VMS-300A [CUI]
AC-DC POWER SUPPLY;型号: | VMS-300A |
厂家: | CUI INC |
描述: | AC-DC POWER SUPPLY |
文件: | 总10页 (文件大小:2583K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
For more information, please visit the product page.
date 12/06/2016
page 1 of 10
SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
FEATURES
• up to 300W continuous power
• universal input voltage range
• industry standard 3” x 5” footprint
• power factor correction
• remote voltage sense & on/off control
• fan & 5 Vdc aux outputs
• covered and open-frame configurations
• over voltage, over current, over temperature, and short circuit protections
• medical 60601-1 safety approvals
• designed for 2 x MOPP applications
• efficiency up to 94%
output
voltage
output
current
max
output
power1
max
ripple
efficiency3
MODEL
and noise2
max
typ
(Vdc)
12
24
36
48
5
(A)
(W)
(mVp-p)
(%)
VMS-300A-12
VMS-300A-24
VMS-300A-36
VMS-300A-48
Vstb4
25
12.5
8.34
6.25
1
300
300
300
300
5
120
150
150
150
100
92.5
93.5
93.5
94
--
Notes:
1. Maximum output power of 300 W (5 W for Vstb) with 10 CFM forced air, 200 W (3 W for Vstb) with convection cooling.
2. At full load, nominal input, 20 MHz bandwidth oscilloscope, output terminated with 10 μF electrolytic and 0.1 μF ceramic capacitors.
3. At full load, 25°C, 230 Vac input.
4. Standby output voltage. Present on all models.
5. All specifications are measured at Ta=25°C, 230 Vac input voltage, and 60% rated output load unless otherwise specified.
PART NUMBER KEY
VMS-300A - XX - XXX - X
Base Number
Input Connector:
“blank” = TAIWAN KING PIN
TERMINAL PVHI series
Output Voltage
Chassis:
“blank” = open-frame
CNF = covered
1 = LONG CHU P3060 series
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 2 of 10
INPUT
parameter
voltage
conditions/description
min
90
typ
max
264
63
units
Vac
frequency
47
Hz
at 100 Vac
at 240 Vac
4.0
1.8
A
A
current
inrush current
at 240 Vac, 25°C, cold start
30
A
leakage current
0.3
mA
leakage current (enclosure/
patient)
0.1
0.3
mA
W
power factor correction
meets EN 61000-3-2
no load power consumption
measured with the PS-ON signal configured to OFF
OUTPUT
parameter
conditions/description
min
typ
max
units
at 115/230 Vac, full load
12 Vdc output models
24 Vdc output models
36 Vdc output models
48 Vdc output models
25,000
12,500
5,000
μF
μF
μF
μF
output capacitance
3,750
at full load, 25°C
Vo
Vstb
initial set point accuracy
line regulation
±1
±3
%
%
high line to low line at full load
Vo
Vstb
±0.5
±1
%
%
from full to 10% load
Vo
Vstb
load regulation
±1
±5
%
%
hold-up time
at 115 Vac
16
ms
%
adjustability
built in trim pot (VR)
at full load
±5
switching frequency
temperature coefficient
60
0
80
2
kHz
%/°C
Vdc
mA
±0.05
4.5
PS-ON
power on
PS-ON = 0V
PS-ON signal1
PS-ON = NC (internal circuit will drive PS-On to 11~16 Vdc)
power off
PS-ON = NC
0
mA
TTL goes high 50~250 ms after powered on
TTL goes low 5~20 ms before 90% Vo
power good (PG)
standby output voltage
5 Vdc / 1 A
fan output
12 Vdc / 500 mA
Notes:
