DG221UGB [ETC]
Safety Switches;型号: | DG221UGB |
厂家: | ETC |
描述: | Safety Switches |
文件: | 总4页 (文件大小:282K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Safety Switches
Product Description
SAFETY SWITCH
A safety switch is used to open or close an electrical
circuit. Non-fusible safety switches provide a means
to manually connect or disconnect the equipment
from the power source. Fusible safety switches pro-
vide a means to manually open and close a circuit and
overcurrent protection by using customer-installed
fuses. Safety switches are also commonly referred
to as a disconnect switch or simply a disconnect.
DP221NGB Plug Fuse Safety Switch,
30 Amperes, 120/240 Volts
DOUBLE THROW SAFETY SWITCH
A double throw safety switch is sometimes referred to
as a transfer switch. It performs the same function as a
safety switch by opening or closing a circuit; however,
its primary use is to transfer service from a normal
power source to an alternate source (i.e., a residential
generator) or to switch from one load circuit to another.
Features, Functions and Benefits
DG322URB General-Duty, Non-Fusible Safety Switch,
60 Amperes, 240 Volts
✓ 120/240, 240 or 600 volts.
✓ Easy to install.
✓ Ample wiring space.
✓ Padlockable.
✓ UL listed.
DT224URK-NPS General-Duty, Non-Fusible Double
Throw Emergency Power Safety Switch, 200
Amperes, 120/240 Volts
DH362UGK Heavy-Duty, Non-Fusible Safety Switch,
60 Amperes, 600 Volts
EATON CORPORATION Cutler-Hammer
6-7
Safety Switches
DG321NRB General-Duty, Cartridge Fuse Safety Switch,
30 Amperes, 120/240 Volts
DP221NGB
DT223URH-N General-Duty, Non-Fusible
Double Throw Emergency Power Safety Switch,
100 Amperes, 120/240 Volts
DG324NGK
DT224URK-NPS
DH362NGK Heavy-Duty, Fusible Safety Switch,
60 Amperes, 600 Volts
DT363URK Heavy-Duty, Non-Fusible Double Throw
Emergency Power Safety Switch, 100 Amperes, 600 Volts
6-8
EATON CORPORATION Cutler-Hammer
Applications
FIGURE 6-3. RESIDENTIAL GENERATOR APPLICATION WITH
MANUALLY OPERATED DOUBLE THROW SAFETY SWITCH
FIGURE 6-2. HOUSEHOLD WORKBENCH APPLICATION
FIGURE 6-4. RESIDENTIAL GENERATOR APPLICATION WITH
AUTOMATIC TRANSFER SWITCH AND SERVICE ENTRANCE RATED
SAFETY SWITCH
Catalog Numbering System
TABLE 6-14. SAFETY SWITCH CATALOG NUMBERING SYSTEM
DG 2 2 1 N R B
Switch Type
Series
Poles/Blades
NEMA Enclosure Ratings
DP = General-Duty/Plug Fuse
DG = General-Duty/Cartridge Fuse
DH = Heavy-Duty
K = Design (All General-Duty Switches
Above 200 Amperes and All Heavy-Duty
1 = 1-Pole
2 = 2-Pole
3 = 3-Pole
4 = 4-Pole
G = NEMA 1
Amperes
Switches Incorporate K-Series Switch
Design Features Listed Below)
R = NEMA 3R
DT = Double Throw
1 = 30
2 = 60
D = NEMA 12
B = Design General-Duty (30 – 100 Amperes)
W = NEMA 4X
H = General-Duty Double Throw Switch
3 = 100
4 = 200
5 = 400
6 = 600
7 = 800
8 = 1200
Corrosion Resistant
(Compact Design 30 – 100 Amperes)
(304 Grade Stainless Steel)
Voltage
1 = 120 Vac
2 = 240 Vac
6 = 600 Vac
Fusible/Non-Fusible
