SS-T Series
Features
• Sleek, low-profile, stylish design.
• State-of-the-art thermistor technology
for fast response.
Intelligent Addressable Plug-In
Thermal (Heat) Detectors
• SS-TR rate-of-rise model: 15°F (8.3°C)
per minute.
• SS-T fixed heat, Factory preset at
135°F (57°C).
• SS-TH high temperature model of
190°F (88°C).
• Addressable by devices via decade
address switches.
Description
Gamewell’s SmartScanTM intelli-
gent plug-in smoke detectors with
integral communication provide
features that surpass conven-
tional detectors. Detector sensi-
tivity can be programmed in the
control panel software. Sensitiv-
ity is continuously monitored and
reported to the panel. Point ID
capability allows each detector’s
address to be set with decade
• Rotary, decimal addressing (1 – 99)
• Two-wire SLC connection.
• Visible LEDs “blink” every time the unit
is addressed.
• 360°-field viewing angle of the visual
alarm indicators (two bicolor LEDs).
LEDs blink green in Normal condition
and turn on steady red in Alarm.
• Integral communications and built-in
device-type identification.
6936pho1.jpg
SS-T in SS-B6 base
• Remote test feature from the panel.
• Built-in functional test switch activated
by external magnet.
address switches, providing exact detector locations for selective maintenance
and troubleshooting. SS-T Series thermal detectors use an innovative ther-
mistor sensing circuit to produce 135°F/57°C fixed-temperature (SS-T) and rate-
of-rise thermal detection (SS-TR) in a low-profile package. SS-TH provides fixed
high-temperature detection at 190°F/88°C in a low-profile package as well. These
thermal detectors provide cost effective, intelligent property protection in a vari-
ety of applications. SS-T Series addressable detectors are compatible with
Gamewell’s 602, 610, 632, 654 and 658 addressable fire alarm control panels
with a SmartScanTM SLC.
• Low standby current.
• Built-in tamper-resistant feature.
• Designed for direct-surface or electrical-
box mounting.
• Sealed against back pressure.
• Plugs into separate base for ease of
installation and maintenance. Separate
base allows interchange of photoelec-
tric, ionization and thermal sensors.
• SEMS screws for wiring of the separate
base.
• Constructed of off-white Bayblend®,
designed to commercial standards, and
offers an attractive appearance.
• 94-5V plastic flammability rating.
• Remote LED output connection to
optional RA400Z remote LED annuncia-
tor.
Installation
The SS-T Series of plug-in intelligent, addressable thermal detectors use a sepa-
rate base to simplify installation, service, and maintenance. Installation instruc-
tions are shipped with each detector.
Mount base (all base types) on an electrical backbox which is at least 1.5" (3.81
cm) deep. Suitable back boxes include:
• Optional sounder, relay, and isolator
bases.
• Optional recessed (RMK400) or surface
(SMK400) base mounting kits.
• 4.0" (10.16 cm) square box.
• 3.5" (8.89 cm) or 4.0" (10.16 cm) octagonal box.
• Single-gang box (except relay or isolator base).
• With B501BH or B501BHT base, use a 4.0" (10.16 cm) square box.
• With B224RB or B224BI base, use a 3.5" (8.89 cm) or 4.0" (10.16 cm) oc-
tagonal box, or a 4.0" (10.16 cm) square box.
Listings
Listings and approvals below apply to
the SS-T Series of intelligent, address-
able thermal (heat) detectors. In some
cases, certain detectors may not be
listed by certain approval agencies, or
listing may be in process. Consult
factory for latest listing status.
NOTES: 1) Because of the inherent supervision provided by the SLC loop, end-of-line resis-
tors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring.
2) When using relay or sounder bases, consult the SS-LI data sheet for device limitations
between isolator modules and isolator bases.
Applications
Use thermal detectors for protection of property. For further information, go to
systemsensor.com for manual I56-407-00, Applications Manual for System
Smoke Detectors, which provides detailed information on detector spacing, place-
ment, zoning, wiring, and special applications.
• UL Listed: file S2527.
• CSFM approved: file 3240-1288:166.
• MEA approved: file 383-02-E Vol. V.
Bayblend® is a registered trademark of Bayer Corporation.
SS-T Series CS-2460 09/01/06
Page 1 of 2
Specifications
Product Line Information
SS-T: Intelligent, addressable thermal
detector. Must be mounted to one of the
bases listed below.
SS-B6.
Size
BCK-200B: Black detector covers, box of
10.
