LF305-S_06 [LEM]

Current Transducer; 电流传感器
LF305-S_06
型号: LF305-S_06
厂家: LEM    LEM
描述:

Current Transducer
电流传感器

传感器
文件: 总3页 (文件大小:185K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Current Transducer LF 305-S  
IPN = 300 A  
For the electronic measurement of currents: DC, AC, pulsed...,  
with a galvanic isolation between the primary circuit (high power)  
and the secondary circuit (electronic circuit).  
16167  
Electricaldata  
IPN  
IPM  
RM  
Primary nominal current rms  
Primary current, measuring range  
Measuring resistance  
300  
0 .. ± 500  
RM mini  
A
A
Features  
RM maxi  
· Closed loop (compensated) current  
transducer using the Hall effect  
· Isolated plastic case recognized  
according to UL 94-V0.  
with ± 12 V  
with ± 15 V  
with ± 20 V  
@ ± 300 A max  
0
0
0
0
15  
15  
39  
12  
58  
22  
93  
45  
W
W
W
W
W
W
@ ± 500 A max  
@ ± 300 A max  
@ ± 500 A max  
@ ± 300 A max  
@ ± 500 A max  
Advantages  
· Excellent accuracy  
· Very good linearity  
ISN  
KN  
VC  
IC  
Secondary nominal current rms  
Conversion ratio  
Supply voltage (± 5 %)  
Current consumption  
150  
1 : 2000  
± 12 .. 20  
26 (@±20V)+IS mA  
mA  
· Low temperature drift  
· Optimized response time  
· Wide frequency bandwidth  
· No insertion losses  
· High immunity to external  
interference  
V
Accuracy - Dynamic performance data  
X
Overall accuracy @ IPN , TA = 25°C  
Linearity error  
± 0.4  
< 0.1  
%
%
eG  
· Current overload capability.  
L
Typ Maxi  
Applications  
IO  
Offset current @ IP = 0, TA = 25°C  
± 0.20 mA  
IOM  
Magnetic offset current1) @ IP = 0 and specified RM,  
after an overload of 3 x IPN  
· AC variable speed drives and servo  
motor drives  
· Static converters for DC motor drives  
· Battery supplied applications  
· Uninterruptible Power Supplies  
(UPS)  
± 0.08 mA  
± 0.1 ± 0.30 mA  
IOT  
tra  
Temperature variation of IO  
- 10°C .. + 70°C  
Reaction time @ 10 % of IPN  
Response time 2) to 90 % of IPN step  
< 500  
< 1  
ns  
µs  
t
r
di/dt di/dt accurately followed  
BW Frequency bandwidth (- 1 dB)  
> 100  
DC .. 100  
A/µs  
kHz  
· Switched Mode Power Supplies  
(SMPS)  
· Power supplies for welding  
applications.  
General data  
TA  
TS  
RS  
m
Ambient operating temperature  
Ambient storage temperature  
Secondary coil resistance @ TA = 70°C  
- 10 .. + 70  
- 25 .. + 85  
25  
°C  
°C  
W
g
Applicationdomain  
Mass  
95  
· Industrial.  
Standards  
EN 50178: 1997  
1)  
Notes:  
The result of the coercive field of the magnetic circuit  
With a di/dt of 100 A/µs.  
2)  
page1/3  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.  
www.lem.com  
061031/7  
Current Transducer LF 305-S  
Isolationcharacteristics  
Vd  
Rms voltage for AC isolation test, 50/60 Hz, 1 mn  
Impulse withstand voltage 1.2/50 µs  
3.8  
10  
kV  
kV  
V
w
dCp  
dCl  
CTI  
Creepage distance  
Clearance distance  
Comparative Tracking Index (Group II)  
11.9  
11.5  
175  
mm  
mm  
Applicationexamples  
According to EN 50178 and IEC 61010-1 standardsand following conditions:  
· Over voltage category OV 3  
· Pollution degree PD2  
· Non-uniform field  
EN 50178  
Rated isolation voltage  
1000 V  
IEC 61010-1  
Nominal voltage  
1000 V  
V
dCp, dCI,  
W
Single isolation  
Reinforced isolation  
500 V  
500 V  
Safety  
This transducer must be used in electric/electronic equipment with respect to  
applicable standards and safety requirements in accordance with the manufacturer's  
operating instructions.  
Caution, risk of electrical shock  
When operating the transducer, certain parts of the module can carry hazardous  
voltage (eg. primary busbar, power supply).  
Ignoring this warning can lead to injury and/or cause serious damage.  
This transducer is a built-in device, whose conducting parts must be inaccessible  
after installation.  
A protective housing or additional shield could be used.  
Main supply must be able to be disconnected.  
page2/3  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.  
www.lem.com  
061031/7  
Dimensions LF 305-S (in mm. 1 mm = 0.0394 inch)  
Connection  
Bottom view  
Right view  
Back view  
Top view  
Mechanicalcharacteristics  
Remarks  
· General tolerance  
· Transducer fastening  
Vertical position  
± 0.5 mm  
· IS is positive when IP flows in the direction of the arrow  
· Temperature of the primary conductor should not exceed  
100°C  
2 holes Æ 4.3 mm  
2 steel screws M4  
Recommended fastening torque 3.2 Nm or 2.37 Lb.-Ft.  
4 holes Æ 1.9 mm, depth : 7 mm  
4screwsPTKA25, length:6mm  
Recommended fastening torque 0.7 Nm or 0.52 Lb.-Ft.  
· Dynamic performances (di/dt and response time) are best  
with a single bar completely filling the primary hole  
· This is a standard model. For different versions (supply  
voltages, turns ratios, unidirectional measurements...),  
please contact us.  
or  
Flat lying position  
4 holes Æ 4.3 mm  
4 steel screws M4  
Recommended fastening torque 2.9 Nm or 2.14 Lb.-Ft.  
or  
4 holes Æ 1.9 mm, crossing  
4 screws PTKA 25, length:10 mm  
Recommended fastening torque 0.75 Nm 0.55 Lb.-Ft.  
· Primary through-hole  
Æ 20 mm  
· Connection of secondary  
Molex5045-03/A  
page3/3  
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.  
www.lem.com  
061031/7  

相关型号:

LF305RU

Very Wide Input, 3W SMT Single & Dual Output DC/DC Converters
MPD

LF305RW

Wide Input, 3W SMT Single & Dual Output DC/DC Converters
MPD

LF306RU

Very Wide Input, 3W SMT Single & Dual Output DC/DC Converters
MPD

LF306RW

Wide Input, 3W SMT Single & Dual Output DC/DC Converters
MPD

LF307RU

Very Wide Input, 3W SMT Single & Dual Output DC/DC Converters
MPD

LF307RW

Wide Input, 3W SMT Single & Dual Output DC/DC Converters
MPD

LF30AB

VERY LOW DROP VOLTAGE REGULATORS WITH INHIBIT
STMICROELECTR

LF30ABDT

VERY LOW DROP VOLTAGE REGULATORS WITH INHIBIT
STMICROELECTR

LF30ABDT-TR

Very low drop voltage regulators with inhibit
STMICROELECTR

LF30ABP

VERY LOW DROP VOLTAGE REGULATORS WITH INHIBIT
STMICROELECTR

LF30ABPT

VERY LOW DROP VOLTAGE REGULATORS WITH INHIBIT
STMICROELECTR

LF30ABPT-TR

Very low drop voltage regulators with inhibit
STMICROELECTR