300E  
350E  
SySTEM/CATALOG  
NUMBER  
MAx INTERRUPTING  
RATING RMS (ASyM)  
FIGURE  
E
SIzE  
DIM. A (INChES)  
DIM. B (INChES)  
NUMBER  
RATED  
10E1CL15.5  
15E1CL15.5  
20E1CL15.5  
25E1CL15.5  
30E1CL15.5  
40E1CL15.5  
50E1CL15.5  
65E1CL15.5  
80E1CL15.5  
100E1CL15.5  
125E2CL15.5  
150E2CL15.5  
175E2CL15.5  
200E2CL15.5  
150E3CL15.5  
200E3CL15.5  
250E3CL15.5  
300E3CL15.5  
10E  
15E  
19.8"  
19.8"  
18.1"  
18.1"  
18.1"  
18.1"  
18.1"  
18.1"  
18.1"  
21.13"  
21.13"  
21.13"  
19.1"  
19.1”  
19.1"  
19.1”  
19.1"  
19.1"  
19.1"  
19.1"  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
60,000  
7
7
7
7
7
7
7
7
7
7
8
8
8
8
9
9
9
9
20E  
19.8"  
25E  
19.8"  
30E  
19.8"  
40E  
19.8"  
50E  
19.8"  
65E  
22.81"  
22.81"  
22.81"  
22.81"  
22.81”  
22.81"  
22.81”  
22.81"  
22.81"  
22.81"  
22.81"  
80E  
100E  
125E  
150E  
175E  
200E  
150E  
200E  
250E  
300E  
8
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
®
Fuses — MediumVoltage  
POWR-GARD FusesMediumVoltage  
E-RATED POTENTIAL TRANSFORMER FUSES  
Current-Limiting  
Characteristics  
Description  
Potential Transformer (PT) fuses are current-limiting fuses with  
high interrupting ratings designed for the protection of potential  
transformers.  
Voltage Ratings:  
Current Range:  
625 VAC – 25,800 VAC  
1/2E – 10E  
Application Note  
Dimensions  
When applying fuses for the protection of transformers,  
the magnetizing current in-rush must be considered. The  
characteristics of the in-rush, which can be matched with  
a fuse time-current curve, should be available from the  
transformer manufacturer.  
B
A
SySTEM/CATALOG  
NUMBER  
DIMENSION A  
DIAMETER DIMENSION B  
(INChES)  
MAx INTERRUPTING  
RATING RMS (SyM)  
E
SIzE  
(INChES)  
RATED  
3E4PT6  
5E4PT6  
7E4PT6  
10E4PT6  
500E4PT2.4  
1E4PT2.4  
3E  
5E  
7E  
10E  
1/2E  
1E  
4.6”  
4.6”  
4.6”  
4.6”  
4.6”  
4.6”  
0.8125”  
0.8125”  
0.8125”  
0.8125”  
0.8125”  
0.8125”  
37,500  
37,500  
37,500  
37,500  
37,500  
37,500  
2E4PT2.4  
2E  
4.6”  
0.8125”  
37,500  
1E6PT2.75  
2E6PT2.75  
3E6PT2.75  
1E8PT2.75  
2E8PT2.75  
3E8PT2.75  
1E  
2E  
3E  
1E  
2E  
3E  
7.4”  
7.4”  
7.4”  
9.5”  
9.5”  
9.5”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
37,500  
37,500  
37,500  
37,500  
37,500  
37,500  
1E5PT4.8  
1E  
5.6”  
0.8125”  
50,000  
2E5PT4.8  
2E  
5.6”  
0.8125”  
50,000  
1/2E6PT5.5  
1E6PT5.5  
2E6PT5.5  
3E6PT5.5  
5E6PT5.5  
1/2E8PT5.5  
1E8PT5.5  
2E8PT5.5  
3E8PT5.5  
5E8PT5.5  
10E8PT5.5  
1/2E8PT8.25  
1E8PT8.25  
2E8PT8.25  
3E8PT8.25  
1/2E11PT15.5  
1E11PT15.5  
2E11PT15.5  
3E11PT15.5  
3E16PT15.5  
5E16PT15.5  
1/2E  
1E  
2E  
3E  
5E  
1/2E  
1E  
