100W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
AC-DC Converter
100 Watt
The 100ACPM_SC series features standard rail mounting, energy efficiency
and is highly cost-effective. The series offers stability and high noise
immunity especially for industrial control equipment, machinery and
other demanding environments for industrial equipment. This converter
offers a compact and light weight design with and standard rail installation
(35mm). Furthermore this series offers Easy Fuse Tripping due and a
built-in DC OK relay contact. The converter can be installed on TS-35/7.5
or TS-35/15.
High efficiency up to 88%
Universal AC input range
(85~264VAC)
Built-in Active PFC function,
PF>0.93
Over power protection (OPP)
Over load protection (OLP)
Short circuit protection (SCP)
Wide operating ambient
temperature (-20°C~60°C)
Withstand 300VA surge input
for 5 secs.
100% full load burn-in test
Easy assembling from top side
PCB soldering side with
conformal coating
pending
Common specifications
Short circut protection:
Temperature rise at full load:
Cooling:
Input specifications
Long-term mode, automatic recovery
40°C MAX
Input voltage range
Input frequency
Power factor
90~264VAC
47~63Hz
Free air convection
-20°C~+60°C
115VAC
• 0.98 (max)
230VAC
• 0.93 (typ)
Operation temperature range:
Storage temperature range:
Storage humidity range:
Temperature coefficient:
MTBF (using MIL-HDBK-217F):
Power boost:
AC current
1.5A (max)
-30°C ~+85°C
Inrush current
Cold start
115VAC
• 30A (max)
230VAC
• 50A (typ)
< 95%
0.03%/°C MAX
Leakage current
Input—output: ≤0.25mA
Input—PG: ≤3.5mA
+25°C >200,000 hours
150% of rated current
support
Parallel function:
Output specifications
Safety standards:
UL60950-1 2nd Ed; IEC 60950-
1:2005(2nd Ed); EN60950-1:2006
Item
Test conditions
Min
Typ
Max
Units
Output voltage
accuracy (full load)
• 5V, 12V
• 24V, 48V
2
1
%
%
Case material:
Heat-resistant Plastic (UL94-V0) and
metal
Voltage adjustment
range
• 5V
3.3
10
21
5.5
15
27
V
V
V
V
Dimensions:
Weight:
129×98.3×37.6mm
487g
• 12V
• 24V
• 48V
43.2
52.8
Line regulation
Load regulation
Set-up time
Vin= min. to max. at
full load
0.5
%
Isolation specifications
• 5V, 12V
• 24V, 48V
2
1
%
%
Item
Test condition
Min
Typ
Max
Units
VAC
Withstand voltage*
• Primary-Sec.: 10mA
• Primary-PG: 10mA
• Secondary-PG: 10mA 500
3000
1500
• @115VAC input
• @230VAC input
4
2
s
s
Hold-up time
@230VAC input
12
ms
%
Isolation resistance
100
MΩ
Overshoot and
undershoot
5
* Input-Output, tested for 1 minute, 500VDC and leakage current less than 1mA
Switching frequency
100
KHz
Protection specifications
* Measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated
with a 0.1 uF & 10uF parallel capacitor.
Over-load
protection
110%~150% of rated output current, hiccup mode, auto
recovery
Over-power
protection
110%~150% of rated output current, hiccup mode, auto
recovery
Example:
100ACPM_24SC
100= 100Watt
AC= AC-DC
PM= series
24= 24 Vout
Note:
1. All parameters NOT specially mentioned are measured at rated input, rated load
and 25°C of ambient temperature.
S= single output
C= PFC (Power Factor Correction)
Page 1 of 3
GAPTEC-Electronic GmbH & Co. KG
100ACPM_SC – Rev. 2017-1.0
sales@gaptec-electronic.com – www.gaptec-electronic.com
Specifications subject to change without notice.
100ACPM_SC Series
100W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
EMC specifications
EMC / Emission
Compliance to EN55022, Class B
EMC / Harmonic current
EMC / Immunity
Compliance to EN61000-3-2, CLASS A
Compliance to EN61000-4-2, -3, -4, -5, -6, -8, -11; heavy industry level
The power supply is considered as a component which will be installed into a final equipment.
The final equipment must be re-confirmed that it still meets EMC directives.
Approval
Model
Power
[W]
Output
[Vo, VDC]
Rated Current
[A]
Current Range
[A]
Ripple&Noise* [mV, typ]
Efficiency [%, typ]
0~70°C
-20~0°C
UL (pending)
UL (pending)
UL (pending)
UL (pending)
100ACPM_05SC
100ACPM_12SC
100ACPM_24SC
100ACPM_48SC
100
100
100
100
5
20
8.5
4.2
2.2
0~20
0~8.5
0~4.2
0~2.2
150
150
84
87
88
88
12
24
48
150
150
150
150
150
200
Measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uF & 10uF parallel capacitor.
Mechanical dimensions
Unit: mm
Tolerance: 1mm
Mounting
method
Mounting
holes
AC terminal blocks installation information
Screw specs
L max.
Torque max.
Terminal No.
Function
Wire specs
Torque max.
7.5Kgf.cm
Bottom
Bottom
Side
1-4
M3
M3
M3
M3
5mm
3mm
5mm
3mm
7kgf.cm (max)
6.5kgf.cm (max)
7kgf.cm (max)
6.5kgf.cm (max)
1
2
3
L
N
5-10
22-12AWG
11-13
14-16
PG
Side
DC terminal blocks installation information
Terminal No.
Function
Wire specs
Rec. torque
7.5Kgf.cm
4
5
-V
22-12AWG
+V
Page 2 of 3
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com
100ACPM_SC – Rev. 2017-1.0
Specifications subject to change without notice.
100ACPM_SC Series
100W - Single Output AC-DC Converter - Universal Input - Isolated & Regulated
Typical characteristics
Derating Curve
AMBIENT TEMPERATURE (°C)
Functional block diagram
Functional diagram
Page 3 of 3
100ACPM_SC – Rev. 2017-1.0
GAPTEC-Electronic GmbH & Co. KG
sales@gaptec-electronic.com – www.gaptec-electronic.com
Specifications subject to change without notice.
相关型号:
100AFX330M20X20
CAPACITOR, ALUMINUM ELECTROLYTIC, NON SOLID, POLARIZED, 100 V, 330 uF, THROUGH HOLE MOUNT, CAN
RUBYCON
100AFX330MST20X20
CAPACITOR, ALUMINUM ELECTROLYTIC, NON SOLID, POLARIZED, 100 V, 330 uF, THROUGH HOLE MOUNT, CAN
RUBYCON
100AFX390M20X20
CAPACITOR, ALUMINUM ELECTROLYTIC, NON SOLID, POLARIZED, 100 V, 390 uF, THROUGH HOLE MOUNT, CAN
RUBYCON
©2020 ICPDF网 联系我们和版权申明