1. When not used, short PS-ON & signal GND.
PROTECTIONS
parameter
conditions/description
min
typ
max
units
latch mode
12 Vdc output models
24 Vdc output models
36 Vdc output models
48 Vdc output models
15
30
43
56
Vdc
Vdc
Vdc
Vdc
over voltage protection
over current protection
short circuit protection
over temperature protection
130
150
180
110
%
hiccup, auto recovery
auto recovery (temperature of C37)
°C
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 3 of 10
SAFETY & COMPLIANCE
parameter
conditions/description
min
typ
max
units
input to output (2MOPP) for 1 minute
input to earth (1MOPP) for 1 minute
output to earth (1MOPP) for 1 minute
4,000
1,500
1,500
Vac
Vac
Vac
isolation voltage
isolation resistance
safety approvals
safety class
100
MΩ
UL/cUL 60601-1, IEC 60601-1, EN 60601-1 (3.1 edition)
class I
EN55011, EN55022 Class B, EN55024, FCC Class B, EN61204-3, EN61000-6-1, EN61000-6-3,
EN60601-1-2, EN61000-3-2, EN61000-3-3
EMI/EMC
MTBF
RoHS
as per MIL-HDBK-217F, at 115 Vac, 25°C, GB
2011/65/EU
100,000
hours
Notes:
1. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives.
ENVIRONMENTAL
parameter
conditions/description
min
-40
-40
typ
max
80
units
°C
operating temperature
storage temperature
operating humidity
operating altitude
see derating curves
85
°C
non-condensing
93
%
3000
4
m
as per MIL-STD-810F Table 514.5C-VIII; 15~2000
Hz for 1 hour on each axis for 3 hours
vibration2
shock2
G
G
as per MIL-STD-810F Table 516.5, Table 516.5-1;
for 10 ms on each axis 3 times
75
Notes:
2. See Installation Instructions for mounting requirements.
DERATING CURVES
VMS-300A Output Power vs. Input Voltage
(Natural Convection)
VMS-300A-CNF Output Power vs. Input Voltage
(Natural Convection)
300
250
300
250
200
150
100
50
200
150
100
50
90
110
130
150
170
190
210
230
250 264
90
110
130
150
170
190
210
230
250 264
Input Voltage (Vac)
Input Voltage (Vac)
VMS-300A-CNF Output Power vs. Ambient Temperature
VMS-300A Output Power vs. Ambient Temperature
(Natural Convection)
(Natural Convention)
300
300
Input voltage 220~264 Vac
Input voltage 220~264 Vac
250
250
Input voltage 100~200 Vac
Input voltage 90~200 Vac
200
200
150
100
50
150
100
50
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
Ambient Temperature (°C)
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 4 of 10
DERATING CURVES (CONTINUED)
VMS-300A Output Power vs. Ambient Temperature
(with 10 CFM airflow)
VMS-300A-CNF Output Power vs. Ambient Temperature
(with 10 CFM airflow)
300
300
250
250
200
150
100
50
200
150
100
50
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80
-40 -30 -20 -10
0
10 20 30 40 50 60 70 80
Ambient Temperature (°C)
Ambient Temperature (°C)
EFFICIENCY CURVES
12 Vdc Output Efficiency Curve
24 Vdc Output Efficiency Curve
(at 25°C)
(at 25°C)
36 Vdc Output Efficiency Curve
48 Vdc Output Efficiency Curve
(at 25°C)
(at 25°C)
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 5 of 10
MECHANICAL
parameter
conditions/description
min
typ
max
units
VMS-300A models: 5.00 x 3.00 x 1.38 (127 x 76.2 x 35.1 mm)
VMS-300A-CNF models: 5.35 x 3.46 x 1.59 (136 x 88 x 40.4 mm)
inch
inch
dimensions
weight
VMS-300A models
VMS-300A-CNF models
410
515
g
g
cooling
external fan
CN1 input connector
CN1 input connector (optional)
CN4 output connector
CN5 output connector
CN1 mates with JST housing VHR series or equivalent
CN1 mates with MOLEX housing 5195 series or equivalent
CN4 mates with JST housing PH series or equivalent
CN5 mates with JST housing PH series or equivalent
+Vo & -Vo terminals are M3 screws that mate with round or Y
terminals with max OD of 6.75 mm and max ID of 3.9 mm
output terminals
MECHANICAL DRAWING
