JAGUAR VX  
Torque Vector System  
Sensorless Vector Variable Frequency Inverters  
- 0.4kW to 280kW  
High performance, Torque Vector Control  
Up to 250% torque at 1Hz  
Low torque ripple at low speed  
Fast torque response - 200mS, 0 - 100% load  
Load speed regulation < 1% open loop  
User friendly self tuning to motor  
Ultra compact IP20 enclose (22kW)  
Dual LED/LCD plain English display  
User programmable I/O  
Low motor noise profile  
Auto energy saving function  
Renowned IMO 5 year warranty  
5
Specifications  
JAGUAR VX ORDER CODES  
JAGUAR VXP ORDER CODES  
MOTOR RATING (kW)  
VX40  
-
VX75  
-
VX150  
-
VX220  
-
VX400  
VX550  
VX750 VX1100 VX1500 VX1850 VX2200  
-
4
-
VX750P VX1100P VX1500P VX1850P VX2200P  
0.4  
1.5  
1.7  
0.75  
2.5  
1.5  
2.2  
5.5  
13  
7.5  
18  
11  
24  
15  
30  
18.5  
39  
22  
45  
72  
RATED O/P CURRENT (A)  
100% RATED I/P CURRENT RMS  
(AT 400V)*  
3.7  
5.5  
9
2.9  
5.5  
7.7  
12.6  
18.2  
24.4  
36.3  
48.5  
59  
HEAT LOSS (W)  
45  
50  
65  
85  
110  
140  
200  
315  
340  
450  
510  
(AT 2 KHz CARRIER FREQUENCY)  
INPUT VOLTAGE/FREQUENCY  
WEIGHT (Kg)  
3 PHASE  
380 TO 415V (+10%,-15%)  
50/60 Hz (+5%,-5%)  
10.6/6.5 10.6/11.5 10.6/11.5 10.6/12  
0.95 0.94 0.95 0.96  
0.2 - 400 Hz (‘P’ MODELS 0.2 - 120 Hz)  
2.4  
3.2  
3.2  
3.2  
3.2  
6.5  
5.3/6.5  
0.95  
INPUT POWER FACTOR**  
OUTPUT VOLTAGE FREQUENCY  
0.96  
0.95  
0.94  
0.93  
0.94  
0.95  
3 PHASE  
0 - V INPUT  
JAGUAR VX ORDER CODES  
JAGUAR VXP ORDER CODES  
MOTOR RATING (kW)  
VX30K VX37K  
VX45K VX55K VX75K  
VX90K VX110K VX132K VX160K VX200K VX220K  
VX30KP VX37KP VX45KP VX55KP VX75KP VX90KP VX110KP VX132KP VX160KP VX200KP VX220KP VX280KP  
30  
60  
58  
37  
75  
71  
45  
91  
85  
55  
75  
90  
110  
210  
203  
132  
253  
243  
160  
304  
293  
200  
377  
363  
220  
415  
400  
280  
520  
508  
RATED O/P CURRENT (A)  
100% RATED I/P CURRENT RMS  
(AT 400V)*  
112  
104  
150  
141  
176  
168  
HEAT LOSS (W)  
1200  
1400  
1600  
1900  
2300  
2700  
3000  
3400  
4000  
4600  
5000  
6000  
(AT 2 KHz CARRIER FREQUENCY)  
INPUT VOLTAGE/FREQUENCY  
WEIGHT (Kg)  
3 PHASE  
380 TO 415V (+10%,-15%)  
50/60 Hz (+5%,-5%)  
120/125 125/177  
36  
36/37  
0.95  
37/44  
0.95  
45/54  
0.95  
54/61  
0.95  
61/88  
0.95  
88  
88/120  
0.95  
177  
177  
INPUT POWER FACTOR**  
OUTPUT VOLTAGE FREQUENCY  
0.95  
0.95  
0.95  
0.95  
0.95  
0.95  
3 PHASE  
0 - V INPUT  
0.2 - 400 Hz (‘P’ MODELS 0.2 - 120 Hz)  
NOTES  
*
FIGURES FOR INPUT ARE QUOTED WHEN USING A DC REACTOR FROM VX30K AND VX30KP UP, NO REACTOR < 30KW  
**  
AT 100% FULL LOAD CURRENT AND USING DC REACTOR  
PRICE  
INFORMATION  
AND ORDERING  
Jaguar VX  
Basic circuit configuration and terminals  
WARNING! INVERTER MUST  
BE EARTHED  
Braking resistor (option)  
RTS = Volt-free NC contact  
for thermal protection.  
for all inverters.  
RTS  
BU  
DC Bus reactor  
Terminal Markings for DC  
Terminal Makings for DC  
*
(Optional 22kW)  
bus reactor and Braking  
P(+)  
GND  
(PE)  
DB  
Resistor for Braking Unit  
2
1
GND  
(PE)  
Braking unit (option).  
0V  
