VMS-225 [CUI]

AC-DC POWER SUPPLY;
VMS-225
型号: VMS-225
厂家: CUI INC    CUI INC
描述:

AC-DC POWER SUPPLY

文件: 总6页 (文件大小:595K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
For more information, please visit the product page  
|
If your application requires forced air, view our Dc Fans  
date 09/05/2017  
page 1 of 6  
SERIES: VMS-225 DESCRIPTION: AC-DC POWER SUPPLY  
FEATURES  
• up to 225 W continuous power  
• -40°C to 70°C operating temperature  
• industry standard foot print 2” x 4”  
• low profile 1”  
• power factor correction  
• 12 V/0.5 A fan output  
• standby power <0.5 W  
• efficiency up to 94%  
• long life electrolytic capacitors  
• complying with the latest EMI standard  
IEC 60601-1-2: 2014 (4th edition)  
output  
voltage  
output  
current  
max  
output  
ripple  
efficiency  
MODEL  
power1,2  
and noise3,4  
max  
max  
typ  
(Vdc)  
12  
(A)  
(W)  
(mVp-p)  
(%)  
VMS-225-12  
VMS-225-15  
VMS-225-24  
VMS-225-30  
VMS-225-48  
VMS-225-58  
18.75  
15  
225  
225  
225  
225  
225  
225  
120  
150  
240  
300  
480  
580  
92  
92  
93  
93  
94  
94  
15  
24  
9.38  
7.5  
30  
48  
4.69  
3.88  
58  
Notes:  
1. Maximum output power of 225 W with 13 CFM forced air cooling, and 120 W with natural convection cooling at 100 to 264 Vac.  
2. Combined output power of main output and fan supply shall not exceed the max power rating.  
3. Ripple is peak to peak with 20 MHz bandwidth and 10 µF tantalum capacitor in parallel with a 0.1 µF capacitor at rated line voltage and load ranges.  
4. Output ripple can be more than 10% of the output voltage at -40°C.  
5. All specifications are measured at Ta=25°C, nominal input voltage, and rated output load unless otherwise specified.  
PART NUMBER KEY  
VMS-225 - XX - X  
Output Connections:  
“blank” = screw type  
1 = header type  
Base Number  
Output Voltage  
cui.com  
For more information, please visit the product page  
|
If your application requires forced air, view our Dc Fans  
CUI Inc SERIES: VMS-225 DESCRIPTION: AC-DC POWER SUPPLY  
date 09/05/2017 page 2 of 6  
INPUT  
parameter  
voltage  
conditions/description  
min  
80  
typ  
max  
264  
63  
units  
Vac  
frequency  
47  
Hz  
at 115 Vac, full load  
at 230 Vac, full load  
2.2  
1.1  
A
A
current  
inrush current  
at 230 Vac, cold start  
at 230 Vac  
45  
0.1  
0.5  
A
leakage current  
touch current  
0.3  
mA  
mA  
power factor  
at full load  
0.95  
no load power consumption  
input fuse  
W
6.3 A/250 V time delay fuse (included)  
OUTPUT  
parameter  
conditions/description  
min  
typ  
±1  
±0.5  
±1  
2
max  
units  
%
initial set point accuracy  
line regulation  
load regulation  
start-up delay time  
rise time  
%
from 100% to 10% load  
%
s
at 115/230 Vac  
at 115/230 Vac  
built in trim pot  
55  
ms  
ms  
%
hold-up time  
adjustability1  
10  
±3  
switching frequency  
50  
300  
kHz  
25% step load change, at 0.1 A/µS slew rate, 50%  
duty cycle, 50/60 Hz, max excursion 4%, recovery  
time 5 ms  
transient response  
temperature coefficient  
at 0~50°C  
±0.05  
%/°C  
fan output2  
12 Vdc / 500 mA  
Notes:  
1. Adjustment potentiometer is located on the SMT side of the PCB.  
2. Fan supply output voltage tolerance including set point accuracy, line and load regulation is ±10% and ripple and noise is less than 10%.  
PROTECTIONS  
parameter  
conditions/description  
hiccup, auto recovery  
hiccup, auto recovery  
hiccup, auto recovery  
min  
110  
110  
typ  
max  
units  
%
over voltage protection  
over current protection  
short circuit protection  
140  
%
SAFETY & COMPLIANCE  
parameter  
conditions/description  
min  
typ  
max  
units  
input to output (2 x MOPP)  
input to ground (1 x MOPP)  
output to ground  
4,200  
1,500  
1,500  
Vac  
Vac  
Vac  
isolation voltage  
IEC 60601-1: 2005 +CORR1:2006  
+CORR2:2007 +AM1:2012, EN 60601-1:2006  
+A11:2011 +A1:2013, ANSI/AAMI ES 60601-1  
(2005+CI:09+A2:10), AMD1:2012 CAN/CSA-  
C22.2 No 60601-1 (2008) 60601-1:14 ISO 14971,  
2nd edition complies with LVD directive  
safety approvals  
safety class  
class I  
conducted emissions  
EN 55011 Class B  
Notes:  
3. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives.  
cui.com  
For more information, please visit the product page  
|
If your application requires forced air, view our Dc Fans  
CUI Inc SERIES: VMS-225 DESCRIPTION: AC-DC POWER SUPPLY  
date 09/05/2017 page 3 of 6  
SAFETY & COMPLIANCE  
parameter  
conditions/description  
min  
typ  
max  
units  
EN 55011 Class B (to be controlled in end system with external  
core (King core K5B RC 25 x 12 x 15-M in input cable (5 turns))  
radiated emissions  
input current harmonics  
voltage fluctuation and flicker  
