B84143V0180R127 [EPCOS]
3-line sine-wave EMC output filters for converters and power electronics -SineFormer-; 三线正弦波EMC输出滤波器变频器和电力电子-SineFormer-型号: | B84143V0180R127 |
厂家: | EPCOS |
描述: | 3-line sine-wave EMC output filters for converters and power electronics -SineFormer- |
文件: | 总9页 (文件大小:902K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
3-line sine-wave EMC output filters
for converters and power electronics
SineFormer
520 V AC, 11 ... 320 A, 40 °C
Series/type:
B84143V*R127
Date:
November 2007
EPCOS AG 2007. Reproduction, publication and dissemination of this publication and the infor-
mation contained therein without EPCOS’ prior express consent is prohibited.
3-line filters
B84143V*R127
Sine-wave EMC output filters SineFormer
Filters for converters and power electronics
Rated voltage 520 V AC, 50/60 Hz
Rated current 11 to 320 A
Construction
■ 3-line sine-wave EMC output filter
■ Metal case
Features
■ Supersede shielded motor cables
■ Motor noise reduction
■ Reduction of bearing current
■ dv/dt reduction
■ Easy to install
■ Compact design
■ Degree of protection: IP 201)
■ Design complies with EN 60939, UL 1283, CSA 22.2 No.8
■ Optimized for long motor cables (up to 1000 m) and
operation under full load
■ No integrated forced ventilation (maintenance-free)
■ Connection to converter DC-link is not necessary
■ Reducing eddy current losses
Applications
■ Frequency converters for motor drives, e.g.
– elevators
– pumps
– traction and conveyer systems
– HVAC systems (heating, ventilation and air conditioning)
Terminals
■ Line side (to converter): shielded cable up to 180 A;
copper bus bars for the 320-A filter
■ Load side (to motor): Finger-safe terminal blocks up to 180 A;
copper bus bars for the 320-A filter
Marking
■ Marking on component:
Manufacturer’s logo, ordering code, rated voltage,
rated current, rated motor frequency, rated switch frequency,
rated temperature, climatic category, date code
■ Minimum marking on packaging:
Manufacturer’s logo, ordering code, date code, quantity
1) To IEC 60529:2001
Please read Cautions and warnings and
Important notes at the end of this document.
2
07/07
3-line filters
B84143V*R127
Sine-wave EMC output filters SineFormer
Typical circuit diagram
Converter
U1
Motor
U2
V1
V2
W1
W2
SSB2260-B
Technical data and measuring conditions
Rated voltage VR
520 V AC, 50/60 Hz
320-A type: 600 V AC
Rated current IR
Test voltage Vtest
Referred to 40 °C ambient temperature
2100 V DC, 2 s (line/line)
2700 V DC, 2 s (lines/case)
Frequency
Motor
0 ... 100 Hz
Pulse (switch)
4 ... 8 kHz (320-A type: 2.5 ... 3.0 kHz)
Overload capability (thermal)
Max. dv/dt on filter input
Convection distance to other devices
Vibration (sine)
1.5 · IR for 1 min per hour
5 kV/μs
See next page
10 cycles, 1 oct./min, 3 ... 13 Hz: 3 mm, 3 ... 200 Hz: 1 g
Shock (half sine)
15 g, 11 ms, 3 axis, 3 shocks per direction, 18 total
(to IEC 60 068-2-6)
Current (IR) derating depending on altitude From 1000 ... 4000 m: 5%/1000 m
Current (IR) derating depending on
ambient temperature
From 40 ... 60 °C: 10%/5 °C
Temperature
Inside iron choke: approx. 130 °C
Housing: approx. 70 °C
Noise
Approx. 72 dB (A)
Climatic category (IEC 60068-1)
25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Please read Cautions and warnings and
Important notes at the end of this document.
3
07/07
3-line filters
B84143V*R127
Sine-wave EMC output filters SineFormer
Characteristics and ordering codes
VR
AC
IR
Terminal Voltage Losses Rtyp
Approx. Ordering code
weight
Approvals
cross
section
mm2
drop
at
100 Hz
V
A
%
5
W
mΩ
46
32
20
15
8
kg
11
520
4
6
50
70
9
11
B84143V0011R127
×
×
×
×
×
×
−
×
×
×
×
×
×
−
16
33
7
B84143V0016R127
B84143V0033R127
B84143V0066R127
B84143V0095R127
B84143V0180R127
B84143V0320R127
10
25
50
150
8
120
180
250
400
750
24
66
8
47
95
10
10
99
180
320
6
125
195
600
see dim. 10
drawing
4
× = approval granted
Convection space (cabinet fan recommended)
>100 mm
>200 mm
>100 mm
>200 mm
>200 mm
SSB2258-Z
SSB2257-R
Please read Cautions and warnings and
Important notes at the end of this document.
4
07/07
3-line filters
B84143V*R127
Sine-wave EMC output filters SineFormer
Dimensional drawings
B84143V0011R127 ... B84143V0095R127 (11 ... 95 A)
l
Ring bolt
only for
66-A and
95-A filters
PE
12
c
øk
r
d
e
f
Terminal blocks
Q (Cross section of the wire end)
SSB2259-8-E
Dimensions (mm)
Filter
a
b
c
d
e
f
h
g
k
B84143...
V0011R127 120
V0016R127 120
V0033R127 150
V0066R127 210
V0095R127 250
100
100
120
160
200
335
375
470
650
780
280
320
380
530
650
260
300
360
500
620
700
160
190
240
280
360
6.6
6.6
6.6
8.6
11
14
900
16
20
30
43
900
1500
1600
Filter
l
m
r
Terminal blocks
Threaded bolt
PE Nm
2±0.1
2±0.1
Q
B84143...
mm2
Nm
mm2
2.5
4
V0011R127 −
V0016R127 −
V0033R127 −
V0066R127 545
V0095R127 665
−
−
4
0.6 ... 0.8 M5×9.5
1.5 ... 1.8 M5×9.5
−
−
6
−
−
10
25
50
1.5 ... 1.8 M5×12.5 2±0.1
6
122
163
165
200
4 ... 4.5
6 ... 8
M6×16.5 3±0.15
M6×15.5 3±0.15
16
35
Please read Cautions and warnings and
Important notes at the end of this document.
5
07/07
3-line filters
B84143V*R127
Sine-wave EMC output filters SineFormer
B84143V0180R127 (180 A)
Terminal blocks 150 mm2
Tightening torque 12 ... 15 Nm
PE M8 x 30
Cable clamp for cable ø55
Tightening torque 6±0.3 Nm
Wire end ferrule
A70-25 (4x)
(like DIN 46228)
2700+10
15
880
30
800
Shielded cable 70 mm2
65
910
1130
SSB2261-J-E
Please read Cautions and warnings and
Important notes at the end of this document.
6
07/07
3-line filters
B84143V*R127
Sine-wave EMC output filters SineFormer
B84143V0320R127 (320 A)
ø45
ø25
Cable gland MS-SC 36
Ring bolt
DIN 580-M10
(232)
12
Converter
Motor
200
200
PE M12 x 19.5
Tightening torque 15.5±1.5 Nm
2 x 65 = 130
2 x 65 = 130
953
910
PE M10 x 32.5
Tightening torque 10±1 Nm
71.5
660
PE M10 x 36
Tightening torque 10±1 Nm
ø12
(10 x)
405±1
405±1
980±1
1010
SSB2262-S-E
Please read Cautions and warnings and
Important notes at the end of this document.
7
07/07
3-line filters
B84143V*R127
Sine-wave EMC output filters SineFormer
Cautions and warnings
■ Please note the advices in our data book “EMC Filters” (latest edition). Attention should be paid
to the chapter “General safety notes”.
■ It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
■ Danger of electric shock. SineFormer contain components that store an electric charge. Danger-
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
■ The protective earth connections shall be the first to be made when the SineFormer is installed
and the last to be disconnected. Depending on the magnitude of the leakage currents, the par-
ticular specifications for making the protective-earth connection must be observed.
■ Impermissible overloading of the SineFormer, such as with circuits able to cause resonances,
impermissible voltages at higher frequencies etc. can lead to bodily injury and death as well as
cause substantial material damages (e.g. destruction of the filter housing).
■ SineFormer must be protected in the application against impermissible exceeding of the rated
currents by overcurrent protective.
■ In case of leakage currents > 3.5 mA you shall mount the PE conductor stationary with the re-
quired cross section before beginning of operation and save it against disconnecting. For leak-
age currents IL1) < 10 mA the PE conductor must have a KU value2) of 4.5; for leakage currents
IL ≥ 10 mA the PE conductor must have a KU value of 6.
■ The information, specifications and values contained in this data sheet are based on our know-
lege of typical requirements that are often placed on SineFormer. It is incumbent on the customer
to check and decide whether this SineFormer is suitable for use in a particular application.
■ In particular the values with regard to “temperature” and “noise” have to be observed.
1) IL = leakage current
2) The KU value (symbol KU) is a classification parameter of safety-referred failure types designed to ensure protec-
tion against hazardous body currents and excessive heating.
A value of KU = 4.5 with respect to interruptions is attained:
− with a permanently connected protective earth circuit 1.5 mm2
− with a protective earth circuit 2.5 mm2 connected via shroud connectors (IEC 60309-2).
KU = 6 with respect to interruptions is achieved for fixed-connection lines 10 mm2 where the type of connection
and line layout correspond to the requirements for PEN conductors as specified in relevant standards.
Please read Cautions and warnings and
Important notes at the end of this document.
8
07/07
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical require-
ments that are often placed on our products in the areas of application concerned. We neverthe-
less expressly point out that such statements cannot be regarded as binding statements
about the suitability of our products for a particular customer application.
As a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with
them than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications re-
quiring a very high level of operational safety and especially in customer applications in which the
malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suit-
able design of the customer application or other action taken by the customer (e.g. installation of
protective circuitry or redundancy) that no injury or damage is sustained by third parties in the
event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this pub-
lication may contain substances subject to restrictions in certain jurisdictions (e.g. be-
cause they are classed as “hazardous”). Useful information on this will be found in our Material
Data Sheets on the Internet (www.epcos.com/material). Should you have any more detailed
questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products. Consequent-
ly, we cannot guarantee that all products named in this publication will always be available.
The aforementioned does not apply in the case of individual agreements deviating from the fore-
going for customer-specific products.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, BAOKE, Alu-X, CeraDiode, CSSP, MiniBlue, MKK, MLSC, MotorCap,
PCC, PhaseCap, PhaseMod, SIFERRIT, SIFI, SIKOREL, SilverCap, SIMDAD, SIMID,
SineFormer, SIOV, SIP5D, SIP5K, ThermoFuse, WindCap are trademarks registered or pend-
ing in Europe and in other countries. Further information will be found on the Internet at www.ep-
cos.com/trademarks.
9
07/07
相关型号:
B84143V0320R127
3-line sine-wave EMC output filters for converters and power electronics -SineFormer-
EPCOS
©2020 ICPDF网 联系我们和版权申明