SS-T Series  
Features  
• Sleek, low-profile, stylish design.  
• State-of-the-art thermistor technology  
for fast response.  
Intelligent Addressable Plug-In  
Thermal (Heat) Detectors  
• SS-TR rate-of-rise model: 15°F (8.3°C)  
per minute.  
• SS-T fixed heat, Factory preset at  
135°F (57°C).  
• SS-TH high temperature model of  
190°F (88°C).  
• Addressable by devices via decade  
address switches.  
Description  
Gamewell’s SmartScanTM intelli-  
gent plug-in smoke detectors with  
integral communication provide  
features that surpass conven-  
tional detectors. Detector sensi-  
tivity can be programmed in the  
control panel software. Sensitiv-  
ity is continuously monitored and  
reported to the panel. Point ID  
capability allows each detector’s  
address to be set with decade  
• Rotary, decimal addressing (1 – 99)  
• Two-wire SLC connection.  
• Visible LEDs “blink” every time the unit  
is addressed.  
• 360°-field viewing angle of the visual  
alarm indicators (two bicolor LEDs).  
LEDs blink green in Normal condition  
and turn on steady red in Alarm.  
• Integral communications and built-in  
device-type identification.  
6936pho1.jpg  
SS-T in SS-B6 base  
• Remote test feature from the panel.  
• Built-in functional test switch activated  
by external magnet.  
address switches, providing exact detector locations for selective maintenance  
and troubleshooting. SS-T Series thermal detectors use an innovative ther-  
mistor sensing circuit to produce 135°F/57°C fixed-temperature (SS-T) and rate-  
of-rise thermal detection (SS-TR) in a low-profile package. SS-TH provides fixed  
high-temperature detection at 190°F/88°C in a low-profile package as well. These  
thermal detectors provide cost effective, intelligent property protection in a vari-  
ety of applications. SS-T Series addressable detectors are compatible with  
Gamewell’s 602, 610, 632, 654 and 658 addressable fire alarm control panels  
with a SmartScanTM SLC.  
• Low standby current.  
• Built-in tamper-resistant feature.  
• Designed for direct-surface or electrical-  
box mounting.  
• Sealed against back pressure.  
• Plugs into separate base for ease of  
installation and maintenance. Separate  
base allows interchange of photoelec-  
tric, ionization and thermal sensors.  
• SEMS screws for wiring of the separate  
base.  
• Constructed of off-white Bayblend®,  
designed to commercial standards, and  
offers an attractive appearance.  
• 94-5V plastic flammability rating.  
• Remote LED output connection to  
optional RA400Z remote LED annuncia-  
tor.  
Installation  
The SS-T Series of plug-in intelligent, addressable thermal detectors use a sepa-  
rate base to simplify installation, service, and maintenance. Installation instruc-  
tions are shipped with each detector.  
Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81  
cm) deep. Suitable back boxes include:  
• Optional sounder, relay, and isolator  
bases.  
• Optional recessed (RMK400) or surface  
(SMK400) base mounting kits.  
• 4.0" (10.16 cm) square box.  
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.  
• Single-gang box (except relay or isolator base).  
With B501BH or B501BHT base, use a 4.0" (10.16 cm) square box.  
With B224RB or B224BI base, use a 3.5" (8.89 cm) or 4.0" (10.16 cm) oc-  
tagonal box, or a 4.0" (10.16 cm) square box.  
Listings  
Listings and approvals below apply to  
the SS-T Series of intelligent, address-  
able thermal (heat) detectors. In some  
cases, certain detectors may not be  
listed by certain approval agencies, or  
listing may be in process. Consult  
factory for latest listing status.  
NOTES: 1) Because of the inherent supervision provided by the SLC loop, end-of-line resis-  
tors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring.  
2) When using relay or sounder bases, consult the SS-LI data sheet for device limitations  
between isolator modules and isolator bases.  
Applications  
Use thermal detectors for protection of property. For further information, go to  
systemsensor.com for manual I56-407-00, Applications Manual for System  
Smoke Detectors, which provides detailed information on detector spacing, place-  
ment, zoning, wiring, and special applications.  
• UL Listed: file S2527.  
• CSFM approved: file 3240-1288:166.  
• MEA approved: file 383-02-E Vol. V.  
Bayblend® is a registered trademark of Bayer Corporation.  
SS-T Series CS-2460 09/01/06  
Page 1 of 2  
Specifications  
Product Line Information  
SS-T: Intelligent, addressable thermal  
