1140-F211-P1M1-7A [ETAL]
Motors, transformers, solenoids, hand-held machines and appliances;型号: | 1140-F211-P1M1-7A |
厂家: | ETAL Group |
描述: | Motors, transformers, solenoids, hand-held machines and appliances |
文件: | 总2页 (文件大小:292K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Thermal Overcurrent Circuit Breaker 1140-...
Description
Miniaturised single pole thermal circuit breaker with push-to-reset
tease-free, trip-free, snap action mechanism (R-type TO CBE to EN
60934). Available in versions for panel mounting, snap-in or threadneck,
or as an integral type. For lower current ratings see types 104, 105, 106.
Approved to CBE standard EN 60934 (IEC 60934).
Typical applications
Motors, transformers, solenoids, hand-held machines and appliances.
1
Ordering information
1140-E...
1140-F...
1140-G.1.
Type No.
1140
single pole thermal circuit breaker
Mounting
Technical data
E2 integral mounting
F1 snap-in panel mounting
G1 threadneck panel mounting 3/8-27UNS with hex nut and
knurled nut (hardware bulk shipped with 5 pcs plus)
Number of poles
For further details please see chapter: Technical Information
Voltage rating
AC 240 V; DC 48 V
(UL: AC 250 V; DC 50 V)
1 1-pole protected
Actuator style
Current ratings
3.5...16 A
Typical life
AC + DC
1
black push button
3.5...8 A
9...16 A
200 operations at 2 x IN, inductive
100 operations at 2 x IN, inductive
Terminal design
P1 blade terminals A6.3-0.8 (QC .250)
Characteristic curve
Ambient temperature
-20...+60 °C (-4...+140 °F) T 60
M1
medium delaye
Current ratings
3.5...16 A
Insulation co-ordination
(IEC 60664 and 60664 A) withstand voltage
2.5 kV
rated impulse
pollution
degree
2
reinforced insulation in operating area
1140 - F1 1 1 - P1 M1 - 10 A = ordering example
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area
AC 3,000 V
Preferred types
Insulation resistance
Interrupting capacity Icn
> 100 MΩ (DC 500 V)
3.5...8 A
9...16 A
8 x IN
120 A
Preferred types
Standard current ratings (A)
Interrupting capacity
(UL 10777)
IN
UN
4
5
6
7
8
9
10 11 12 13 14 15 16
3.5...16 A DC 50 V
3.5...16 A AC 250 V 2,000 A
2,000 A
x
x
x
x
x
x
x
x
x
x
x
x
x
1140-G111-P1M1-
Degree of protection
(IEC 60529/DIN 40 050)
operating area IP40
terminal area IP00
Standard current ratings and typical internal resistance values
Vibration
10 g (57-500 Hz) 0.76 mm (10-57 Hz),
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Current
rating (A)
Internal
Current
Internal
resistance (Ω)
Shock
25 g (11 ms)
to IEC 60068-2-27, test Ea
resistance (Ω) rating (A)
Corrosion
Humidity
Mass
96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
3.5
4
0.06
0.04
10
11
12
13
14
15
16
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
< 0.02
240 hours at 95 % RH
to IEC 60068-2-78, test Cab
5
0.03
approx. 10 g
6
0.02
7
< 0.02
< 0.02
< 0.02
Approvals
8
Authority
Standard
Rated voltage
Current ratings
9
VDE
IEC/EN 60934 AC 240 V
DC 48 V
3.5 A…16 A
3.5 A…16 A
UL
UL 1077
AC 250 V
DC 50 V
3.5 A…16 A
3.5 A…16 A
CSA
C22.2 No 235
AC 250 V
DC 50 V
3.5 A…15 A
3.5 A…16 A
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
1635
www.e-t-a.de
1
Thermal Overcurrent Circuit Breaker 1140-...
Internal connection diagram
Dimensions
Accessory
1
1140-E211-P1M1
Water splash cover/knurled
nut assembly, transparent
ø4.2
.165
ø7
.276
X 201 285 01 ꢀꢁꢂ6ꢃꢄ
19
.748
9
.354
ꢀ
hole for
mounting
screw M2x5
1
Typical time/current characteristics at +23 °C/+73.4 °F
blade terminal
DIN 46244-A6.3-0.8 (QC .250)
1140-F111-P1M1
1ꢃꢃꢃꢃ
ꢃꢓꢃ5 ꢔ 3 ꢕ
ø4.2
.165
ø7
.276
3ꢓ5 ꢔ 16 ꢕ
1ꢃꢃꢃ
1ꢃꢃ
1ꢃ
1
11
.433
9
.354
blade terminal
DIN 46244-A6.3-0.8
(QC .250)
19
.748
25
.984
panel cut-out
d
a
mm
21.9 .862
22 .866
22.1 .870
mm inch
inch
0.8
1.0
1.5
.031
.039
.059
.874
2-3 .079-.118 22.2
a
ꢃꢓ1
1
ꢀ
ꢁ
6
ꢂ 1ꢃ
ꢀꢃ
ꢁꢃ
1140-G111-P1M1
ꢄ ꢅꢆꢇꢈꢉ ꢊꢋꢅꢈꢌ ꢍꢎꢊꢊꢈꢏꢅ
tightening torque max. 0.8 Nm
3
/
-27 UNS-2A
8
ø4.2
.165
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the
circuit breaker current ratings by the derating factor shown below. See also
section Technical information.
-4
-20
+14
-10
+32 +73.4 +104 +122 +140
Ambient temperature °F
°C
0
+23
+40
+50
+60
0.76 0.84 0.92
1
1.08 1.16 1.24
Derating factor
Installation drawings
blade terminal
DIN 46244-A6.3-0.8 (QC .250)
mounting hole
SW 14
.551
1140-F...
ꢀꢁꢂꢃꢄꢅꢆꢇꢈ ꢄꢃꢂꢄ
9
8.9-0.1
.354
19
.748
ꢋ
ꢌ315
ꢋ
ꢌ315
ꢉꢀꢊꢇꢅꢆꢇꢈ ꢄꢃꢂꢄ
ꢀꢁꢂꢃꢄꢅꢆꢇꢈ ꢄꢃꢂꢄ
.350-.004
1140-E...
Accessory
Hex nut 3/8"
nickel-plated brass
Y 300 192 01
Knurled nut 3/8"
plastic (standard)
Y 307 117 02
ꢀ
ꢁ315
ꢋ
ꢌ315
ꢉꢀꢊꢇꢅꢆꢇꢈ ꢄꢃꢂꢄ
ꢀꢁꢂꢃꢄꢅꢆꢇꢈ ꢄꢃꢂꢄ
3ꢁꢂꢃꢄꢅꢆꢇꢈꢃꢄꢉ
ꢄꢊ5
ꢊꢎꢋꢂ
1140-G...
ꢀ15
3
ꢊ5ꢋ1
ꢊ11ꢂ
ꢉꢀꢊꢇꢅꢆꢇꢈ ꢄꢃꢂꢄ
ꢋ
ꢌ315
ꢀ
ꢁ315
ꢈꢌ1ꢍ
ꢊ551
3ꢁꢂꢃꢄꢅꢆꢇꢈꢃꢄꢉ
mm
)
This is a metric design and millimeter dimensions take precedence (
inch
2
www.e-t-a.de
1635
相关型号:
©2020 ICPDF网 联系我们和版权申明