The marking of these  
Applicable to VX1100, VX1500P, VX30K  
and inverters larger than these.  
terminals varies between  
24V  
different sizes of Jaguar VX  
Link P1 to ( )  
inverter. Please refer to  
*
On-board braking IGBT and resistor applicable  
only to VX40 to VX750 and VX750P to VX1100P.  
Disconnect the internal resistor (R) before  
connecting an external resistor.  
P(+)  
N(-)  
if DC reactor  
manual for specific details.  
not required  
P1  
*
*
*
Input  
contactor  
R
L1  
U
3-phase  
power  
supply  
50Hz or  
60Hz  
V
L2  
L3  
M
W
Note (1)  
GND  
Power  
(PE)  
Current  
detection  
charge  
LED  
Connect via  
(13) +10V DC  
(12)  
Z
(11)  
0V  
RF filter (if fitted)  
Analog voltage  
frequency ref.  
input  
SMPS  
+24V DC  
‘CRG’  
Gate  
drive  
Voltage  
detection  
(Pot. 1k, 1W)  
Note (2)  
A/D  
Earth busbar  
at MCC  
DC voltage  
detection  
250Ω  
(C1)  
+ve  
4-20mA  
analog input  
Keypad Panel  
Programmable  
analog  
output  
(FMA)  
LED, LCD  
displays  
Keys  
CPU  
0 to 10V DC  
(FMP)  
(CM)  
Pulse output  
0V  
Digital  
output  
Frequency  
command  
switch  
PWM  
generator  
PRICE  
(V1)  
Note (3)  
INFORMATION  
AND ORDERING  
Accel /  
Decel  
Auto-  
voltage  
regulator  
(FWD)  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
4.7kΩ  
regulator  
(REV)  
(THR)  
(HLD)  
(X1)  
Torque  
vector  
calculator  
Function  
generator  
BU  
RTS  
A/D  
1
2
Protective  
logic  
CPU  
Input  
signal  
Run  
relay  
output  
(AX1)  
(AX2)  
Note (3)  
(X2)  
Control  
inputs  
(30C)  
(30B)  
(30A)  
Trip  
relay  
output  
(X3)  
(X4)  
(Y1E)  
(Y2E)  
(Y3E)  
(Y4E)  
(X5)  
(BX)  
Output  
signal  
Programmable  
outputs  
(RST)  
0V  
(Y5E)  
(P24) or (CMS)  
Note (6)  
+24V DC  
(CMC)  
(P24) or (CMS) Note (6)  
(CM)  
Note (4)  
0V  
NOTES (1) For inverters rated 22kW the inrush contactor is replaced by an SCR. 0V Common Terminals (11) and  
(2) Voltage detection circuit applicable for inverters 30kW only.  
(3) Standard for inverters 30kW, optional for smaller models.  
(4) Two terminals (CM) standard for inverters 22kW, one for 30kW.  
(5) If motor thermistors are required, please consult IMO.  
(CM) are optically isolated.  
Relay status shown as at inverter  
‘power ON’ or ‘healthy’.  
(6) Internal +24V DC supply terminal designated P24 (22kW) or CMS (30kW).  
Jaguar VX  
Control circuit connections  
Purpose  
Terminal  
Terminal Name  
Speed reference 0V common  
Potentiometer input  
Description  
11  
12  
For use with terminals 12, 13 and C1 (and V1, 30kW only)  
Maximum speed demand is at +10V with a 0V to +10V DC  
input. Input impedance 20k(22kW), 22k(30kW).  
Analog  
frequency  
setting  
13  
Potentiometer supply  
Current loop input  
Regulated +10V DC power supply for 1kmin. speed control  
potentiometer. Input 10mA max.  
C1  
Maximum speed demand is at 20mA with a 4-20mA DC  
input, impedance 250. Inverter output frequency is  
proportional to current input signal, zero speed = 4mA.  
V1*  
CM†  
FWD  
Auxiliary freq. reference  
0V common  
Bipolar 0V to ±10V input.  
0V common terminals for general use.  
