BB-485OPDRI-PH [ETC]
REPEATER RS422/485 ISOLATED;型号: | BB-485OPDRI-PH |
厂家: | ETC |
描述: | REPEATER RS422/485 ISOLATED 中继器 |
文件: | 总2页 (文件大小:486K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Heavy Industrial RS-422/485
Isolated Repeater
M
www.advantech-bb.com
PRODUCT FEATURES
•
•
•
•
•
•
•
IEEE-61850-3, IEEE-1613
NEMA TS2
-40 to 85°C Operating Temperature
Rugged IP30 Metal Panel Mount Case
50G Shock, 4G Vibration
2kV Triple Isolation
10 to 48 VDC Input Power
M
re
through some of the most exacting compliance tests in the industry. Meeting
the requirements of IEC 61850-3 and IEEE 1613, it is suitable for installation
in electrical substations. These specifications are more stringent than the
NEMA TS1/TS2 requirements for transportation applications. Powerful
isolation on both data ports protects your equipment and data from damaging
ground loops and surges. Additional isolation on the power supply circuits
adds a third degree of protection.
ORDERING INFORMATION
MODEL NUMBER
DESCRIPTION
485OPDRI-PH
Heavy Industrial RS-232 to RS-422/485 Isolated Repeater
ACCESSORIES
MDR-40-24 - DIN Rail Mount Power Supply 24VDC, 1.7 A output power
DRAD35 - DIN Rail Mounting Kit, 35mm
TBKT1 - Replacement Terminal Block, 2
Packaged in a rugged IP30 metal case, it extends full or half-duplex RS-
422/485 signals an additional 4000 feet and allows you to add another 32
nodes to your network. Bit-wise enabled circuitry automatically detects the
data rate without setting a DIP switch.
MECHANICAL
All product specifications are subject to change without notice.
485OPDRI-PH_2917ds
orders@advantech-bb.com
support@advantech-bb.com
Corporate Headquarters: 707 Dayton Road, PO Box 1040 Ottawa, IL 61350 USA 815-433-5100 Fax 433-5104
European Office: Westlink Commercial Park, Oranmore Co. Galway Ireland +353 91 792444 Fax +353 91 792445
Heavy Industrial RS-422/485
Isolated Repeater
Model 485OPDRI-PH
SPECIFICATIONS
SERIAL TECHNOLOGY
RS-422
RS-485 4-Wire
RS-485 2-Wire
RS-422/485 CON.
Data Rate
INDICATORS
Power
TD / RD (Each Port)
MECHANICAL
TDA(-), TDB(+), RDA(-), RDB(+)
TDA(-), TDB(+), RDA(-), RDB(+)
Data A(-), Data B(+)
5 Position, Removable Terminal Block
1.2 to 115.2 Kbps
2 KV RMS, 1 minute
600 W Peak Power Dissipation
Clamping time < 1 pico-second
Red LED
Green LED
13.24 x 9.29 x 3.30 cm
5.2 x 3.7 x 1.3 in
IP30 Metal, Panel Mount
0.46 lbs (208.65 grams)
122832 Hours
Dimensions
Enclosure
Weight
MTBF
Isolation
Surge Protection
Industrial Bus
Bias
Termination
POWER
Source
Power Connector
Input Voltage
Power Consumption
TERMINAL BLOCKS
Wire Size Accepted
Pitch
Modbus ASCII / RTU
Built-in, switchable 1.2KΩ XMT/RCV
Built-in, switchable 120Ω
MTBF Calc. Method
ENVIRONMENTAL
Operating Temperature
Storage Temperature
Operating Humidity
REGULATORY
Parts Count Reliability Prediction
-40 to 85°C (-40 to 176°F)
-40 to 85°C (-40 to 176°F)
0 to 95% Non-condensing
External
2-Position Removable Terminal Block
10 to 48 VDC (56 VDC Maximum)
0.5 W typical (2.3 W with termination)
FCC, CE, IEC 61850-3, IEEE 1613, UL C1 D2,
File: E245458, NEMA TS2
Approvals
28 to 12 AWG, Copper wire only
5.08 mm
Insulation Resistance
Maximum Torque
≥500 MΩ @ 500 VDC
5 Kg / cm
Temperature Rating of field installed conductors 105°C minimum
IEC 61850-3 ELECTRO MAGNETIC INTERFERENCE SPECIFICATIONS
Test
Description
Test Level
Level
Enclosure Contact
Enclosure Air
Enclosure Ports
8 kV
4
4
3
-
4
4
3
3
3
3
3
4
4
61000-4-2
61000-4-3
61000-4-4
ESD
15 kV
Radiated RFI
Burst (Fast Transient)
10 V/m
4 kV @ 2.5 Khz
4 kV
Signal Ports
DC Power Ports
Signal Ports
2 kV line to earth, 1 kV line to line
2 kV line to earth, 1 kV line to line
10 V RMS
61000-4-5
61000-4-6
61000-4-12
Surge
DC Power Ports
Signal Ports
Induced (Conductive) RFI
Damped Oscillatory
DC Power Ports
Signal Ports
10 V RMS
2.5 kV common, 1 kV diff mode @ 1MHz
2.5 kV common, 1 kV diff mode @ 1MHz
30 V Continuous, 300 V for 1 s
30 V Continuous, 300 V for 1 s
DC Power Ports
Signal Ports
61000-4-16
61000-4-17
Mains Frequency Voltage
Ripple on DC Power Supply
DC Power Ports
DC Power Ports
10%
3
IEEE 1613 C37.90 ELECTROMAGNETIC INTERFERENCE SPECIFICATIONS
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
8 kV
C37.90.3
C37.90.2
C37.90.1
ESD
-
-
-
15 kV
Radiated RFI
Fast Transient
10 v/m
4 kV @ 2.5 kHz
4 kV
ENVIRONMENTAL SPECIFICATIONS
60068-2-1
60068-2-2
60068-2-30
IEC 600068-2-6
IEC 600068-2-27
IEC 60068-2-32
Cold Temperature
Dry Heat
Humidity (damp heat cycle)
Vibration
Shock
Drop
Test Ad
Test Bd
Test Dd
Test Fc
Test Ea
-
(-)40 C, 16 Hours
(+)85 C, 16 Hours
90% (non-condensing) (+)55C, 6 Cycles
4g
-
-
-
Class 2
Class 2
-
50g
6 faces, 1 corner, 3 edges, total 10 drops at 1 m
orders@advantech-bb.com
support@advantech-bb.com
Corporate Headquarters: 707 Dayton Road, PO Box 1040 Ottawa, IL 61350 USA 815-433-5100 Fax 433-5104