Description  
NAC Expander/Power Supply  
The FireForce 8 (FF8) from Gamewell-FCI is a Notification  
Appliance Circuit (NAC) extender panel designed to extend  
the power capabilities of existing NACs and provide power  
(1.5 A) for other ancillary devices. The FF8 will connect to  
any brand of a UL-Listed Fire Alarm Control Panel (FACP)  
to provide Notification Appliance Circuit expansion.  
Designed with advanced switch-mode power-supply tech-  
nology, the FireForce 8 provides filtered and electronically-  
regulated power distributed to four (4) NACs. Each NAC is  
rated at 3.0 Amp. maximum, with a total output capacity of  
8.0 Amp. The outputs may be configured as the following:  
Four (4), Class B (Style W, X, Y)  
Two (2), Class A (Style Z)  
Two (2), Class B and one Class A  
Four (4), Class A (Style Z) with the optional Class A  
adaptor installed  
FireForce 8  
Features  
The FF8 includes an internal battery charger.  
Provides two fully-supervised input/control circuits  
Redundant activation option for survivability  
Multiple sync protocols, compatible with the following  
appliances: Cooper-Wheelock, Faraday, System Sen-  
sor, Amseco, and Gentex-as field-selectable options  
Four (4) configurable supervised NAC outputs  
8.0 Amp., 24 VDC, fully regulated full-load output  
(power-limited)  
Output fault notification to FACP  
1.5 A auxiliary power output  
Eight trouble and status LEDs  
Common trouble Form-C relay  
Isolated AC Fail Form-C relay, immediate or delayed  
six hours  
Ground fault detection  
26 AH battery charger capability  
Selectable temporal coding  
Facilitates multiple NAC synchronization for large  
areas  
Optional multipack for up to four FF8s in a single lock-  
able enclosure  
Gamewell-FCI’s FF8 provides independent output circuit  
supervision. In the event of a NAC fault, the FF8 can be  
configured to notify the FACP. The FF8 has field-select-  
able, built-in strobe and horn sync protocols. Protocols  
support Faraday, Gentex, System Sensor, Amseco, and  
Cooper-Wheelock devices; or pass through a pre-gener-  
ated sync protocol from a single synchronization source.  
This eliminates the need for additional individual sync mod-  
ules. Independent horn silencing via sync protocol allows  
synchronized horns and strobes to operate on a single cir-  
cuit.  
One of the most challenging aspects of a retrofit application  
is locating the existing EOL resistor. In retrofit applications  
that have EOL values other than the 3.9K ohm EOL resis-  
tor normally used with the FF8, a single resistor matching  
the existing EOL can be used as a reference EOL for all  
outputs. This feature speeds installation and system check-  
out. The reference resistor must be within a range of 2K  
ohm to 25K ohm.  
Optional Class A adaptor  
“FireForce 8” labeling is placed on the cabinet front, mak-  
ing the FF8 ideal for all retrofit applications.  
An ISO 9000-2000 Company  
For enhanced notification appliance circuit survivability, the  
FF8 can utilize its dual-activation inputs for redundant trip  
operation.  
SIGNALING  
MEA  
Approved  
206-01-E 7300-1288:162  
S521  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.  
©2007 by Honeywell International Inc. All rights reserved.  
www.gamewell-fci.com  
CS-2282 Rev. a page 1 of 2  
Engineer’s Specifications  
Specifications (Continued)  
The Fire Alarm System shall be designed with remotely  
located Notification Appliance Circuit (NAC) Expander/  
Power Supplies for the support of notification appliances.  
The remote Power Supplies shall be fully supervised and  
shall provide 8.0 Amps. of notification appliance power and  
1.5 Amps. of auxiliary power output. The NAC Extender  
Panel shall be able to select strobe synchronization proto-  
col via an internal dip switch. There shall be five selectable  