ESD immunity  
EN 61000-3-2, class D  
EN 61000-3-3, pass  
EN 61000-4-2, level 4, criterion A  
EN 61000-4-3, level 4, criterion A  
radiated field immunity  
electrical fast transient  
immunity  
EN 61000-4-4, level 4, criterion A  
surge immunity  
conducted immunity  
magnetic field immunity  
voltage dips, interruptions  
MTBF  
EN 61000-4-5, level 4, criterion A  
EN 61000-4-6, level 4, criterion A  
EN 61000-4-8, level 4, criterion A  
EN 61000-4-11, criterion A & B  
as per Telcordia-SR332-issue 3  
2011/65/EU  
3,370,000  
hours  
RoHS  
Notes:  
1. The power supply is considered a component which will be installed into final equipment. The final equipment still must be tested to meet the necessary EMC directives.  
ENVIRONMENTAL  
parameter  
conditions/description  
min  
-40  
-40  
20  
typ  
max  
70  
units  
°C  
operating temperature  
storage temperature  
operating humidity  
storage humidity  
see derating curves  
85  
°C  
non-condensing  
non-condensing  
90  
%
20  
90  
%
operating altitude  
16,000  
ft  
DERATING CURVES  
Output Power vs. Input Voltage  
Output Power vs. Ambient Temperature  
225  
210  
195  
180  
165  
150  
135  
120  
105  
90  
100  
99  
Forced Air (13 CFM)  
98  
97  
96  
95  
94  
Natural Convection  
80  
75  
60  
45  
30  
15  
0
93  
92  
91  
92  
-40 -30 -20 -10  
0
10  
20 30  
40  
50  
60  
70  
85 90 95 100 105 110 115 120 125 255 260 264  
Input Voltage (Vac)  
Ambient Temperature (ºC)  
cui.com  
For more information, please visit the product page  
|
If your application requires forced air, view our Dc Fans  
CUI Inc SERIES: VMS-225 DESCRIPTION: AC-DC POWER SUPPLY  
date 09/05/2017 page 4 of 6  
MECHANICAL  
parameter  
dimensions  
weight  
conditions/description  
min  
typ  
max  
units  
inch  
g
4.00 x 2.00 x 1.00 (101.60 x 50.80 x 25.40 mm)  
200  
cooling  
external fan  
J1 input connector  
Mates with JST housing VHR-3M; pins SVH-41T-P1.1 or equivalent  
Screw Type: Accepts 28 ~ 16 AWG wire  
Header Type: Mates with JST housing VHR-6M; pins SVH-41T-P1.1 or equivalent  
J2 output connector  
J3 fan connector  
Mates with Tyco 640440-2  
MECHANICAL DRAWINGS  
Screw Type  
units: inch [mm]  
tolerance: ±0.04 [±1.0]  
J1  
PIN  
1
Function  
L
NC  
N
2
3
J2  
PIN  
1
Function  
+VE  
+VE  
+VE  
-VE  
2
3
4
5
-VE  
6
-VE  
J3  
PIN  
1
Function  
+FAN  
2
-FAN  
cui.com  
For more information, please visit the product page  
|
If your application requires forced air, view our Dc Fans  
CUI Inc SERIES: VMS-225 DESCRIPTION: AC-DC POWER SUPPLY  
date 09/05/2017 page 5 of 6  
MECHANICAL DRAWINGS (CONTINUED)  
Header Type  
units: inch [mm]  
tolerance: ±0.04 [±1.0]  
J1  
PIN  
1
Function  
L
NC  
N
2
3
J2  
PIN  
1
Function  
+VE  
+VE  
+VE  
-VE  
2
3
4
5
-VE  
6
-VE  
J3  
PIN  
1
Function  
+FAN  
2
-FAN  
cui.com  
For more information, please visit the product page  
|
If your application requires forced air, view our Dc Fans  
CUI Inc SERIES: VMS-225 DESCRIPTION: AC-DC POWER SUPPLY  
date 09/05/2017 page 6 of 6  
REVISION HISTORY  
rev.  
description  
date  
1.0  
initial release  
09/05/2017  
The revision history provided is for informational purposes only and is believed to be accurate.  
Headquarters  
20050 SW 112th Ave.  
Tualatin, OR 97062  
800.275.4899  
Fax 503.612.2383  
cui.com  
techsupport@cui.com  
CUI offers a two (2) year limited warranty. Complete warranty information is listed on our website.  
CUI reserves the right to make changes to the product at any time without notice. Information provided by CUI is believed to be accurate and reliable. However, no responsibility is  
assumed by CUI for its use, nor for any infringements of patents or other rights of third parties which may result from its use.  
CUI products are not authorized or warranted for use as critical components in equipment that requires an extremely high level of reliability. A critical component is any component of a  
life support device or system whose failure to perform can be reasonably expected to cause the failure of the life support device or system, or to affect its safety or effectiveness.  

相关型号:

VMS-225-12

Chassis Mount Power Supply, 12 Vdc, 18.75 A, 225 W
CUI

VMS-225-12-1

AC-DC Regulated Power Supply Module
CUI

VMS-225-15

AC-DC POWER SUPPLY
CUI

VMS-225-24

AC-DC POWER SUPPLY
CUI

VMS-225-24-1

AC/DC CONVERTER 24V 120W/225W
CUI

VMS-225-30

AC-DC POWER SUPPLY
CUI

VMS-225-30-1

AC/DC CONVERTER 30V 120W/225W
CUI

VMS-225-48

AC-DC POWER SUPPLY
CUI

VMS-225-48-1

AC-DC Regulated Power Supply Module
CUI

VMS-225-58

Chassis Mount Power Supply, 58 Vdc, 3.88 A, 225 W
CUI

VMS-225-58-1

AC-DC Regulated Power Supply Module
CUI

VMS-275

AC-DC POWER SUPPLY
CUI