FC-10C
TEN ZONE PANEL
Conventional Fire Alarm Control
Description
The FC-10C Fire Alarm Control panel is a proven, versa-
tile, ten-zone modular control with integral communicator
and remote-site upload/download capability. It meets the
requirements of NFPA Standard 72 for Central Station,
Protected Premises, and Remote (DACT) Supervising
Station Fire Alarm Systems. It is Listed to UL Standard
864, inherently power limited and meets all UL transient
immunity requirements.
The integral communicator includes a wide range of se-
lectable transmission formats to communicate to virtually
all central stations. Other features of the communicator
are: A line-active indicator for each of two phone lines,
“Kiss-Off” signal LED, dual “low telephone voltage detect”
circuitry, programmable event codes per format and se-
lectable/deselectable transmission of up to 100 events.
FC-10C
Features
• Inherently power-limited.
Multiple security techniques allow uploading or download-
ing within one minute without affecting normal fire panel
functions. Key system information that can be uploaded
are: Current System Status, History, Walk Test Files and
System Programming.
• Integral digital communicator.
• Fifteen (15) selectable transmission formats.
• Up to 100 transmitted events/messages.
• Fire Drill Function.
• Integral voltmeter.
An integral voltmeter allows voltage measurements for
Zone, AC line, NAC1, NAC2, resettable power and bat-
tery.
Housed in a red steel enclosure, the surface mounted
unit, (trim ring optional) provides space for two (2) B-7R
batteries.
• Fully programmable via integral keypad.
• Auto-reset supervisory operation.
• Temporal pattern output per ANSI S3.41.
• Single person walk test with 256 event walk test
memory.
• Alarm verification.
• Real-time clock/calendar.
• 256-Event History with time and date stamp, stored in
The many features of the FC-10C control provide a cost
effective approach to systems design, and allow a great
degree of flexibility in one enclosure. Many of these fea-
tures include two (2) notification appliance circuits
(expandable to four) with output expandable from 3.0 to
6.0 amps total. Class A operation is possible with optional
modules. Fully programmable via integral keypad, the
notification appliance circuits may be programmed Si-
lenceable, Non-silenceable, Auto-silence (program 5 to 30
minutes) and Silence Inhibit (60 seconds).
permanent memory.
• Zone disable feature via software.
• Two (2) fully programmable Form “A” relay contact
output.
• Programmable trouble reminder.
• Surface mount technology.
• Ground start module (optional).
• Contact-by-Zone module (optional).
• Serial annunciator output (optional).
• Printer interface for on or off-line printing (optional)
Initiating zones may be programmed for process monitor-
ing via latching or non-latching contact closure and can be
used to monitor high-low temperature, loss of air flow,
water level, gas detection, open/close, refrigeration and
non-fire related tamper functions.
An ISO 9000-2000 Company
Also programmable are Alarm Presignal Timer, Alarm
Verification Timer and Optional Trouble Reminder.
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: 203-484-7161 - Fax: 203-484-7118
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2006 Gamewell-FCI. All rights reserved.
www.gamewell-fci.com
9020-0459 Rev. G page 1 of 2
Description (Continued)
Ordering Information
Part Number Description
Optional modules are available for ground start opera-
tion, trouble reminder and addition of two (2) fully pro-
grammable Form “C” relays. An optional serial interface
allows for a choice of remote annunciators with switches
for Reset, Drill, Silence and Acknowledge.
700-01198
700-01199
700-01216
700-01192
FC-10C
(Ten zone control communicator)
FC-10C PCB
Ten Zone Module, replacement board
FC-10TR
Trim Ring
PRT-24
Specifications
Printer interface module - provides
EIA-232 printer output.
Operating temperature:
Relative humidity:
Dimensions:
32° - 120° F (0° - 49° C)
85 % (non-condensing)
Includes cable, DB9F and DB25
adapter.
Door
17 1/8" H x 14 3/4" W
(43.46 x 37.36 cm)
16 7/8" H x 14 1/2" W x 4 1/2" D
(42.93 x 36.83 cm x 11.43 cm)
20 1/8" H x 17 5/8" W
(50.85 x 44.75 cm)
700-01201
700-01202
LED-101M
RS-485 interface module
RZA-10
Remote zone annunciator, 10 zones
(requires one (1) LED-101M)
Backbox
Trim Ring
Mounts on three-gang box.
RZA-10L
Remote zone annunciator, 10 zone
limited.
700-01203
700-01204
UL Listed Receivers compatible with FC-10C:
• Ademoco 685
• Silent Knight 9000
• ITI-CS-4000
• Osborne Hoffman Models 1 / 2
• Radionics 6000/6500
• Sescoa 3000R
(requires one (1) LED-101M) mounts
on three-gang box.
• FBI CP220FB
RZA-10LS2
Remote zone annunciator, 8 red, 2
yellow LEDs
(requires one (1) LED-101M) mounts
on three-gang box.
700-01205
700-01206
ACM-8RF
Eight-relay module (contact-by-zone)
CAC-10F
Class “A” initiating circuit converter
module
700-01207
NAC-REM
Two NAC/two form “C” add-on
module
700-01213
700-01222
SK-10C
Software kit (upload/download utility)
120 VAC, 100 VA transformer, ex-
pands NAC power
from 3.0 to 6.0 amperes and system
power from 3.6 to 6.6 amperes.
600-90000
MCBL-7
DACT phone cord, 7 feet long (2 re-
quired)
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com 9020-0459 Rev. G page 2 of 2
相关型号:
©2020 ICPDF网 联系我们和版权申明