SV-PS [GAMEWELL-FCI]
Graphical Monitoring Software and Interface Hardware System; 图形监控软件和接口硬件系统型号: | SV-PS |
厂家: | GAMEWELL-FCI BY HONEYWELL |
描述: | Graphical Monitoring Software and Interface Hardware System |
文件: | 总2页 (文件大小:88K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
600 Series
SmartView™
Graphical Monitoring Software and
Interface Hardware System
Description
SmartView™ is a dynamic, feature-rich, graphical fire
alarm monitoring software and interface hardware system
for the Gamewell-FCI IdentiFlex 600 Series of addressable
fire alarm control panels.
Gamewell-FCI’s SmartView™ system includes worksta-
tion software — a Microsoft® Windows® 2000-based graph-
ical user interface. SmartView®’s software is designed to be
easy to configure and simple to operate. SmartView® pre-
sents information through a graphical menu system and
dynamic color display while operating over a high-speed
Ethernet LAN/WAN or single-user network.
SmartView
Features
Similar to a website, the menu pages feature user-defined
“hot spots” that either launch a task-specific application or
direct users to another menu page. The system utilizes
custom fire alarm icons to display point-specific alarm infor-
mation. Each alarm event is displayed on a color-coded
alarm display, or with its floor plan pinpointing the exact
location of the alarm. Point-specific user instructions can
also be displayed. All events and user actions are logged
for creating user-selected customized reports. To enhance
user accessibility, event information can also be broadcast
to pagers or emailed via an optional Internet connection.
•
•
Fire alarm monitoring software operating on Windows®
2000/XP Professional operating system software.
Compatible with all Gamewell-FCI IdentiFlex 600 Series
fire alarm panels.
Ethernet TCP/IP net controller.
High-speed networking.
Power supply with UPS battery backup.
SQL database.
Supports up to three workstations standard with P/N
SV-MWS.
•
•
•
•
•
•
•
•
SmartLink™ peer-to-peer compatible.
Fully supervised.
NetController features flash memory for easy on-line
software updates.
Optional Internet connection.
Paging and email compatible.
SmartView™ can monitor an individual IdentiFlex 600
Series addressable fire alarm panel, or an entire
SmartNet™/SmartLink™ network. The SmartView™ sys-
tem supports up to three SmartView™ workstations as
standard; for systems that require four or more worksta-
tions, please consult the factory. Included with each unit of
SmartView™ software is a net communications central pro-
cessing unit with 8 MB DRAM, 4 MB flash, a math copro-
cessor, communication ports, Gamewell-FCI 600 Series
fire alarm panel interface, and power supply.
•
•
•
•
•
Easy configuration.
Familiar interface similar to Windows® Explorer.
Event logs with modifiable “listviews” for customized
reports.
•
•
•
•
Select event-specific icons.
Color-coded alarm bar and Customize graphics.
Display multiple floor plans and user instructions.
Multiple workstation support.
Microsoft® Windows® is a registered trademark of Microsoft® Corporation.
SmartView™, SmartNet™ and SmartLink™ are trademarks of Honeywell International Inc.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
©2007 Honeywell International Inc. All rights reserved.
Specifications are for information only, are not intended for installatiown pwurpwos.egs,aamndearwe seulblje-cftctoi.cchoanmge without notice. No responsibility is assumCeSd-b2y1G5a0meRweellv-F.CAI fopr athgeier u1se.of 2
Specifications
Ordering Information
Net communications and power supply:
Operating
Model
SV-SWS
Description
Single workstation system, including
operating software, SV-NC, SV-PS, and
enclosure.
Multiple workstation system including up to
three workstations, including operating
software, SV-NC, SV-PS, and enclosure.
Workstation software required for each
additional workstation PC.
Net communications unit with
Gamewell-FCI driver (fiber).
Net communications unit with
Gamewell-FCI driver.
+32°F to +120°F (0°C to +49°C).
Temperature:
Relative Humidity:
Input Voltage:
10% to 95% non-condensing.
100-240 VAC, 50/60 Hz
SV-MWS
Power Consumption: 10 watts.
Overload Protection: 3.0A resettable fuse TVS
protection.
Battery Backup/UPS: UPS circuit with built-in trickle
charger included. Provides four
(4) hours of backup time with two
(2), 12-volt, 7.0 AH batteries (not
included).
SV-MWOS
SV-NC-F
SV-NC
SV-PS
Power supply.
PC hardware requirements:
PC with 750 MHz (or higher) processor, 256 MB (minimum)
RAM, 10 GB (minimum) hard drive.
CD-RW drive.
10/100 baseT Ethernet card.
19" (48.26 cm) diagonal (minimum) monitor screen, display
set to 1024 x 768.
Microsoft® Windows® 2000/XP
Operating system:
Professional.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
CS-2150 Rev. A page 2 of 2
www.gamewell-fci.com
相关型号:
SV01201-01-0F
Telecom and Datacom Connector, 20 Contact(s), Female, Right Angle, Surface Mount Terminal, Socket, ROHS COMPLIANT
FOXCONN
SV01201-01-7F
Telecom and Datacom Connector, 20 Contact(s), Female, Right Angle, Surface Mount Terminal, Locking, Socket, ROHS COMPLIANT
FOXCONN
SV01203-01-0F
Telecom and Datacom Connector, 20 Contact(s), Female, Right Angle, Surface Mount Terminal, Socket, ROHS COMPLIANT
FOXCONN
SV01203-01-7F
Telecom and Datacom Connector, 20 Contact(s), Female, Right Angle, Surface Mount Terminal, Locking, Socket, ROHS COMPLIANT
FOXCONN
SV01207-01-0F
Telecom and Datacom Connector, 20 Contact(s), Female, Right Angle, Surface Mount Terminal, Socket, ROHS COMPLIANT
FOXCONN
SV01207-01-7F
Telecom and Datacom Connector, 20 Contact(s), Female, Right Angle, Surface Mount Terminal, Locking, Socket, ROHS COMPLIANT
FOXCONN
SV01301-01-0F
Telecom and Datacom Connector, 30 Contact(s), Female, Right Angle, Surface Mount Terminal, Socket, ROHS COMPLIANT
FOXCONN
SV01301-01-7F
Telecom and Datacom Connector, 30 Contact(s), Female, Right Angle, Surface Mount Terminal, Locking, Socket, ROHS COMPLIANT
FOXCONN
©2020 ICPDF网 联系我们和版权申明