detector. Must be mounted to one of the  
bases listed below.  
SS-B6.  
Size  
BCK-200B: Black detector covers, box of  
10.  
M02-04-01: Test magnet.  
M02-09-00: Test magnet with telescope  
stick.  
XR2B: Detector removal tool. Allows  
installation and/or removal of SS-T Series  
thermal detector heads from base in high  
ceiling installations.  
T55-127-000: Detector removal tool without  
pole.  
2.1" (5.3 cm) high x 4.1" (10.4 cm)  
diameter installed in B501 base, 6.1"  
(15.5 cm) diameter installed in SS-B6  
base.  
SS-TR: Same as SS-T with rate-of-rise  
feature.  
SS-TH: Intelligent, addressable high-  
temperature thermal (190°F/88°C) detector.  
Shipping weight  
4.8 oz. (137 g).  
Bases:  
Operating temperature range  
SS-T, SS-TR: –20°C to 38°C (–4°F to  
100°F)  
SS-B6: Standard U.S. low-profile base, UL  
Listing.  
B501BP: Standard European flangeless  
base, pkg. of 10.  
B501BH: Sounder base, includes B501  
base above.  
B501BHT: Same as B501BH, but includes  
temporal sounder.  
SS-TH: –20°C to 66°C (–4°F to 150°F).  
XP-4: Extension pole for XR2B. Comes in  
three 5-ft. sections.  
Detector spacing  
UL approved for 50 ft. (15.24 m) center  
to center. FM approved for 25 x 25 ft.  
(7.62 x 7.62 m) spacing.  
Detector Guards:  
NOTE: The following guards are not UL listed  
with the SS-T detectors. Consult with AHJ.  
B224RB: Intelligent relay base.  
B224BI: Intelligent isolator base. Isolates  
SLC from loop shorts.  
Relative humidity  
10% – 93% noncondensing.  
STI 9601: Low-profile, flush-mount smoke  
detector guard, wire.  
Thermal ratings  
STI 9602: Low-profile, surface-mount, smoke  
Accessories:  
Fixed-temperature setpoint 135°F (57°C),  
rate-of-rise detection 15°F (8.3°C) per  
minute, high temperature heat 190°F  
(88°C).  
detector guard, wire.  
RA400Z: Remote LED annunciator. 3 – 32  
VDC. Fits U.S. single-gang electrical box.  
Supported by SS-B6 and B501 bases only.  
SMK400: Surface mounting kit provides for  
entry of surface wiring conduit. For use  
with B501 base only.  
RMK400: Recessed mounting kit. For use  
with B501 base only.  
SMB600: Surface mounting kit for use with  
STI 9609: High-profile, flush-mount, smoke  
detector guard, wire.  
STI 9605: High-profile, surface-mount, smoke  
detector guard, wire.  
STI 9604: Flush-mount heat detector  
guard, wire.  
STI 9610: Surface-mount heat detector  
guard, wire.  
STI-8200-SS: Flush-mount stainless steel  
smoke detector guard  
STI-8230-SS: Surface-mount stainless  
steel smoke detector guard  
ELECTRICAL SPECIFICATIONS:  
Voltage range  
15 - 32 volts DC peak.  
Standby current (max. avg.)  
200 µA @ 24 VDC (without communica-  
tion); 300 µA @ 24 VDC (one communi-  
cation every 5 seconds with LED en-  
abled).  
Wiring Diagrams  
LED current (max.)  
6.5 mA @ 24 VDC (“ON”).  
BASES AVAILABLE:  
SS-B6: 6.1" (15.5 cm) diameter.  
B501: 4.1" (10.4 cm) diameter.  
B501BH or B501BHT: Sounder base  
assembly. Includes B501 base.  
B224RB Relay Base: Screw terminals:  
up to 14 AWG (2.0 mm²). Relay type:  
Form-C. Rating: 2.0 A @ 30 VDC  
resistive; 0.3 A @ 110 VDC inductive; 1.0  
A @ 30 VDC inductive. Dimensions: 6.2"  
(15.748 cm) x 1.2" (3.048 cm).  
B224BI Isolator Base: Dimensions: 6.2"  
(15.748 cm) x 1.2" (15.748 cm). Maxi-  
mum: 25 devices between isolator  
bases. See Note 2 under Installation on  
page 1.  
Gamewell-FCI  
12 Clintonville Road  
Northford, CT 06472-1610  
Phone: 203-484-7161  
Fax: 203-484-7118  
Address dial on back of detector.  
Specifications and wiring information are provided for information only and are believed  
to be accurate. Gamewell-FCI assumes no responsibility for their use.  
Data and design are subject to change without notice. Installation and wiring instructions  
shipped with the product shall always be used for actual installation. For more  
information, contact Gamewell-FCI.  
www.gamewell-fci.com  
AHoneywell Company  
© 2006 Gamewell-FCI  
Page 2 of 2  
SS-T Series  
CS-2460 09/01/06  

相关型号:

B501BHT-2

Intelligent Low Profile Plug-in Detectors
SYSTEMSENSOR

B501BP

Intelligent Addressable Plug-In Ionization Smoke Detector
GAMEWELL-FCI

B502

BLOCK TYPE AUTOMOTIVE PECTIFIER
MIC

B502-N

BLOCK TYPE AUTOMOTIVE PECTIFIER
MIC

B502-P

BLOCK TYPE AUTOMOTIVE PECTIFIER
MIC

B5020

UL94V-0 PBT impeller and frame
MECHATRONICS

B5020L

UL94V-0 PBT impeller and frame
MECHATRONICS

B5021RW

Analog Circuit
MPD

B5021RW-H

Analog Circuit
MPD

B5022RW

Analog Circuit
MPD

B5022RW-H

Analog Circuit
MPD

B5023RW

Analog Circuit
MPD