If FWD and  
REV are both  
closed or both  
Forward and STOP command  
FWD-P24 closed: Motor runs forward  
open: Motor decelerates to rest  
open, inverter  
output STOPS.  
REV  
HLD  
Reverse and STOP command  
FWD/REV command hold  
REV-P24 closed: Motor runs in reverse  
open: Motor decelerates to rest  
HLD-P24 closed: Latches momentary FWD or REV inputs  
open: FWD/REV non-latching  
BX  
Coast-to-stop command  
External Trip/Alarm input  
BX-P24 closed: Inhibit inverter output instantaneously  
open: Normal  
THR  
THR-P24 closed: Normal  
open: Trip (OH2) inverter output instantaneously  
Programmable  
inputs  
If RST-P24 closed for 100ms, inverter internal fault trips are  
reset, and also alarm 30A/B/C (see below).  
RST  
Trip/Alarm RESET  
X1  
X2  
X3  
Programmable input 1  
Programmable input 2  
Programmable input 3  
Preset speeds or motorised potentiometer  
Preset speeds or mains-to-inverter changeover  
Preset acc/dec command. LOC/REM changeover.  
DC injection brake command.  
X4  
X5  
Programmable input 4  
Programmable input 5  
Preset acc/dec times. 2nd motor V/F ratio. Data protection  
enable/disable.  
24V current source for programmable I/O terminals and for  
FWD, REV, HLD, BX, THR, RST and X1 to X5.  
P24  
P24  
+24V DC power supply  
Analog meter  
Output frequency, current, torque or load factor can be  
selected. 0V to +10V DC at 2mA max. (Min. impedance 5kΩ)  
FMA  
FMP  
Meter  
outputs  
Pulse output proportional to inverter output frequency. Pulse  
frequency 6 to 100 x O/P Hz at +10V DC (adjustable).  
Pulse frequency meter  
Output:  
Open-collector common  
Programmable output 1  
Programmable output 2  
Programmable output 3  
Programmable output 4  
Programmable output 5  
CMC  
Y1E  
Y2E  
Y3E  
Y4E  
Y5E  
0V  
27V DC,  
Up to 16 different outputs can be programmed  
from the operating Functions representative of  
dynamic operating conditions.  
Factory defaults:  
Y1E Inverter running  
Y2E FAR  
Y3E FDT  
50mA per  
O/P channel,  
total 50mA  
maximum.  
Caution  
Read Technical  
Manual before  
use.  
Programmable  
outputs  
Y4E Overload early warning  
Y5E Undervoltage  
Relay changes state when an internal protection function is  
active and when the inverter trips.  
Contact: 250V AC, capacity 0.5A, cosφ 0.3  
30A  
30B  
30C  
Normally open  
Normally closed  
Common  
Relay  
outputs  
Relay closes when inverter is running  
Contact: 250V AC, capacity 0.5A, cosφ 0.3  
AX1*  
AX2*  
Run relay  
* Standard for 30kW only, optional for 22kW.  
† Two CM terminals for 22kW, one for 30kW.  
PRICE  
INFORMATION  
AND ORDERING  
Jaguar VX  
Parameter list/function code table  
Group No.  
Name  
LCD Display  
Setting range  
Unit Resol. Def.  
Basic  
Functions  
00 Frequency command  
00 FREQ COMND 0 = KEYPAD, or keys  
1 = TERMINAL, 0 to +10V  
0
2 = TERMINAL, 4 to 20mA  
01 Operating mode  
01 OPR METHOD 0 = KEYPAD, RUN/STOP keys  
1 = TERMINAL, (FWD) & (REV)  
0
02 Max. O/P frequency  
03 Base freq., motor 1  
04 Max. O/P V, motor 1  
02 MAX Hz  
VX, 50-400Hz VX…P, 50-120Hz  
VX, 50-400Hz VX…P, 50-120Hz  
Hz  
