060UR2D1100B [IXYS]
Electric Fuse, 1100A, 600VAC, 600VDC, 200000A (IR), Inline/holder;![060UR2D1100B](http://pdffile.icpdf.com/pdf2/p00291/img/icpdf/060UR2D1100B_1764985_icpdf.jpg)
型号: | 060UR2D1100B |
厂家: | ![]() |
描述: | Electric Fuse, 1100A, 600VAC, 600VDC, 200000A (IR), Inline/holder 电路保护 |
文件: | 总8页 (文件大小:648K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
WESTCODE An IXYS Company
German Standard DIN 110 690V
Date:- 18 Mar, 2005
Data Sheet Issue:- 1
Ultra Rapid
Semiconductor Protection Fuse
European Square Body Fuses
German Standard DIN 110 Blade Contact
Voltage Ratings 600V to 690V
Current Ratings 63A to 1600A
Sizes 0, 1, 2, 3
Key Features:
Extremely high interrupting rating fuses for the protection of power semiconductors in accordance
with IEC Standard 60269.1 and 4.
Exceptionally low I2t, power losses
Highly reliable low voltage trip indicator system which conforms to UL, IEC, DIN and VDE standards
Non Magnetic construction
Increased technical performance gives higher ratings and a reduction in volume and weight
Microswitch system reference : MS 3V 1-5
Fuse holder types : SI DIN80 630A or SI DIN80 1250A
Data Sheet: 069URxDxxxxB Issue 1
Page 1 of 8
March, 2005
WESTCODE An IXYS Company
German Standard DIN 110 690V
Main Characteristics:
Current
rating
IN(A)
63
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Tested
Interrupting
rating
Total Clearing
I2t @ UN (kA2s)
Watt Losses
Size
Voltage
Ref:
0.8IN
IN
069UR0D0063B
069UR0D0080B
069UR0D0100B
069UR0D0125B
069UR0D0160B
069UR0D0200B
069UR0D0250B
069UR0D0315B
069UR0D0350B
069UR0D0400B
069UR0D0450B
069UR0D0500B
069UR0D0550B
0.2
0.33
0.47
0.85
1.6
3.
1.1
1.8
7.5
14
19
26
30
37
43
50
55
60
65
88
88
90
80
9.5
13.0
15.0
18.5
21.5
25
100
125
160
200
250
315
350
400
450
500
550
2.50
4.50
8.5
690V
15.5
30
0
5.8
12
200kA @690V
62
22.5
30
15.5
23
80
120
150
240
300
32.5
44
26
690V
+6%
41
44
-
52
45
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch Reference : MS 3V 1-5
Current
rating
IN(A)
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Tested
Interrupting
rating
Total Clearing
I2t @ UN (kA2s)
Watt Losses
Size
Voltage
Ref:
0.8IN
IN
160
069UR1D0160B
069UR1D0200B
069UR1D0315B
069UR1D0315B
069UR1D0350B
069UR1D0400B
069UR1D0450B
069UR1D0500B
069UR1D0550B
069UR1D0630B
069UR1D0700B
1.3
2.6
4.7
7.5
10.5
19
7
27.5
35
45
52
65
67
68
70
72
75
85
95
200
250
315
350
400
450
500
550
630
700
13.5
25
22.5
25.5
32.5
33.5
34
40
55
200kA @690V
1
690V
100
140
195
280
390
490
26.5
37
35
36
52
37.5
42.5
42.5
75
95
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch Reference : MS 3V 1-5
Data Sheet: 069URxDxxxxB Issue 1
Page 2 of 8
March, 2005
WESTCODE An IXYS Company
German Standard DIN 110 690V
Current
rating
IN(A)
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Tested
Interrupting
rating
Total Clearing
I2t @ UN (kA2s)
Watt Losses
Size
Voltage
Ref:
0.8IN
IN
400
069UR2D0400B
069UR2D0450B
069UR2D0500B
069UR2D0550B
069UR2D0630B
069UR2D0700B
069UR2D0800B
069UR2D0900B
069UR2D1000B
060UR2D1100B
15
20
80
115
145
195
280
400
600
900
1250
1450
32.5
75
80
450
500
550
630
700
800
900
1000
1100
40
45
28
90
690V
37
47.5
52.5
55
95
54
105
110
120
125
135
165
200kA @660V
200kA @600V
2
76
115
170
240
270
60
690V
+6%
62.5
67.5
82.5
600V
-
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch Reference : MS 3V 1-5
Current
rating
IN(A)
Pre-arcing
I2t @ 1 ms
I2tp(kA2s)
Tested
Interrupting
rating
Total Clearing
I2t @ UN (kA2s)
Watt Losses
0.8IN IN
Size
Voltage
Ref:
500
069UR3D0500B
069UR3D0550B
069UR3D0630B
069UR3D0700B
069UR3D0800B
069UR3D0900B
069UR3D1000B
069UR3D1100B
069UR3D1250B
069UR3D1400B
060UR3D1600B
19
27
100
140
52.5 105
550
630
55
60
110
120
125
130
135
155
160
180
200
240
40
210
700
55
300
62.5
65
690V
800
95
490
200kA @660V
170kA @700V
3
900
135
170
240
350
480
555
700
67.5
77.5
80
1000
1100
1250
1400
1600
900
1260
1850
2500
3300
690V
+6%
90
100
120
-
600V
Notes: Minimum operating voltage for integrated trip indicator = 20V
Microswitch Reference : MS 3V 1-5
Electrical Characteristics:
Times vs current characteristics
The following curves indicate the pre-arcing time for each rated current as a function of RMS value of
pre-arcing current I:
-
-
-
Tolerances on this current ± 8%
Beyond 30 sec or 10 sec, small overloads must be eliminated by another device.