2E  
3E  
5E  
10E  
1/2E  
1E  
2E  
3
1/2E  
1E  
2E  
3E  
3E  
7.4”  
7.4”  
7.4”  
7.4”  
7.4”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
1.5625”  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
50,000  
35,000  
35,000  
35,000  
35,000  
35,000  
35,000  
9.5”  
9.5”  
9.5”  
9.5”  
9.5”  
9.5”  
9.5”  
9.5”  
9.5”  
9.5”  
12.8”  
12.8”  
12.8”  
12.8”  
17.5”  
17.5”  
5E  
1/2E16PT25.5  
1/2E  
17.5”  
1.5625”  
32,000  
1E16PT25.5  
1E  
17.5”  
1.5625”  
32,000  
9
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  
POWR-GARD® FusesMediumVoltage  
LIVE PARTS  
Description  
Live parts are available for mounting E, R, and PT single, double, and triple barrel fuses.  
Mounting clips are available for ferrule type and clip lock style fuses.  
All clips are sold in pairs.  
Part Number: 700-156  
Part Number: 700-300  
System Number: 0700156.Z  
System Number: 0700300.Z  
For use with 3" diameter fuses.  
9
5
8
For use with 1 /16" to 1 / ” (1.625”) diameter PT fuses.  
Dimensions in inches  
Dimensions in inches  
Part Number: 700-500  
Part Number: 700-530  
System Number: 0700530.Z  
For use with all 3" diameter fuses.  
.08  
System Number: 0700500.Z  
For use with all 13/16" (.8125”) diameter PT fuses  
Dimensions in inches  
Dimensions in inches  
.31  
.71  
.30  
.78  
.038" HOLES  
.08  
1.50  
4.50  
1.15  
.05  
3.08  
4.16  
.78  
.63  
Part Number: 700-520-CL  
System Number: 0700520.ZXCL  
Clip Lock Design  
Mounting Details for Clip Lock Dimensions in inches  
TRIPLE BARREL  
3.63  
DOUBLE BARREL  
Bottom Lever In  
Closed Position  
3.63  
4.85  
SINGLE BARREL  
1.75  
Blown Fuse  
Indicator  
1.00  
A
2.00  
4.9  
.56 Dia. (2) Holes  
For Mounting  
Cable/Bus  
3.75 2.00  
Top Lever in  
Open Position  
2.00  
TOP  
VIEW  
Dimensions for reference only.  
.44 DIA. (2) HOLES  
10  
www.littelfuse.com  
© JUNE 2011 Littelfuse POWR-GARD Products  

相关型号:

125E2C5.5

ELECTRIC FUSE
LITTELFUSE

125E2C8.25

MEDIUM VOLTAGE FUSES
LITTELFUSE

125E2CL15.5

MEDIUM VOLTAGE FUSES
LITTELFUSE

125E2CL8.25

MEDIUM VOLTAGE FUSES
LITTELFUSE

125ECAY

Visible LED, Transparent,
VCC

125EWAY

Visible LED, Water Clear,
VCC

125F-R05-JBQ

Fixed Resistor, Wire Wound,
RCD

125FPA122K

Axial Leaded Impregnated Polypropylene Film with Aluminum Foil Electrodes
ILLINOISCAPAC

125FPA850K

Axial Leaded Impregnated Polypropylene Film with Aluminum Foil Electrodes
ILLINOISCAPAC

125FPF102K

Oval Leaded Polypropylene Film with Aluminum Foil Electrodes
ILLINOISCAPAC

125FPF122K

Oval Leaded Polypropylene Film with Aluminum Foil Electrodes
ILLINOISCAPAC

125FPF850K

Oval Leaded Polypropylene Film with Aluminum Foil Electrodes
ILLINOISCAPAC