Hz  
V
1
1
1
50  
50  
03 BASE Hz -1  
04 RATED V -1  
0 = Output dependent on supply V*  
320 to 480 = output V  
400  
05 Accel. time, motor 1  
06 Decel. time, motor 1  
05 ACC TIME 1  
06 DEC TIME 1  
0.01 to 3600  
s
s
0.01 6.00  
0.01 6.00  
0.00 = ramp inhibit, or 0.01 to 3600  
07 Torque boost, motor 1 07 TRQ BOOST 1 0.0 = auto; 0.1 to 20.0 fixed boost  
0.1  
0.0  
[0.1]  
08 Electronic thermal  
08 ELECTRN OL 0 = Inactive  
1 = Active for standard motor  
1
O/L, type  
2 = Active for inverter-rated motor  
09 Electronic O/L, level  
09 OL LEVEL  
10 RESTART  
20% to 105% of inverter rating  
A
0.01  
3
10 Restart after  
momentary power  
supply failure  
0 = Inactive 1  
1 = Inactive 2  
2 = Active, smooth recovery  
3 = Active, restart at set Hz  
4 = Active, restart at start Hz  
11 O/P freq. HI limit  
12 O/P freq. LO limit  
13 Min. O/P freq. (bias)  
14 Freq. I/P ref. gain  
15 Driving torque limit  
11 H LIMITER  
12 L LIMITER  
13 FREQ BIAS  
14 FREQ GAIN  
VX, 0-400Hz VX…P, 0-120Hz  
VX, 0-400Hz VX…P, 0-120Hz  
VX, 0-400Hz VX…P, 0-120Hz  
0.0 to 200.0%  
Hz  
Hz  
Hz  
%
1
1
1
70  
0
0
0.1 100.0  
15 DRV TORQUE 20 to 180, 999% (999 = no limit)  
%
1
150  
[120]  
16 Braking torque limit  
16 BRK TORQUE 0, 20 to 180, 999% (999 = no limit)  
%
1
100  
[100]  
17 DC inj. brk. Start frequ. 17 DC BRK Hz  
18 DC inj. brk. Brkg. level 18 DC BRK LVL  
19 DC inj. brk. Brkg. time 19 DC BRK t  
0.0 to 60.0Hz  
Hz  
%
s
0.1  
0.1  
0.1  
0.0  
0.0  
0.0  
0.0 to 100%  
0.0 (brake inactive), or 0.1 to 30.0s  
20 Pre-set multistep  
to frequencies 1 to 7  
26  
20 MULTI Hz -1  
to  
26 MULTI Hz -7  
VX  
0.00, 0.20 to 400.0Hz  
Hz  
0.01 0.00  
VX…P 0.00, 0.20 to 120.0Hz  
(0.00 = preset disabled)  
27 Intl. electronic thermal 27 DBR OL  
O/L for intl. brkg. R  
0 = Inactive  
1 = Active for intl. R, invrs. 7.5kW  
2 = Inactive  
1 [0]  
28 Slip compensation  
28 SLIP COMP  
-9.9Hz to +5.0Hz  
Hz  
0.1  
2
0.0  
0
29 Torque vector control  
29 TRQ VECTOR 0 = Inactive 1 = Active  
2 to 14 (even nos. only)  
30 Number of motor poles 30 MTR POLES  
4
Functions marked by heavy outlines can be set whilst the inverter is running. DEF = factory-set defaults. Resol = resolution.  
Default values are for all inverters. Where VX…P defaults differ, they are shown in square brackets […].  
* LCD display shows 0V  
† Approx. rated current for inverter-rated motors  
PRICE  
INFORMATION  
AND ORDERING  
Jaguar VX  
Parameter list/function code table (continued)  
Group No.  
Name  
LCD Display  
Setting range  
Unit Resol. Def.  
31 Function Block 32 to 41  
0 = Functions 32 to 41 hidden  
1 = Functions 32 to 41 displayed  
s
0
31 32—41 •  
31  
Prog. I/P  
terminals  
32 Select the functions of  
terminals X1 to X5  
0000 to 2222  
0000  
32 X1-X5 FUNC  
3X ACC TIME X  
Acc./Dec.  
times  
33 Accel time 2  
34 Decel time 2  
35 Accel time 3  
36 Decel time 3  
37 Accel time 4  
38 Decel time 4  
0.00 = Ramp inhibited, coasting  
0.01 to 3600s  
0.01 10.00  
10.00  
15.00  
15.00  
3.00  
3.00  
2nd  
motor  
39 Base freq., motor 2  
40 Max. O/P V, motor 2  
VX, 50-400Hz VX…P, 50-120Hz  