Open-frame
units: inch [mm]
tolerance: X.XXX = ±0.020 [±0.50]
5.000 [127.00]
4.551 [115.60]
Air flow
direction
CN1
10CFM
FAN
PIN
1
Function
ACL
0.224 [5.70]
2
-
3
ACN
CN5
CN1
ACL
1
2
3
4
3
2
1
CN4
+Vo
ACN
PIN
1
Function
-FAN
-Vo
2
+FAN
GND
cross sectional view A
Scale 1:1
3
4
3
2
1
4
+5 VSB
GND
CN5
5
VR
6
PS-ON
CN4
1
2
3
4
5
6
CN5
PIN
1
Function
GND
2
PG
4-M4*0.7
3
-Sense
+Sense
4
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 6 of 10
MECHANICAL DRAWING (CONTINUED)
Covered
units: inch [mm]
tolerance: X.XXX = ±0.020 [±0.50]
5.35 [136.00]
Air flow
direction
10CFM
CN1
Function
FAN
PIN
1
ACL
-
2
3
ACN
CN1
ACL
1
2
3
+Vo
CN5
CN4
ACN
4
3
2
1
PIN
1
Function
-FAN
-Vo
2
+FAN
GND
3
cross sectional view A
Scale 1:1
4
+5 VSB
GND
5
VR
6
PS-ON
CN4
1
2
3
4
5
6
CN5
PIN
1
Function
GND
2
PG
3
-Sense
+Sense
4
0.402 [10.20]
4.55 [115.60]
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 7 of 10
INSTALLATION INSRUCTIONS
The VMS-300A series has (4) 4 mm diameter mounting holes that can be used in (3) types of installations.
Type 1
Type 2
Mounting from top with spacers (required to meet
vibration specifications)
Mounting from top without spacers
Screw Size: (4) M3X0.5
Spacer: 4 mm diameter max, 8 mm high minimum
Screw Size: (4) M3X0.5
Mounting torque: 3 kgf-cm
Mounting torque: 3 kgf-cm
Type 3
Mounting Torque
Mounting from bottom
VMS-300A
Screw Size: (4) M4X0.7
Mounting torque: 7 kgf-cm
VMS-300A-CNF
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 8 of 10
INSTALLATION INSRUCTIONS (CONTINUED)
Output Terminals
Mate with round or Y terminals with max OD of 6.75 mm and max ID of 3.9 mm
Terminal Size: (2) M3
Torque: 3 kgf-cm
Mounting Clearance
Allow at least 4 mm side clearance and 5 mm height clearance. If clearances aren’t met, the isolation and withstand
specifications may not be met.
Field Ground
Should be connected to the earth (ground) terminal of the apparatus otherwise conducted noise and output noise will
increase.
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 9 of 10
APPLICATION NOTES
On/off Remote Control
A PS On/Off remote control is provided in CN4. See Figure 1 for the PS-ON diagram and control function.
Figure 1
VMS-300A
Note: Power on: VPS-ON ≤ 2V, IPS-ON ≥ 2 mA
(PS-ON and GND short, IPS-ON = 4.5 mA typical)
Power off: Open circuit, VPS-ON = 11~16 V
When the PS On/off remote control function is not
used, connect a short circuit between the PS-ON
control & the signal GND.
Output Remote Sensing
The VMS-300A series can remotely sense both lines of the output. The feature moves the effective voltage regulation point
from the output of the unit to the point of connection of the remote sense pins. This feature automatically adjusts the real
output in order to compensate for voltage drops in distribution and maintain a regulated voltage at the point of load. The
remote sense voltage range is as follows:
[(+Vout) – (-Vout)] – [(+Sense) – (-Sense)] ≤ 10% Vo_nominal
If the remote sense is not used, the sense pins should be connected locally to the respective Vout pins. The remote sense pins are located
on CN4.
Figure 2
AC_L
+Vo
+Sense
VMS-300A
Load
AC_N
PE
Series
-Sense
-Vo
cui.com
For more information, please visit the product page.
CUI Inc │SERIES: VMS-300A │ DESCRIPTION: AC-DC POWER SUPPLY
date 12/06/2016 │ page 10 of 10
REVISION HISTORY
rev.
description
date
1.0
initial release
12/06/2016
The revision history provided is for informational purposes only and is believed to be accurate.
Headquarters
20050 SW 112th Ave.
Tualatin, OR 97062
800.275.4899
Fax 503.612.2383
cui.com
techsupport@cui.com
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.
相关型号: