FF6 [GAMEWELL-FCI]
NAC Expander/Power Supply; NAC扩展器/电源型号: | FF6 |
厂家: | GAMEWELL-FCI BY HONEYWELL |
描述: | NAC Expander/Power Supply |
文件: | 总2页 (文件大小:136K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Features
FireForce 6
• Provides two fully-supervised input/
control circuits (9 – 32 VDC).
• Multiple sync protocols, compatible with
the following appliances: Cooper-
Wheelock, Faraday, System Sensor, and
Gentex — as field-selectable options.
NAC Expander/Power Supply
• Four configurable supervised NAC
outputs.
Description
• 6.0 Amp, 24 VDC, fully regulated full-load
output (power-limited).
The FireForce 6 (FF6) from
Gamewell is a Notification Appli-
ance Circuit (NAC) extender panel
designed to extend the power
capabilities of existing NACs and
provide power (3.0 A maximum) for
other ancillary devices. The FF6 will
connect to any brand of UL-Listed
Fire Alarm Control Panel (FACP) to
provide Notification Appliance
Circuit expansion.
• Output fault notification to FACP.
• Continuous auxiliary power output.
• Trouble and status LEDs.
• Common trouble Form-C relay.
• Isolated AC Fail Form-C relay, immediate
or delayed six hours.
• Ground fault detection.
Designed with advanced switch-
mode power-supply technology, the
FireForce 6 provides filtered and
• 33 AH battery charger capability.
• Selectable temporal coding.
• Facilitates multiple NAC synchronization
for large areas.
electronically-regulated power
distributed to four NACs. Each NAC is rated at 3.0 Amp maximum, with a
total output capacity of 6.0 Amp. The outputs may be configured as: four
Class B (Style W, X, Y); or two Class A (Style Z); or two Class B and one
Class A. The FF6 includes an internal battery charger.
Field-Selectable NAC Signaling
OUTPUT
INPUT
(follows input)
Steady
Steady
Steady
Temporal
Gamewell’s FF6 provides independent output circuit supervision. In the
event of a NAC fault, the FF6 can be configured to notify the FACP. The
FF6 has field-selectable, built-in strobe and horn sync protocols. Protocols
support Faraday, Gentex, System Sensor, and Cooper-Wheelock devices; or
pass through a pre-generated sync protocol from a single synchronization
source. This eliminates the need for additional individual sync modules.
Independent horn silencing via sync protocol allows synchronized horns and
strobes to operate on a single circuit.
Steady – Sync
Steady with
noise eliminated
Sync
Sync
g2282io.tbl
Listings
Listings and approvals below apply to the
basic FireForce 6 panel. In some cases,
certain modules may not be listed by
certain approval agencies, or listing may
be in process. Consult factory for latest
listing status.
Engineer’s Specifications
The Fire Alarm System shall be designed with remotely located Notification
Appliance Circuit (NAC) Expander/Power Supplies for the support of
notification appliances. The remote Power Supplies shall be fully supervised
and shall provide 6.0 Amps of notification appliance power and auxiliary
power output. The NAC Extender Panel shall be able to select strobe
synchronization protocol via an internal dip switch. There shall be five
selectable protocols available. The NAC Extender Panel shall synchronize
all outputs simultaneously. The internal battery charging circuit shall
charge up to 33 AH batteries. The NAC Expander/Power Supply shall be a
Gamewell FireForce 6.
• UL Listed: file S521.
• MEA approved: file 429-92-E, Vol. XVI.
FireForce 6 CS-2498 09/01/06
Page 1 of 2
Specifications
Ordering Information
Primary input power
120 VAC, 60 Hz, 3.0 A; or 220 V, 1.5 A;
jumper selectable.
FF6
24 VDC, 6.0 Amp, fire alarm NAC expander/power supply
with integral battery charger.
Secondary power
24-volt operation: two 7 – 33 AH
BAT-1270
Battery, 12 VDC, 7 AH (two required for 24 V operation).
batteries.
BAT-12120 Battery, 12 VDC, 12 AH (two required for 24 V operation).
BAT-12180 Battery, 12 VDC, 18 AH (two required for 24 V operation).
BAT-12260 Battery, 12 VDC, 26 AH (two required for 24 V operation).
Battery charging capacity
Up to 33 AH batteries.
Battery space
Up to two 7 AH batteries maximum inside
FF6 cabinet. Larger batteries require a
separate battery cabinet.
Total output power
6.0 A maximum.
Standby current
75 mA.
Auxiliary power output
3.0 A maximum.
NAC output ratings
24 VDC fully regulated, 3.0 A maximum
per circuit (6.0 A total).
End-of-Line resistor
4.7 K ohm.
Common trouble relay
2.0 A/28 VDC or 120 VAC.
Input control circuit
9 – 32 VDC @ 5 mA minimum.
Temperature rating
32°F to 120°F (0°C to 49°C).
Relative humidity
85% maximum, noncondensing.
Dimensions
FF6 Cabinet: 16.0" H x 12.25" W x 3.0" D
(cm: 40.64 H x 30.88 W x 7.62 D).
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Specifications and wiring information are provided for information only and are
believed to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation.
For more information, contact Gamewell-FCI.
Fax: 203-484-7118
www.gamewell-fci.com
A Honeywell Company
© 2006 Gamewell-FCI
Page 2 of 2
FireForce 6 CS-2498 09/01/06
相关型号:
FF6-10-AC-QD-SS
Snap Acting/Limit Switch, SPST, Momentary, Quick Connect Terminal, Panel Mount-threaded
HONEYWELL
FF6-10-AC-QD05
Snap Acting/Limit Switch, SPST, Momentary, Quick Connect Terminal, Panel Mount-threaded
HONEYWELL
FF6-10-DC-QD05
Snap Acting/Limit Switch, SPST, Momentary, Quick Connect Terminal, Panel Mount-threaded
HONEYWELL
FF6-11-AC-QD05
Snap Acting/Limit Switch, DPST, Momentary, Quick Connect Terminal, Panel Mount-threaded
HONEYWELL
FF6-11-AC-QDO5
Snap Acting/Limit Switch, 3PST, Momentary, Wire Terminal, Non-contact Switch Actuator, Panel Mount
HONEYWELL
FF6-11-DC-QD05
Snap Acting/Limit Switch, DPST, Momentary, Quick Connect Terminal, Panel Mount-threaded
HONEYWELL
©2020 ICPDF网 联系我们和版权申明