Hz  
V
1
1
50  
39 BASE Hz -2  
40 RATED V -2  
0 = Output dependent on supply V*  
320 to 480 = output V  
400  
41 Torque boost, motor 2  
0.1 to 20.0 fixed boost  
0.1  
2.0  
0
41 TRQ BOOST 2  
42 Function Block 43 to 51  
0 = Functions 43 to 51 hidden  
1 = Functions 43 to 51 displayed  
42 43—51 •  
42  
43 FMP terminal, pulse  
rate multiplier  
x6 to x100  
1
x24  
Digital  
O/P  
43 FMP PULSES  
44 Voltage O/P adjustmt.  
50% to 120%  
65% to 200%  
%
%
1
1
100%  
100%  
44 FMP V-ADJ  
45 FMA V-ADJ  
45 FMA terminal, voltage  
adjustment  
Analog  
O/P  
46 FMA terminal function  
0 = O/P freq.  
2 = O/P torque  
1 = O/P current  
3 = %FLT  
Hz  
0
46 FMA FUNC  
47 Y1-Y5 FUNC  
48 FAR HYSTR  
47 Select the functions of  
terminals Y1E to Y5E  
00000 to FFFFF  
01234  
2.5  
O/P term.  
functions  
48 FAR function (‘At  
Speed’ window)  
0.0 to 10.0Hz  
0.1  
49 FDT function (level)  
50 FDT function (hyster.)  
51 O/L alarm (level)  
VX, 0-400Hz VX…P, 0-120Hz  
Hz  
Hz  
A
1
50  
1.0  
49 FDT LEVEL  
50 FDT HYSTR  
51 OL WARNING  
0.0 to 30.0Hz  
0.1  
Approx. 20 to 105% inverter rated  
current  
0.01  
52 Function Block 53 to 59  
0 = Functions 53 to 59 hidden  
1 = Functions 53 to 59 displayed  
0
52 53—59 •  
52  
53 Skip frequency 1  
54 Skip frequency 2  
55 Skip frequency 3  
56 Skip hysteresis  
57 Starting frequency  
58 Holding time  
VX, 0-400Hz VX…P, 0-120Hz  
VX, 0-400Hz VX…P, 0-120Hz  
VX, 0-400Hz VX…P, 0-120Hz  
0 to 30Hz  
Hz  
Hz  
Hz  
Hz  
Hz  
s
1
1
0
0
53 JUMP Hz 1  
54 JUMP Hz 2  
55 JUMP Hz 3  
56 JUMP HYSTR  
57 START Hz  
58 HOLDING t  
59 FILTER  
Frequency  
control  
1
0
1
3
0.2Hz to 60.0Hz  
0.1  
0.1  
0.5  
0.0  
0.0 to 10.0s  
59 Frequency I/P  
reference filter  
0.01 to 5.00s  
s
0.01 0.05  
Functions marked by heavy outlines can be set whilst the inverter is running. DEF = factory-set defaults. Resol = resolution.  
Default values are for all inverters. Where VX…P defaults differ, they are shown in square brackets […].  
* LCD display shows 0V  
† Approx. rated current for inverter-rated motors  
PRICE  
INFORMATION  
AND ORDERING  
Jaguar VX  
Parameter list/function code table (continued)  
Group No.  
Name  
LCD Display  
Setting range  
Unit Resol. Def.  
60 Function Block 61 to 79  
0 = Functions 61 to 79 hidden  
1 = Functions 61 to 79 displayed  
s
0
0
0
60 61—79 •  
60  
LED &  
LCD  
displays  
61 LEDs, function for  
normal display  
0 to 8  
61 LED MNTR 1  
62 LED MNTR 2  
63 SPEED COEF  
64 LCD MNTR  
65 PATTERN  
62 LEDs display at STOP  
0 = Set point (flashing)  
1 = Actual output value only  
63 Coefficient for machine  
speed and line speed  
0.01 to 200.00 x Hz output  
0.01 0.01  
64 LCD display function  
0 to 3: Drive status, standard screen  
or bar graphs  
0
0
Pattern  
operations  
65 Pattern operation,  
mode select  
0 to 3: Inactive or cyclic  
66 Pattern stages 1 to 7  
to  
72  
Operation time 0.00 to 6000s  
FWD/REV codes F1 to F4  
ACC/DEC codes R1 to R4  
0.01 0.00  
F1  
6X STAGE X  
73 ACC/DEC mode  
0 to 2: linear, S-curve, non-linear  
0
73 ACC PTN  
74 Series brake motor  