M02-04-01: Test magnet.
M02-09-00: Test magnet with telescope
stick.
XR2B: Detector removal tool. Allows
installation and/or removal of SS-T Series
thermal detector heads from base in high
ceiling installations.
T55-127-000: Detector removal tool without
pole.
2.1" (5.3 cm) high x 4.1" (10.4 cm)
diameter installed in B501 base, 6.1"
(15.5 cm) diameter installed in SS-B6
base.
SS-TR: Same as SS-T with rate-of-rise
feature.
SS-TH: Intelligent, addressable high-
temperature thermal (190°F/88°C) detector.
Shipping weight
4.8 oz. (137 g).
Bases:
Operating temperature range
SS-T, SS-TR: –20°C to 38°C (–4°F to
100°F)
SS-B6: Standard U.S. low-profile base, UL
Listing.
B501BP: Standard European flangeless
base, pkg. of 10.
B501BH: Sounder base, includes B501
base above.
B501BHT: Same as B501BH, but includes
temporal sounder.
SS-TH: –20°C to 66°C (–4°F to 150°F).
XP-4: Extension pole for XR2B. Comes in
three 5-ft. sections.
Detector spacing
UL approved for 50 ft. (15.24 m) center
to center. FM approved for 25 x 25 ft.
(7.62 x 7.62 m) spacing.
Detector Guards:
NOTE: The following guards are not UL listed
with the SS-T detectors. Consult with AHJ.
B224RB: Intelligent relay base.
B224BI: Intelligent isolator base. Isolates
SLC from loop shorts.
Relative humidity
10% – 93% noncondensing.
STI 9601: Low-profile, flush-mount smoke
detector guard, wire.
Thermal ratings
STI 9602: Low-profile, surface-mount, smoke
Accessories:
Fixed-temperature setpoint 135°F (57°C),
rate-of-rise detection 15°F (8.3°C) per
minute, high temperature heat 190°F
(88°C).
detector guard, wire.
RA400Z: Remote LED annunciator. 3 – 32
VDC. Fits U.S. single-gang electrical box.
Supported by SS-B6 and B501 bases only.
SMK400: Surface mounting kit provides for
entry of surface wiring conduit. For use
with B501 base only.
RMK400: Recessed mounting kit. For use
with B501 base only.
SMB600: Surface mounting kit for use with
STI 9609: High-profile, flush-mount, smoke
detector guard, wire.
STI 9605: High-profile, surface-mount, smoke
detector guard, wire.
STI 9604: Flush-mount heat detector
guard, wire.
STI 9610: Surface-mount heat detector
guard, wire.
STI-8200-SS: Flush-mount stainless steel
smoke detector guard
STI-8230-SS: Surface-mount stainless
steel smoke detector guard
ELECTRICAL SPECIFICATIONS:
Voltage range
15 - 32 volts DC peak.
Standby current (max. avg.)
200 µA @ 24 VDC (without communica-
tion); 300 µA @ 24 VDC (one communi-
cation every 5 seconds with LED en-
abled).
Wiring Diagrams
LED current (max.)
6.5 mA @ 24 VDC (“ON”).
BASES AVAILABLE:
SS-B6: 6.1" (15.5 cm) diameter.
B501: 4.1" (10.4 cm) diameter.
B501BH or B501BHT: Sounder base
assembly. Includes B501 base.
B224RB Relay Base: Screw terminals:
up to 14 AWG (2.0 mm²). Relay type:
Form-C. Rating: 2.0 A @ 30 VDC
resistive; 0.3 A @ 110 VDC inductive; 1.0
A @ 30 VDC inductive. Dimensions: 6.2"
(15.748 cm) x 1.2" (3.048 cm).
B224BI Isolator Base: Dimensions: 6.2"
(15.748 cm) x 1.2" (15.748 cm). Maxi-
mum: 25 devices between isolator
bases. See Note 2 under Installation on
page 1.
Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
Phone: 203-484-7161
Fax: 203-484-7118
Address dial on back of detector.
Specifications and wiring information are provided for information only and are believed
to be accurate. Gamewell-FCI assumes no responsibility for their use.
Data and design are subject to change without notice. Installation and wiring instructions
shipped with the product shall always be used for actual installation. For more
information, contact Gamewell-FCI.
www.gamewell-fci.com
AHoneywell Company
© 2006 Gamewell-FCI
Page 2 of 2
SS-T Series
CS-2460 09/01/06
相关型号:
©2020 ICPDF网 联系我们和版权申明