ABD-RT2F [GAMEWELL-FCI]
Single-ended reflected type beam smoke sensor; 单端反射型光束感烟传感器![ABD-RT2F](http://pdffile.icpdf.com/pdf1/p00130/img/icpdf/ABD-R_717761_icpdf.jpg)
型号: | ABD-RT2F |
厂家: | ![]() |
描述: | Single-ended reflected type beam smoke sensor |
文件: | 总2页 (文件大小:67K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
![](http://public.icpdf.com/style/img/ads.jpg)
Velociti™ Series
ABD-2F and ABD-RT2F
Single-Ended Reflected Type
Beam Smoke Sensor
Description
The Gamewell-FCI Velociti™ Series, ABD-2F and addres-
sable projected beam smoke sensor is uniquely suited to
sense smoke in hostile environments or open areas with
high ceilings where spot-type sensors are unsuitable or
difficult to install and maintain. It is intended for use in the
signaling line circuits with the E3 Series® ILI-MB-E3 and
ILI-S-E3 (Velociti mode only). The ABD-2F consists of a
combination transmitter/receiver unit and a reflector.
When smoke enters the path between the unit and the
reflector, it causes a reduction in the signal, and when the
smoke level reaches the predetermined threshold, an
alarm results.
A unique single-ended reflective design offers simpler
installation than the traditional transmitter and receiver
types of beam sensors. Alignment is swiftly accomplished
via an optical sight and a 2-digit signal strength meter inte-
gral with the product. Listed for operation from –22° F to
131° F, the ABD-2F can be installed in garages, ware-
houses and other hostile environments where temperature
extremes exceed the capability of spot-type sensors.
ABD-2F/RT2F
Features
•
•
•
Single-ended, reflective design
Six (6), user-selectable sensitivity levels
16 to 328 foot (4.9 to 99.9 m) detection range
The Velociti™ Series uses a communication protocol that
substantially increases the speed of communication
between the sensors and Gamewell-FCI analog address-
able fire alarm controls. These devices operate in a
grouped fashion. If one of the devices in the group
changes status, the panel’s microprocessor stops the
group poll and concentrates on the single device. The net
effect is response speed up to five times greater than ear-
lier designs.
•
•
•
•
•
Compatible with the E3 Series® ILI-MB-E3 and ILI-S-E3
Integral sensitivity test feature (ABD-2SF)
Digital display - no special tools required
User-friendly alignment procedure
Integral automatic gain control compensates for signal
deterioration from dust build-up
•
Remote test station (optional)
The unit has four (4), standard sensitivity selections along
with two (2), Acclimate settings. When either of the two
Acclimate settings are selected, the sensor will automati-
cally adjust its sensitivity using advanced software algo-
rithms to select the optimum sensitivity for the specific
environment.
An ISO 9001-2000 Company
SIGNALING
®
FM
Velociti™ is a trademark and E3 Series is a registered trademark of Honeywell
MEA
International Inc.
APPROVED
Approved
S1913
3023594 219-02-E Vol. VI 07260-0694:262
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
©2007 by Honeywell International Inc. All rights reserved.
Specifications are for information only, are not intended for installation pwurpwoswes,.ganadmareeswubejecllt-tofcchia.cngoemwithout notice. No responsibility is assumed by Gamewell-FCI for their use.
9020-0623 Rev. B1 page 1 of 2
Description (continued)
Ordering Information
The ABD-RT2F is equipped with an integral sensitivity test
feature consisting of a test filter attached to a servo motor
inside the sensor optics. The ABD-RT2F requires an addi-
tional, external power supply. Using the remote test station
Model RTS451, the motor moves the filter in the path of
the light beam, thereby serving as an accurate test of the
receiver sensitivity. This test feature allows the user to
quickly and easily meet the annual maintenance and test
requirements of NFPA 72.
Model
Description
ABD-2F
Single-ended reflected type beam smoke
sensor
ABD-RT2F Single-ended smoke sensor with integral
sensitivity test
BEAMLRK Long range accessory kit (required for
applications with a range over 230 ft. (70m)
BEAMMMK Multi-mount kit (provides ceiling or wall
mount capability with increased angular
adjustment)
Specifications
BEAMSMK Surface mount kit
RTS451
Remote test station
Operating Temperature
Range:
RTS451KEY Remote test station with key lock
-22° F to 131° F
(-30° C to 55° C)
Operating Humidity
Range:
10% to 93 RH
non-condensing
Dimensions:
Detector:
10” H x 7.5” W x 3.3” D
(25.4 H x 19 W x 8.4 D cm)
16-230 ft. (4.9 x 70.1 m)
7.9” H x 9.1” W
Reflector:
(20 H x 23 W cm)
Voltage Range:
Alarm Current:
Standby Current:
15 to 32 VDC
8.5 mA max.
2 mA max. avg. @ 24 VDC
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9020-0623 Rev. B1 page 2 of 2
www.gamewell-fci.com
相关型号:
![](http://pdffile.icpdf.com/pdf2/p00239/img/page/ABCBFC00C0_1447290_files/ABCBFC00C0_1447290_1.jpg)
![](http://pdffile.icpdf.com/pdf2/p00239/img/page/ABCBFC00C0_1447290_files/ABCBFC00C0_1447290_2.jpg)
ABD6F150C0
Mains Power Connector, 10/15A, 125/250VAC, Male, Solder Terminal, ROHS COMPLIANT
SCHURTER
![](http://pdffile.icpdf.com/pdf2/p00240/img/page/ABDBFC00C0_1447793_files/ABDBFC00C0_1447793_1.jpg)
![](http://pdffile.icpdf.com/pdf2/p00240/img/page/ABDBFC00C0_1447793_files/ABDBFC00C0_1447793_2.jpg)
ABD6FC00C0
Mains Power Connector, 10/15A, 125/250VAC, Male, Solder Terminal, ROHS COMPLIANT
SCHURTER
![](http://pdffile.icpdf.com/pdf2/p00239/img/page/ABCBFC00C0_1447290_files/ABCBFC00C0_1447290_1.jpg)
![](http://pdffile.icpdf.com/pdf2/p00239/img/page/ABCBFC00C0_1447290_files/ABCBFC00C0_1447290_2.jpg)
ABDBF150C0
Mains Power Connector, 10/15A, 125/250VAC, Male, Solder Terminal, ROHS COMPLIANT
SCHURTER
![](http://pdffile.icpdf.com/pdf2/p00240/img/page/ABDBFC00C0_1447793_files/ABDBFC00C0_1447793_1.jpg)
![](http://pdffile.icpdf.com/pdf2/p00240/img/page/ABDBFC00C0_1447793_files/ABDBFC00C0_1447793_2.jpg)
ABDBFC00C0
Mains Power Connector, 10/15A, 125/250VAC, Male, Solder Terminal, ROHS COMPLIANT
SCHURTER
©2020 ICPDF网 联系我们和版权申明