driving  
Not available  
74 SERIES BRK  
Special  
Functions  
1
75 Energy saving  
0 = Inactive 1 = Active  
0 = Inactive 1 = Active  
0 = Inactive 1 = Active  
0 [1]  
75 ENERGY SAV  
76 REV LOCK  
77 DATA INIT  
76 REV phase sequ. lock  
0
0
77 Data initialising (data  
reset)  
0 = GERMAN, 1 = ENGLISH  
0 to 3  
78 Language of displays  
1
5
78 LANGUAGE  
79 BRIGHTNESS  
2 = SPANISH, 3 = ITALIAN  
79 LCD display  
brightness  
0 (bright) to 10 (dark)  
80 Function Block 81 to 94  
0 = Functions 81 to 94 hidden  
1 = Functions 81 to 94 displayed  
0
80 81—94 •  
80  
Special  
Functions  
2
81 PWM carrier frequency  
(motor sound)  
0 (low) to 10 (high) carrier  
frequency  
10  
81 MTR SOUND  
82 Auto-restart, start delay  
0.0 to 5.0s  
s
0.1  
1
0.1  
10  
82 RESTART 1  
83 FALL RATE  
83 Auto-restart, freq. fall  
rate  
0.00 to 100.00  
Hz/s  
84 Auto-reset, number of  
restarts  
0 to 7  
0
84 AUTO RESET  
85 Auto-reset, interval  
86 Motor 1, frame size  
2 to 20s  
s
5
1
85 RESET INT  
0 = 1 higher 1 = nominal  
2 = 1 lower 3 = 2 lower  
86 MOTOR CAP  
Motor  
characteristics  
87 Motor 1, rated current  
88 Motor 1, no-load current  
89 Motor 2, rated current  
90 Motor 1, tuning  
0.00 to 2000A  
A
A
0.1  
0.1  
0
87 MOTOR 1-Ir  
88 MOTOR 1-Io  
89 MOTOR 2-Ir  
90 TUNING  
0.00 to 2000A  
0.00 to 2000A  
A
0.1  
0 = Inactive 1 = Active  
0.00 to 50.00%  
0.00 to 50.00%  
%
%
91 Motor 1, %R1 value  
92 Motor 1, %X value  
0.01  
0.01  
91 %R1 SET  
92 %X SET  
Special  
Functions  
3
93  
93 DD FUNC 1  
94 DD FUNC 2  
95 DATA PRTC  
Manufacturers use  
only  
94  
95  
Data security  
0 = Unlocked  
1 = Data secure  
0
Jaguar VX  
Dimensions (mm) 0.4 to 280kW  
Jaguar VX40  
Jaguar VX550, VX750, and VX750P, VX1100P  
130  
195  
110  
96  
220  
196  
37  
6
97  
7
12  
10  
KEYPAD OPERATION  
KEYPAD OPERATION  
Hz  
r/min  
Hz  
r/min  
%
A
m/min  
%
A
m/min  
V
V
PRG  
RUN  
PRG  
RUN  
260  
238  
FUNC  
DATA  
260  
246  
RESET  
STOP  
FUNC  
DATA  
RESET  
STOP  
10  
162  
10  
6
87  
7
Jaguar VX75 to VX400  
Jaguar VX1100 to VX2200 and VX1500P to VX2200P  
145  
150  
136  
195  
52  
250  
7
96  
6
226  
12  
10  
KEYPAD OPERATION  
Hz  
r/min  
%
A
m/min  
V
KEYPAD OPERATION  
Hz  
r/min  
%
A
m/min  
V
PRG  
RUN  
260  
246  
FUNC  
DATA  
RESET  
STOP  
PRG  
RUN  
400  
378  
FUNC  
DATA  
RESET  
STOP  
6
102  
7
10  
162  
10  
*N.B. JAGUAR VX inverters are designed  
for use within shielded steel enclosures  
78  
68  
KEYPAD OPERATION  
Hz  
r/min  
%
A
m/min  
V
125  
REMOTE MOUNTING  
STOP  
KEYPAD WITH OPTIONAL  
2M CONNECTOR CABLE  
PRICE  
115  
PRG  
RUN  
INFORMATION  
FUNC  
DATA  
RESET  
STOP  
AND ORDERING  
Keypad panel  
mounting dimensions.  
Common to all modules.  
Jaguar VX30K to VX220K, VX30KP to VX280KP  
W
W1  
D
V X  
W
W 1  
H
H 1  
H 2  
D
D 1  
d
D1  
-
30K D  
340 240 550 530 500 290 185 10  
340 240 550 530 500 290 185 10  
375 275 550 530 500 290 185 10  
375 275 675 655 625 275 170 10  
530 430 675 645 610 290 185 15  
530 430 740 710 675 300 180 15  
2 holes  
dmm diam.  
-
-
37KP D  
30KP D  
CHARGE  
-
-
45KP D  
-
55KP D  
-
75KP D  
-
90KP D  
37K D  
KEYPAD OPERATION  
Hz  
r/min  
%
A
m/min  
V
-
45K D  
Side vents on  
inverters from  
VX30K to VX75K  
and VX30KP to  
VX90KP only  
H
PRG  
RUN  
-
55K D  
FUNC  
DATA  
RESET  
STOP  
H1  
-
75K D  
H2  
-
-
110KP D 530 430 740 710 675 330 205 15  
90K D  
-
-
132KP D 530 430 740 710 675 330 205 15  
110K D  
-
-
160KP D 530 430 1000 970 935 435 295 15  
132K D  
-
-
200KP D 530 430 1000 970 935 435 295 15  
160K D  
-
-
220KP D 680 580 1000 980 N/A 435 320 N/A  
200K D  
-
-
280KP D 680 580 1000 980 N/A 435 320 N/A  
220K D  
d
Jaguar VX  
Optional accessories  
Accessory  
Filters  
Function  
A specially designed range of easily fitted low profile ‘footprint’ filters up to  
22kW and stand alone filters up to 280kW are available to provide maximum  
RF reduction. See page 363 for details.  
Function Copy Unit  
Saves and loads stored set-ups for up to 12 complete function sets. ‘Copy  
Edit’, ‘verify’ and ‘write-protected’ modes available. Operates from an 85V to  
265V AC supply. Target or donor drives do not need to be powered up to  
transfer data.  
Encoder Feedback Module  
Enables Jaguar VX inverters to be operated in closed-loop control mode.  
Speed control range 180 to 3600 rpm. Speed variation 0.2% at 3600 rpm.  
Encoder output, 20 to 2000 pulses per revolution.  
Relay Output Module  
PID Control Mode Unit  
Converts programmable outputs Y1E . . . Y5E to relay outputs.  
Contact rating 0.3A at 250V AC, cosØ = 0.3.  
Digitally adjustable P, I and D terms through the medium of a  
supplementary function menu.  
Reference input 0V to 10V DC  
Feedback input 0V to 10V DC or 4-20mA DC.  
Synchronisation Module  
Serial Communication Module  
FieldBus Modules  
Provides a multi-synch tasking capability via rotary encoders for  
Master/Slave and ‘Follower’ applications.  
RS422 or RS485, multi-drop up to 31 Jaguar VX inverters of all sizes. Opto-  
isolated.  
Dedicated FieldBus units which allow the connection of multiple  
Jaguar VX inverters to a site standard FieldBus link.  
FieldBus systems available:  
Modbus Plus  
Interbus S  
Profibus DP  
DeviceNet  
Regenerative Brake Units  
Pod Extension Cable  
Provides additional braking for high inertia loads for inverters 11kW to  
280kW. (Units below 11kW have regenerative braking capability built in as  
standard).  
Allows the Jaguar VX keypad to be removed and mounted separately.  
PRICE  
INFORMATION  
AND ORDERING  

相关型号:

VX111101B0J0G

Barrier Strip Terminal Block
AMPHENOL

VX12116100J0G

Barrier Strip Terminal Block
AMPHENOL

VX12KXXB-6AA79-1XX-XDF1

Rocker Switch, Quick Connect Terminal, Rocker Actuator, Panel Mount,
Carling Techn

VX1301-1

ABISOLIERWERKZEUG MIT EINSATZ 3 STUFEN
ETC

VX131200B0J0G

Barrier Strip Terminal Block
AMPHENOL

VX14106100J0G

暂无描述
AMPHENOL

VX141101B0J0G

暂无描述
AMPHENOL

VX14123000J0G

Barrier Strip Terminal Block
AMPHENOL

VX14123100J0G

Barrier Strip Terminal Block
AMPHENOL

VX1412C100J0G

Barrier Strip Terminal Block
AMPHENOL

VX150

FREQUENZUMRICHTER 3 PHASEN VX 1.5KW
ETC

VX1500

FREQUENZUMRICHTER 3 PHASEN VX 15KW
ETC