Curve CC’ represents the maximum times taken by the associated device to clear small overloads; only its
horizontal line is represented.
Its oblique line must be plotted according to sketch in top right corner:
- The intersection of the fuse and CC’ curves indicates the minimum breaking current Ipm of the fuse.
Data Sheet: 069URxDxxxxB Issue 1
Page 3 of 8
March, 2005
WESTCODE An IXYS Company
Times vs current characteristics
Size 0
German Standard DIN 110 690V
Size 1
Size 2
Size 3
Data Sheet: 069URxDxxxxB Issue 1
Page 4 of 8
March, 2005
WESTCODE An IXYS Company
German Standard DIN 110 690V
Total clearing I²T:
The horizontal curves given belowindicated the maximum values of total operating I2t (I2tt) as a function
of prospective current Ip @ 660V, cosϕ = 0.15. Oblique lines indicate the corresponding total operating
time Tt, with pre-arcing time in brackets.
Size 0
Size 1
Size 3
Size 2
Data Sheet: 069URxDxxxxB Issue 1
Page 5 of 8
March, 2005
WESTCODE An IXYS Company
German Standard DIN 110 690V
Cut off Characteristics:
The curves below indicate, for each rated current, the peak value IC that the current may reach as a
function of the prospective fault current Ip.
Size 0
Size 1
Size 2
Size 3
Data Sheet: 069URxDxxxxB Issue 1
Page 6 of 8
March, 2005
WESTCODE An IXYS Company
German Standard DIN 110 690V
I2t Multiplier Coefficient
Peak Arc Voltage
The above Mean curve shows variation of total
clearing time (I2tt) and total operating time Tt in
accordance with working voltage U.
Curve indicating peak arc voltage Um which may
appear across fuse terminals as a function of
working voltage U @ cos ϕ = 0.15.
Dissipated Power
Curve enabling calculation of dissipated power P
by a fuse rated IN, as a function of the RMS
current I, in multiples of IN in a steady state.
Data Sheet: 069URxDxxxxB Issue 1
Page 7 of 8
March, 2005
WESTCODE An IXYS Company
German Standard DIN 110 690V
Outline Drawing & Ordering Information:
Dimensions (mm)
Size
A
B
C
D
E
F
H
25
25
32
40
J
K
L
M
N
R
e
6
6
6
6
Weight
290g
40
46.5
82
47.5
101.6
101.6
101.6
101.6
21
10.5
10.5
10.5
10.5
17.7
17.7
21.2
25.2
134.6
134.6
134.6
134.6
23.8
23.8
23.8
23.3
30.8
30.8
30.8
30.3
25.2
25.2
25.2
25.2
0
51
60
56.5
65.5
79.5
91
47.5
47.5
48.5
25.5
30
1
430g
100
114
2
590g
74.5
37.2
3
860g
ORDERING INFORMATION
(Please quote code as below)
Voltage Rating (V)
Type
Size
Fixing
Current Rating (A)
Indicator
600 – 690
UR
0, 1, 2, 3
D
0063 – 1600
B
Order code: e.g. 069UR1A0350B = 690V, German Blade Contact, Size 1, DIN110, 350A, with button indicator
IXYS
GmbH
Edisonstraße 15
D-68623 Lampertheim
Tel: +49 6206 503-0
Fax: +49 6206 503-627
E-mail: marcom@ixys.de
Semiconductor
Westcode Semiconductors Ltd
Langley Park Way Langley Park
Chippenham Wiltshire SN15 1GE
Tel: +44 (0)1249 444524
Fax: +44 (0)1249 659448
E-mail: WSL.sales@westcode,com
IXYS Corporation
3540 Bassett Street
Westcode Semiconductors Inc
3270 Cherry Avenue
www.westcode.com
www.ixys.com
Santa Clara CA 95054 USA
Tel: +1 (408) 982 0700
Fax: +1 (408) 496 0670
E-mail: sales@ixys.com
Long Beach CA 90807 USA
Tel: +1 (562) 595 6971
Fax: +1 (562) 595 8182
E-mail: WSI.sales@westcode.com
The information contained herein is confidential and is protected by Copyright. The information may not be used or disclosed
except with the written permission of and in the manner permitted by the proprietors Westcode Semiconductors Ltd.
© Westcode Semiconductors Ltd.
In the interest of product improvement, Westcode reserves the right to change specifications at any time without prior notice.
Data Sheet: 069URxDxxxxB Issue 1
Page 8 of 8
March, 2005
相关型号:
©2020 ICPDF网 联系我们和版权申明