or Neutral
F = Fusible without Neutral
U = Non-Fusible
N = Fusible with Neutral
EATON CORPORATION Cutler-Hammer
6-9
120/240 VAC GENERAL-DUTY, FUSIBLE, SINGLE THROW
TABLE 6-16. 120/240 VAC GENERAL-DUTY, FUSIBLE, SINGLE THROW
Maximum Horsepower Ratings ᕃ
NEMA 1
Enclosure
Indoor
NEMA 3R
Enclosure
Rainproof
1-Phase ac
3-Phase ac
dc
Ampere Fuse Type
Rating Provision
120 240
Volt Volt
240
Volt
250 Catalog
Volt Number
UPC
Code
Catalog
Number
UPC
Code
3-Pole 3-Wire (Three Blades, Three Fuses) — 240 Vac
30
60
100
200
400
600
—
—
—
—
H
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
ᕄ
—
ᕄ
—
—
ᕄ
—
ᕄ
—
—
—
50 – 125
75 – 200
ᕄ
—
—
ᕄ
—
—
ᕄ
ᕄ
DG325FGK ᕅ
DG326FGK ᕅ
782113589510
782113589572
DG325FRK ᕅ
DG326FRK ᕅ
782113589527
782113589589
H
4-Wire (Three Blades, Three Fuses, S/N) — 120/240 Vac
30
60
100
200
400
600
H
H
H
H
H
H
—
—
—
—
—
—
1-1/2 – 3
3 – 10
3 – 7-1/2
—
—
—
—
—
—
DG321NGB
DG322NGB
DG323NGB
DG324NGK
DG325NGK
DG326NGK
782113120201
782113144283
782113144344
782113213538
782113639208
782113639222
DG321NRB
DG322NRB
DG323NRB
DG324NRK
DG325NRK
DG326NRK
782113120348
782113144290
782113144351
782113213545
782113639215
782113639239
7-1/2 – 15
7-1/2 – 15 15 – 30
15
—
—
25 – 60
50 – 125
75 – 200
ᕃ Maximum hp ratings apply only when dual element time delay fuses are used.
ᕄ Use 4-wire catalog numbers below.
ᕅ Solid neutral bars are not included. Order separately from Table 6-27 on Page 6-18.
120/240 VAC GENERAL-DUTY, NON-FUSIBLE, SINGLE THROW
TABLE 6-17. 120/240 VAC GENERAL-DUTY, NON-FUSIBLE, SINGLE THROW
Maximum Horsepower Ratings
NEMA 1
Enclosure
Indoor
NEMA 3R
Enclosure
Rainproof
1-Phase ac
3-Phase ac
dc
Ampere
Rating
120
Volt
240
Volt
240
Volt
250
Volt
Catalog
Number
UPC
Code
Catalog
Number
UPC
Code
Non-Fusible — 2-Pole 2-Wire (Two Blades) — 240 Vac
30
60
100
200
2
3
10
15
—
—
—
—
—
—
—
—
—
DG221UGB ᕆ
DG222UGB ᕆ
DG223UGB ᕆ
ᕆᕇ
782113120102
782114731130
782114731147
—
DG221URB ᕆ
DG222URB ᕆ
DG223URB ᕆ
ᕆᕇ
782113120232
782113144238
782114731154
—
3
—
—
3-Pole 3-Wire (Three Blades) — 240 Vac
30
60
100
200
400
600
2
3
10
15
15
—
—
7-1/2
—
—
—
—
—
—
DG321UGB ᕆ
DG322UGB ᕆ
DG323UGB ᕆ
DG324UGK ᕆ
DG325UGK ᕈ
DG326UGK ᕈ
782113120140
782113144306
782113144368
782113213552
782113589534
782113589596
DG321URB ᕆ
DG322URB ᕆ
DG323URB ᕆ
DG324URK ᕆ
DG325URK ᕈ
DG326URK ᕈ
782113120287
782113144313
782113144375
782113213576
782113589541
782113589602
3
15
—
—
—
—
30
60
125
200
ᕆ WARNING! Switch is not approved for service entrance unless a neutral kit is installed.
ᕇ Use 3-wire catalog numbers below.
ᕈ Drilled to accept field installed neutral kits.
Note: All general-duty safety switches are individually packaged.
Note: Accessories are limited in scope on general-duty safety switches. In addition, clear line shields are available as an accessory
on 200 – 600 ampere general-duty switches.
Catalog Numbers: 200 A = 70-7759-11, 400 A = 70-8063-8, 600 A = 70-8064-8.
EATON CORPORATION Cutler-Hammer
6-11
相关型号:
©2020 ICPDF网 联系我们和版权申明