4002ALMHL-AXXX-4 [ETC]
TRIP AMPLIFIER 230V ; TRIP放大器230V型号: | 4002ALMHL-AXXX-4 |
厂家: | ETC |
描述: | TRIP AMPLIFIER 230V
|
文件: | 总2页 (文件大小:51K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Dual Trip Amplifiers
4002ALM
The 4 0 0 2 ALM trip-amplifier can accept a wide range of
input types. The unit can have up to two relay outputs and
can also produce an isolated 4 -2 0 mA retransmission output
■
■
■
■
■
Wide range of configurable inputs
Configurable trip action with fail-safe modes
Optional isolated re-transmission
Optional isolated transmitter supply
Optional LED display or 0-10V signal output of input and
setpoints values
Options and ordering codes
4002ALM HL – A A XX – 4 AB
Input type
4-20mA
Options
HL
HL
A
B
C
D
E
F
G
H
P
Q
R
S
T
U
W
Y
Z
1
LED
display
A
0-20mA
Tx supply
B
0-30mA 2 sec delay
0-1mA
HL
LED and
Tx supply
AB
HL
0-5Vdc
HL
Supply type
230/ 115Vac
1-5Vdc
HL
4
6
0-10Vdc
HL
24Vdc
18-26Vdc
HL
Type K 0-150˚C
Type K 0-200˚C
Type K 0-250˚C
Type K 0-500˚C
Type K 0-600˚C
Type K 0-1200˚C
Type J 0-250˚C
Pt100 3 wire ±100˚C
Pt100 3 wire ±50˚C
Pt100 3 wire ±30˚C
Pt100 3 wire 0-50˚C
Pt100 3 wire 0-100˚C
Pt100 3 wire 0-150˚C
Pt100 3 wire 0-200˚C
Pt100 3 wire 0-250˚C
Pt100 3 wire 0-400˚C
TC
TC
TC
Output options
4-20mA re-transmission
TC
A
X
No re-transmission
TC
TC
TC
RTD
RTD
RTD
RTD
RTD
RTD
RTD
RTD
RTD
PRICE
2
INFORMATION
AND ORDERING
3
4
5
Other ranges and thermocouple
types are available as detailed in the
product description, please contact
our sales department.
6
7
4002ALM
Dimensions and connections
10. Input -ve
11. Input +ve
12.
1. Output -ve
2. Output +ve
24. Power input -ve
T/C -ve
T/C +ve
T/C shield RTD 3rd wire
RTD -ve
RTD +ve
15. Relay 1 N/C
16. Relay 1 N/O
17. Relay 1 common
18. Relay 2 N/C
19. Relay 2 N/O
20. Relay 2 common
25. Power input +ve
13. Trans supply -ve
14. Trans supply +ve
Description
The 4 0 0 2 ALM trip-amplifier can accept a wide range of inputs
including 4 -2 0 mA, ther mocouple, RTD and voltage types. The unit
can have up to two relay outputs and each can operate as a high or
low trip. The unit can also produce an isolated high level output.
4 0 0 2 ALM - HL for DC Cur rent and Voltage
0-20mA, 4-20mA, 0-10mA into 15Ω/ 30Ω
0-1V, 0-10V, 1-5V, into 100kΩ/ 1MΩ
Min and Max full scale ranges:
DC current
DC voltage
0 to 50µA
0 to 100mV
0 to 10A
0 to 300V
The relay outputs are single pole change-over relays with mains voltage
rating. Each trip can be configured so that the alarm condition can be
above or below the setpoint. The relays can be energised or de-energised
in the alarm condition, satisfying fail-safe and non-fail-safe applications. In
addition the alarm LEDs can be selected to light when the relay is either
on or off.
Note: For input voltages greater than 30Vac or 60Vdc a divider unit must
be specified.
4 0 0 2 ALM - TC for Ther mocouples
Types E, J, K, N, R, S and T non-linearised
Ranges 0-250, 0-500, 0-1200˚C (Others available)
Auto cold junction compensation. Open cct t/ c can drive either
upscale or downscale
The input stage is isolated as standard with the inputs user-reconfigurable
to cover several different ranges if specified at point of order. In addition
there is an optional isolated transmitter supply of 24Vdc, suitable for
exciting most standard transmitters.
The following applications are also possible:
4 0 0 2 ALM - RTD for Resistance Ther mometers
2 or 3 wire Pt100 or other, linearised output
Ranges 0-250, 0-500, -100-100˚C (others available)
One output relay is energised when the input reaches the high setpoint
and is latched on until the lower setpoint is reached. The reverse operation
is also possible. This is ideal for applications such as pumping out. All the
above options are user-configurable but can be specified at point of order.
Default configuration is set to Hi/ Hi alarms with LED on when relay
energised. Please specify at time of ordering if other combinations are
required.
Outputs
Mains Rated Relays
03A resistive at 240Vac
SPECIFICATION
PRODUCT
OR
DC Cur rent and Voltage
0-20mA, 4-20mA, 0-10mA into 750Ω
Inputs
TO ORDER
The input types and ranges following are our standard ones only. Contact
sales for others.
0-1V, 0-10V, 1-5V into a minimum 2kΩ
Specifications
P arameter
Min
Typ
24Vdc
50mA
1MΩ
15Ω
Max
Comments
Supply voltage
Options: 24Vdc or 24Vac, 110Vac, 240Vac
24V supply (max if both relays energised)
Dependent on range (Typ=10V)
Dependent on range (Typ=20mA)
At 20mA input on 0(4) to 20mA range
Supply cur rent
20mA
100kΩ
0.02Ω
160mA
10MΩ
Input impedance (volt)
Input impedance (mA)
Volt drop (mA input)
Trip point accuracy
Temperature coefficient
Trip point drift
5kΩ
0.3
0.35
±0.25%
±100ppm/ ˚C
±100ppm/ ˚C
Relay response time
Operating ambient
Relative humidity
Isolation voltage
Surge voltage
10ms
Signal response 300ms for T/ C, 30ms others
Transient of 10kV/ µS
0˚C
0%
55˚C
90%
1kV
2.5kV for 50µS
Notes
Setpoints are adjusted by 20 turn potentiometers on the front panel.
Setpoints can be checked by measuring 0-10V (0-100%) voltage on the front panel terminals.
H/ H, H/ L, L/ H, LL, fail-safe, non-fail-safe and LED options are user selectable using internal links.
Hysteresis is set at 1.0% but other values are possible, please specify if required.
The process input level is available as 0-1V (0-100%) on front panel or on 3 digit LED display.
Figures based on HL version, 24Vdc supply, 20˚C ambient.
相关型号:
4002UL
Pushbutton Switch, SPST, On-(off), Momentary, Solder Terminal, Panel Mount-threaded, ROHS COMPLIANT