protocols available. The NAC Extender Panel shall syn-  
chronize all outputs simultaneously. The NAC Extender  
Panel shall be able to use existing notification appliance  
circuit’s end-of-line resistors in the range of 2K – 25K ohms  
for retrofit applications. The internal battery charging circuit  
shall charge up to 26 AH batteries. The NAC Expander/  
Power Supply shall be a Gamewell-FCI FireForce 8.  
Input Control Circuit: 16 – 30 VDC @ 5 mA minimum  
Temperature Rating: 32°F to 120°F (0°C to 49°C)  
Relative Humidity:  
Dimensions:  
10 - 93%, non-condensing  
FF8 Cabinet:  
18.0" H x 12.5" W x 4.5" D  
(45.72 H x 31.75 W x 11.43 D cm)  
FF8-MP Cabinet:  
37.2" H x 24.0" W x 6.0" D  
(94.49 H x 60.96 W x 15.24 D cm)  
Field Selectable NAC Signaling  
INPUT OUTPUT (Follows Input)  
Temporal  
Steady  
Steady  
Steady  
Sync  
Steady - SYNC  
Steady with Noise Eliminated  
Sync  
Options  
31081  
SCE-95 mounting plate provides a means to install two (2)  
SCE-95 modules. The addition of SCE-95s provides a  
means to run on FF8 outputs via a panel command on an  
SLC. The 31081 mounts over the main PCB and is hinged  
for access to FF8 terminal.  
Ordering Information  
Model  
FF8  
Description  
24 VDC, 8.0 Amp., fire alarm NAC  
expander/ power supply with integral  
battery charger  
FF8-MP  
Multipack FF8 option provides a means to place up to four  
(4) FF8s or 31085s (XP95 device mounting plates) in a sin-  
gle lockable enclosure. UL approved.  
FF8-MP  
Multipack cabinet with one FF8 and  
space for up to three additional FF8-CMs  
or 31085s (See Options Section).  
FF8-CM  
31076  
Chassis assembly version of FF8, for  
mounting in FF8-MP spaces  
Class A adaptor, converts signal circuits  
to Class A wiring (See Options Section).  
Mounting plate for placing up to two  
SCE-95 modules into the FF8  
(FF8 and FF8-MP compatible, See  
Options Section).  
31076  
Class A adaptor converts the four (4) Class B outputs to  
four (4) Class A outputs.  
31081  
Specifications  
31085  
Mounting plate for placing XP95 devices  
into the FF8-MP; includes standoffs for  
eight devices  
Battery, 12 VDC, 7 AH  
(two required for 24 V operation)  
Battery, 12 VDC, 12 AH  
Primary Input Power: 120 VAC, 60 Hz, 3.0 A  
or 220 V, 1.5 A; jumper selectable  
Secondary Power:  
24-volt operation: two 7 – 24 AH  
batteries  
BAT-1270  
Battery Charging  
Capacity:  
BAT-12120  
Up to 26 AH batteries  
(two required for 24 V operation)  
Battery Space:  
Up to two 12 AH batteries maxi-  
mum inside the FF8 cabinet.  
Larger batteries require a separate  
battery cabinet  
Total Output Power: 8.0 A maximum  
Standby Current:  
Auxiliary Power  
Output:  
0.030 A  
0.15 A under all conditions  
1.5 A, if load is removed during  
operation (external relay or AC  
Fail relay use required).  
NAC Output Ratings: 24 VDC fully regulated, 3.0 A  
maximum per circuit (8.0 A total)  
End-of-Line Resistor  
Range:  
2K to 25K, 1/2 watt  
Common Trouble  
Relay, AC Fail Relay:  
2.0 A/28 VDC or 120 VAC  
GAMEWELL-FCI  
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118  
CS-2282 Rev. a page 2 of 2  
www.gamewell-fci.com  

相关型号:

31087

SOLISTRAND, Budget and DIAMOND GRIP
MACOM

31088

SOLISTRAND, Budget and DIAMOND GRIP
MACOM

31089

SOLISTRAND, Budget and DIAMOND GRIP
MACOM

3108A

RS485, 3 Pr #22 Str TC, PO Ins, OSTC Brd, PVC Jkt, CM
BELDEN

3108A0101000

RS485, 3 Pr #22 Str TC, PO Ins, OSTC Brd, PVC Jkt, CM
BELDEN

3108A0102000

RS485, 3 Pr #22 Str TC, PO Ins, OSTC Brd, PVC Jkt, CM
BELDEN

3108A0105000

RS485, 3 Pr #22 Str TC, PO Ins, OSTC Brd, PVC Jkt, CM
BELDEN

3108NL-04W-B10-P00

3108NL (80 X 20L)
HAMMOND

3108NL-04W-B20-P00

3108NL (80 X 20L)
HAMMOND

3108NL-04W-B30-P00

3108NL (80 X 20L)
HAMMOND

3108NL-04W-B40-P00

3108NL (80 X 20L)
HAMMOND

3108NL-04W-B50-P00

3108NL (80 X 20L)
HAMMOND