HTB150-P [LEM]
Current Transducer HTB 50 .. 400 - P and HTB 50 .. 100 - TP;![HTB150-P](http://pdffile.icpdf.com/pdf2/p00333/img/icpdf/HTB150-P_2049818_icpdf.jpg)
型号: | HTB150-P |
厂家: | ![]() |
描述: | Current Transducer HTB 50 .. 400 - P and HTB 50 .. 100 - TP |
文件: | 总3页 (文件大小:551K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
Current Transducer HTB 50 .. 400 - P
and HTB 50 .. 100 - TP
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
IPN = 50 .. 400 A
Electrical data
Primary nominal
current rms
IPN (A)
Primary current
measuring range
IPM (A)
Type
Features
± 50
± 150
± 300
± 450
± 500
± 600
± 600
HTB 50-P, HTB 50-TP1)
HTB 100-P, HTB 100-TP1)
HTB 150-P
HTB 200-P
HTB 300-P
● Hall effect measuring principle
● Galvanic isolation between
primary and secondary circuit
● Isolation voltage 2500 V
● Low power consumption
● Wide power supply: ± 12 ..15 V
● Primary bus bar option for 50
A and 100 A version for ease of
connection
± 100
± 150
± 200
± 300
± 400
HTB 400-P
VC
IC
Supply voltage (± 5 %)2)
Current consumption
± 12 ..15
± 15
2.5
> 500
± 4
100
> 10
V
mA
kV
MW
V
Vd
Rms voltage for AC isolation test, 50 Hz, 1 min
Isolation resistance @ 500 VDC
Output voltage (Analog)@ ± IPN, RL = 10kW, TA = 25°C
Output internal resistance
RIS
VOUT
ROUT
RL
Advantages
W
kW
Load resistance
● Small size and space saving
● Only one design for wide current
ratings range
Accuracy - Dynamic performance data
● High immunity to external
interference.
X
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (0 .. ± IPN)
Electrical offset voltage @ TA = 25°C
Hysteresis offset voltage @ IP = 0;
< ± 1
< ± 1
< ± 30
% of IPN
% of IPN
mV
e
L
Applications
VOE
VOH
● AC variable speed drives
● Static converters for DC motor
drives
● Battery supplied applications
● Uninterruptible Power Supplies
(UPS)
after an excursion of 1 x IPN < ± 1
% of IPN
mV/K
mV/K
%/K
TCVOE Temperature coefficient of VOE HTB 50-(T)P
HTB 100-(T)P .. 400-P
TCVOUT Temperature coefficient of VOUT (% of reading)
tr
BW
< ± 2.0
< ± 1.0
< ± 0.1
< 3
Response time to 90% of IPN step
Frequency bandwidth (- 3 dB)3)
µs
kHz
DC .. 50
● Switched Mode Power Supplies
(SMPS)
General data
● Power supplies for welding
applications
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Standards
- 40 .. + 80
- 40 .. + 85
< 30 ( < 36)
EN 50178 :
°C
°C
g
Application domain
● Industrial
1997
2 pins of Ø2mm diameter are available on transducer
for PCB soldering
Notes : 1) -TP version is equipped with a primary bus bar.
2) Operating at ±12V ≤ Vc < ±15V will reduce the measuring range.
3) Derating is needed to avoid excessive core heating at high frequency.
Page 1/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
120425/12
www.lem.com
Current Transducer HTB 50 .. 400-P and HTB 50 .. 100-TP
Isolation characteristics
Vd
Ve
Vw
Rms voltage for AC isolation test, 50 Hz, 1 min
Partial discharge extinction voltage rms @ 10pC
Impulse withstand voltage 1.2/50 µs
2.5
> 500
4
kV
V
kV
dCp
dCl
CTI
Creepage distance
Clearance distance
Comparative tracking index (Group IIIa)
> 4.5
> 4.5
275
mm
mm
Application examples
According to EN 50178 and CEI 61010-1 standards and following conditions :
- Over voltage category III
- Pollution degree 2
- Heterogeneous field
EN 50178
IEC 61010-1
Single isolation
300 V
150 V
300 V
150 V
Reinforced isolation
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
120425/12
www.lem.com
Dimensions HTB 50 .. 400-P and HTB 50 .. 100-TP (in mm. 1 mm = 0.0394 inch)
Page 3/3
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
120425/12
www.lem.com
相关型号: