CH90-24-W [GAMEWELL-FCI]
Wheelock CH Series Electronic Chimes & Chime Strobes; 会德丰CH系列电子编钟和编钟频闪灯型号: | CH90-24-W |
厂家: | GAMEWELL-FCI BY HONEYWELL |
描述: | Wheelock CH Series Electronic Chimes & Chime Strobes |
文件: | 总4页 (文件大小:170K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Features
• ADA/NFPA/UFC/ANSI compliant
Wheelock CH Series
• Complies with OSHA 29 Part
1910.165
Electronic Chimes & Chime Strobes
• Wall mount models are available
with Field
Selectable Candela Settings of 15/
30/75/110cd or 15/75cd (single
candela model)
Description
• Ceiling mount models are avail-
able with field selectable candela
settings of 15/30/75/95cd
Wheelock’s Series CH Chimes and
Chime Strobes minimize alarm system
power supply requirements and wiring
costs with a low current draw and a
patented chime mounting plate for fast,
easy installation. Each model has a
built-in level adjustment feature and an
aesthetic two (2) screw grille cover.
These unique solid-state chime
appliances provide field selectable
single-stroke or vibrating operation with
Anechoic sound levels adjustable up to
83 dB and tone adjustable from 800 to
1200 Hz.
• Low current draw with temperature
compensation to reduce power
consumption and wiring costs
• Strobes produce once per second
over the regulated voltage range
CH70 Series
CH90 Series
• 24 VDC with wide UL “Regulated
Voltage” using filtered DC or
unfiltered VRMS input voltage
• Synchronize with Wheelock SM,
DSM or any power supply with
built-in Wheelock sync protocol
Strobe options for wall mount models
include 15/75cd or Wheelock’s patented
MCW multi-candela strobe with field
selectable candela settings of 15/30/75/
110cd.
• Adjustable Volume and Tone
Control
• Single Stroke or Vibrating Opera-
tion
Ceiling mount models are available in
Wheelock’s patented MCC multi-
candela ceiling strobe with field
selectable intensities of 15/30/75/95cd.
• Fast Installation with IN/OUT screw
terminals using 12 to 18 AWG
wires
The strobe portion of all Series CH
Chime Strobes may be synchronized
when used in conjunction with the
Wheelock SM, DSM Sync Modules or
a power supply with patented Wheelock
Listings
Listings and approvals below
apply to the basic CH Series
Electronic Chimes and Chime
Strobes. In some cases, certain
modules may not be listed by
certain approval agencies, or
listing may be in process. Consult
factory for latest listing status.
Sync
Protocol.
Wheelock’s
synchronized strobes offer an easy way
to comply with ADA recommendations
concerning photosensitive epilepsy as
well as meeting the requirements of
NFPA 72 and UFC.
Multi-Candela Indicator
(bottom of Strobe Lens)
• UL Listed: files E5946: E5946/
S5391
The Series CH Chime Strobes are UL
Listed for indoor, wall or ceiling mount
• MEA Listed. file 151-92-E Vol. XXI
applications under Standard 1971 for Signaling Devices for the Hearing-Impaired
and under Standard 464 for Private Mode Audible Signal Appliances. They are
available in two attractive package styles for flush mounting to standard electrical
boxes or convenient surface mounting. All models include IN/OUT wiring
terminations that accept two 12 to 18 AWG wires at each terminal. Inputs are
polarized for compatibility with industry standard reverse polarity supervision.
• CSFM approved: file 7135-
0785:151
CH Series CS-2239 06/01/04
Page 1 of 4
CONTACT
WHEELOCK
FORTHECURRENT“INSTALLATION
INSTRUCTIONS”AND“GENERAL
INFORMATION” SHEET (P82380) ON
THESEPRODUCTS. THESEDOCUMENTS
UNDERGOPERIODICCHANGES. ITIS
IMPORTANT THATYOU HAVE CURRENT
INFORMATIONONTHESEPRODUCTS.
THESE MATERIALS CONTAIN IMPOR-
TANT INFORMATION THAT SHOULD BE
READPRIORTOSPECIFYINGOR
INSTALLINGTHESEPRODUCTS,
INCLUDING:
General Notes
•
Strobes are designed to flash once per second minimum over their “Regulated
Voltage Range”. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per
second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second.
All candela ratings represent minimum effective Strobe intensity based on UL
Standard 1971.
•
•
Series E Speaker Strobes and Series E Speakers are listed under UL Standard
1971 for indoor use with a temperature range of 32°F to 120°F (0°C to 49°C)
and maximum humidity of 85%.
•
“Regulated Voltage Range” is the newest terminology used by UL to identify
the voltage range. Prior to this change UL used the terminology “Listed
Voltage Range”.
• TOTALCURRENT REQUIRED BYALL
APPLIANCES CONNECTED TO SYSTEM
SECONDARY POWER SOURCES.
• FUSE RATINGS ON NOTIFICATION
APPLIANCE CIRCUITS TO HANDLE
PEAK CURRENTS FROMALLAPPLI-
ANCES ON THOSE CIRCUITS.
Engineering’s Specifications
The chime appliances shall be Wheelock Series CH Chimes and the chime strobe
appliances shall be Wheelock Series CH Chime Strobes or approved equals. The
chime shall be UL Listed under Standard 464 for Audible Signal Appliances and
chimes equipped with strobes shall be listed under UL Standard 1971 for Emergency
Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet
the requirements of FCC Part 15, Class B and shall incorporate low temperature
compensation to ensure the lowest possible current consumption.
• COMPOSITE FLASH RATE FROM
MULTIPLE STROBES WITHINA
PERSON’S FIELD OF VIEW.
• ADDING, REPLACING OR CHANGING
APPLIANCES OR CHANGING CANDELA
SETTINGS WILLAFFECT CURRENT
DRAW. RECALCULATE CURRENT
DRAW TO INSURE THAT THE TOTAL
AVERAGE CURRENTAND TOTALPEAK
REQUIRED BYALL APPLIANCES DO
NOTEXCEED THE RATED CAPACITY OF
THE POWER SOURCES OR FUSES.
All chimes shall use solid state components and shall provide field selectable single
stroke or vibrating operation with volume control and tone control. All models shall
have a peak Anechoic sound output of 83 dB at 10 feet and an adjustable frequency
range of 800 to 1200 Hz. All inputs shall employ terminals that accept 12 to 18 AWG
wire sizes.
The strobe portion of the appliance shall produce a flash rate of one (1) flash per
second over the Regulated Voltage Range and shall incorporate a Xenon flashtube
enclosed in a rugged Lexan® lens. The strobe shall be of low current design. Where
Multi-Candela Chime Strobes are specified, the strobe intensity shall have a mini-
mum of four (4) field selectable settings and shall be rated per UL Standard 1971 at:
15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for
ceiling mount. The selector switch for selecting the candela shall be tamper resistant
and not accessible from the front of the appliance. The 1575 candela strobe shall be
specified when 15 candela UL Standard 1971 listing with 75 candela on-axis is
required (e.g. ADA compliance).
• THE VOLTAGEAPPLIED TO THESE
PRODUCTS MUST BE WITHIN THEIR
“REGULATED VOLTAGE RANGE”.
• INSTALLATION OF 110 CANDELA
STROBE PRODUCTS IN SLEEPING
AREAS.
• INSTALLATION IN OFFICEAREASAND
OTHER SPECIFICATIONAND INSTALLA-
TION ISSUES.
When synchronization is required, the strobe portion of the appliance shall be com-
patible with Wheelock’s SM, DSM sync modules or any power supply with built-in
Patented Wheelock Sync Protocol. The strobes shall not drift out of synchronization at
any time during operation. If the sync module or Power Supply fails to operate, (i.e.,
contacts remain closed), the strobe shall revert to a non-synchronized flash rate.
The chime and the chime strobe appliances shall be designed for indoor surface or
flush mounting. The chime and chime strobe shall incorporate a chime mounting
plate with a grille cover which is secured with two screws for a level, aesthetic finish
and shall mount to standard electrical hardware requiring no additional trimplate or
adapter.
• USE STROBES ONLY ON CIRCUITS
WITH CONTINUOUSLYAPPLIED
OPERATING VOLTAGE. DO NOT USE
STROBES ON CODED OR INTERRUPTED
CIRCUITS IN WHICHTHEAPPLIED
VOLTAGE IS CYCLED ONAND OFFAS
THE STROBES MAY NOT FLASH.
• FAILURE TO COMPLY WITH THE
INSTALLATION INSTRUCTIONS OR
GENERALINFORMATION SHEETS
COULD RESULTIN IMPROPER INSTAL-
LATION,APPLICATION,AND/OR
OPERATION OFTHESE PRODUCTS IN
AN EMERGENCYSITUATION, WHICH
COULD RESULTIN PROPERTY
All chime and chime strobe appliances shall be backward compatible.
Wheelock products must be used within their published specifications and must be PROPERLY
specified, applied, installed, operated, maintained and operationally tested in accordance with their
installation instructions at the time of installation and at least twice a year or more often and in
accordance with local, state and federal codes, regulations and laws. Specification, application,
installation, operation, maintenance and testing must be performed by qualified personnel for
proper operation in accordance with all of the latest National Fire ProtectionAssociation (NFPA),
Underwriters’ Laboratories (UL), National Electrical Code (NEC), Occupational Safety and Health
Administration (OSHA), local, state, county, province, district, federal and other applicable building
and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appen-
dices and amendments and the requirements of the local authority having jurisdiction (AHJ).
DAMAGEAND SERIOUS INJURY OR
DEATH TO YOUAND/OR OTHERS.
• CONDUCTOR SIZE (AWG), LENGTH
ANDAMPACITY SHOULD BE TAKEN
INTO CONSIDERATION PRIORTO
DESIGNAND INSTALLATION OFTHESE
PRODUCTS, PARTICULARLY IN
RETROFIT INSTALLATIONS.
Page 2 of 4
CH Series CS-2239 06/01/04
Wiring Diagram
FROM
PRECEDING
APPLIANCE,
SYNC MODULE,
POWER SUPPLY
OR FACP
TO NEXT
+
+
APPLIANCE
OR EOLR
-
-
SERIES CH CHIME & STROBE
OPERATE INDEPENDENTLY
(NON-SYNC OR SYNC)
FROM
TO NEXT
PRECEDING
+
-
+
-
STROBE OR
EOLR
APPLIANCE,
SYNC MODULE,
POWER SUPPLY
OR FACP
COM
-
+
+
CHIME
STROBE
(OPTIONAL)
DSM #1
Sync
Strobe NAC Cir.
Strobe NAC Cir.
CH
CH
+
-
SERIES CH CHIME STROBES
SYNCHRONIZED W/ MULTIPLE
DSM MODULES
Note: Figure shows interconnection to
strobe through sync module. Chime
portion requires 2 separate conductors to
FACP.
F
A
C
P
DSM #2
Sync
CH
CH
CH
CH
+
-
DSM #3
Sync
+
Strobe NAC Cir.
-
DSM Interconnecting wiring shown. Maximum of
twenty (20)
DUALSYNCMODULE
SYNC
+
-
SYNC
OUT1
+
IN1
+
MINUS1
+
-
SERIES CH CHIME STROBE
APPLIANCES SYNCHRONIZED
WITH DSM MODULE SINGLE
“CLASSA”
F
+AUDIBLE
A
C
P
SIGNAL
CIRCUITOUT
AUDIBLE
-
+
-
+
-
OUT2
IN2
+
+
APPLIANCE
APPLIANCE
+
-
MINUS2
SIGNAL
CIRCUITRETURN
CH Series CS-2239 06/01/04
Page 3 of 4
NOTE: All CAUTIONS and WARNINGS are identified by the symbol . All warnings are printed in bold capital
letters. PLEASEREADTHESESPECIFICATIONSANDASSOCIATEDINSTALLATIONINSTRUCTIONSCAREFULLYBEFOREUSING, SPECI-
FYING ORAPPLYING THIS PRODUCT. FAILURE TO COMPLYWITHANYOF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD
RESULT IN IMPROPERAPPLICATION, INSTALLATIONAND/OR OPERATION OF THESE PRODUCTS INAN EMERGENCY SITUATION,
WHICHCOULDRESULTINPROPERTYDAMAGE,ANDSERIOUSINJURYORDEATHTOYOUAND/OROTHERS.
Ordering Information
SYNC
W/SM,
DSM
WALL/
CEILING
MOUNT
AGENCY APPROVALS
UL MEA CSFM BFP
STROBE
NON-
SYNC
MODEL
COLOR
MOUNTING
OPTIONS**
MODEL
CANDELA
CH70-24MCW-FR
CH70-24MCW-FW
15/30/75/110
15/30/75/110
X
X
X
X
X
X
X
X
X
X
X
X
Red
White
Red
Wall
Wall
L,O,P,Q,U,Y
L,O,P,Q,U,Y
L,O,P,Q,U,Y
L,O,P,Q,U,V,Y
X
X
X
X
X
X
X
X
X
*
X
X
X
X
X
X
X
X
X
*
CH70-241575W-FR 15 (75 on Axis)
Wall
CH90-24MCC-FW
CH70-24-R
15/30/75/95
White
Red
Ceiling
-
-
Wall/Ceiling L,O,P,Q,U,V,Y
Wall/Ceiling L,O,P,Q,U,V,Y
X
X
X
X
CH90-24-W
White
* Average RMS Current is per UL average RMS method and Average Mean Current is per UL average mean method. For rate In Rush and Peak current across the UL
listed voltage range for both filtered DC and unfiltered VRMS (FWR), see installation instructions.
** Refer to mounting options data sheet.
TABLE1: AVERAGERMS CURRENT*
CH70 STROBE CURRENT - WALL M OUNT
24MCW 24MCWH
15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd
CH90 STROBECURRENT - CEILING MOUNT
CH70/C90
CHIMES
24MCC 24MCCH
241575W
15/75cd
0.101
16 vdc
24 vdc
33 vdc
0.062 0.102 0.192 0.265 0.300 0.420 0.068 0.112 0.211 0.292 0.300 0.420
0.041 0.065 0.116 0.155 0.195 0.270 0.045 0.072 0.128 0.171 0.195 0.270
0.032 0.047 0.081 0.107 0.145 0.190 0.035 0.052 0.089 0.118 0.145 0.190
0.064
0.047
Application
1. The chimes are factory set in single stroke (SS) mode. They can be
changed to vibrating (VIB) mode with jumper on PC Board. SINGLE STROKE
OPERATION: The minimum input pulse duration must be at least 160 ms “on”
time and 160 ms “off” time. The chime will only operate once each time it is
pulsed. This mode is recommended for coded systems. VIBRATING OP-
ERATION: Continuous input voltage applied to the chime will activate the
chime at one-second intervals.
TABLE2: CHIMEdBA RATINGS
dBA @ 10 ft.
PEAK
dBA
REVERBERANT
@ 10 ft.
ANECHOIC
CH70/CH90
SOUND LEVEL
Min
52
Max
2. The volume and tone controls have been adjusted at the factory to insure
maximum dBA output. However, once the mode is selected, the installer
may want to fine-tune the signal to better suit the application.
83
58
3. Anechoic dBA is measured in an anechoic chamber with peak meter re-
sponse. Reverberant dBA is rated per UL Standard 464.
4. Chime inrush current is 0.100 amps maximum with filtered DC input (0.140
amps with VRMS input voltage) with a time duration of 100 milliseconds.
SY N C M O D ELS/ P O WER SUP P LY
A VER A G E
IN P UT
SM Sync Module is rated for
3.0 amperes @ 24 VDC.
M O D EL
M EA N
M O UN T IN G
O P T IO N S
VO LT A G E
(VD C )
N UM B ER
C UR R E N T
DSM Sync Module is rated
for 3.0 amperes per circuit.
The maximum number of
@ 24 VD C
The Gamewell Company
12 Clintonville Road
SM -12/24-R
24
24
.028
.035
W
W
interconnected
DSM
DSM -12/24-R
modules is twenty (20).
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring
instructions shipped with the product shall always be used for actual installation. For
more information, contact Gamewell.
www.gamewell.com
A Honeywell Company
© 2004 Gamewell
Page 4 of 4
CH Series CS-2239 06/01/04