LCA150S-15-SY [COSEL]
AC/DC PS (OPEN FRAME);型号: | LCA150S-15-SY |
厂家: | COSEL CO., LTD. |
描述: | AC/DC PS (OPEN FRAME) |
文件: | 总14页 (文件大小:809K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LC
A
10
S
-5
-O
6
LCA10S
1
2
3
4
5
1Series name
Recommended EMI/EMC Filter
NAC-06-472
R
2100/120V input
3Output wattage
4Single output
5Output voltage
6Optional *3
C :with Coating
G :Low leakage current
Y :with Potentiometer
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL
LCA10S-5
10
LCA10S-5-H
10
LCA10S-12
10.8
LCA10S-15
10.5
LCA10S-24
12
MAX OUTPUT WATTAGE[W]
DC OUTPUT
5V 2A
5V 2A
12V 0.9A
15V 0.7A
24V 0.5A
SPECIFICATIONS
MODEL
LCA10S-5
LCA10S-5-H
LCA10S-12
LCA10S-15
LCA10S-24
VOLTAGE[V]
CURRENT[A]
AC85 - 132 1 or DC110 - 170
f
(
)
ACIN 100V 0.3typ Io=100%
FREQUENCY[Hz]
INPUT
47 - 440 or DC
71typ
EFFICIENCY[%]
71typ
75typ
75typ
78typ
(
)
INRUSH CURRENT[A] ACIN 100V 25typ Io=100%
(
,
,
)
LEAKAGE CURRENT[mA] 0.5max 60Hz According to UL CSA and DEN-AN
LCA
VOLTAGE[V]
CURRENT[A]
5
2
5
12
15
24
(
)
2 Peak 3
0.9
0.7
0.5
LINE REGULATION[mV] 20max
LOAD REGULATION[mV] 40max
20max
48max
100max
120max
160max
150max
180max
120max
48max
60max
120max
120max
160max
150max
180max
150max
60max
96max
150max
120max
160max
150max
180max
240max
96max
40max
1
*
1
*
1
*
1
*
0 to +50
80max
80max
C
RIPPLE[mVp-p]
-10 - 0
140max
120max
160max
140max
120max
160max
50max
C
0 to +50
C
OUTPUT
RIPPLE NOISE[mVp-p]
-10 - 0
C
TEMPERATURE REGULATION[mV] 50max
2
*
DRIFT[mV]
20max
20max
(
,
)
START-UP TIME[ms]
HOLD-UP TIME[ms]
100max ACIN 85V Io=100%
(
,
)
(
,
)
10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100%
(
,
,
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] Fixed "Y"which can be adjusted the output is available as optional:5V -5 to +10% : 12 15 24V 10%
t
OUTPUT VOLTAGE SETTING[V] 4.9 - 5.3
4.9 - 5.3
11.5 - 12.5
14.4 - 15.6
23.0 - 25.0
(
)
OVERCURRENT PROTECTION Works over 105% of rating works over 105% of peak current at option -H and recovers automatically
,
OVERVOLTAGE PROTECTION Works over 115% of rating by zener diode clamping
PROTECTION
CIRCUIT AND OPERATING INDICATION Not provided
OTHERS
REMOTE SENSING
REMOTE ON/OFF
INPUT-OUTPUT
Not provided
Not provided
,
,
,
(
)
)
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , (
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
ISOLATION INPUT-FG
OUTPUT-FG
,
,
(
)
AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
,
,
,
(
) (
),
,
(
,
)
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60
20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
,
(
),
,
(
,
)
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75
20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
,
(
),
,
,
VIBRATION
10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
IMPACT
196.1m/s2 20G 11ms once each X Y and Z axis
(
),
,
,
SAFETY AND
NOISE
,
UL60950-1 CSA C22.2 No.60950-1 Complies with DEN-AN
AGENCY APPROVALS
CONDUCTED NOISE
CASE SIZE/WEIGHT
COOLING METHOD
,
Complies with FCC-B VCCI-B
REGULATIONS
(
)
H D / 65g max
X X
49 17 94mm W
X
X
OTHERS
Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN : RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C with the input voltage held constant at the rated input/output.
*3 Please contact us about safety approvals for the model with option.
*
Avoid prolonged use under over-load.
June 29, 2011
LCA-2
LCA10S
External view
LCA
Performance data
STATIC CHARACTERISTICS (LCA10S-5)
¡
RISE TIME & FALL TIME (LCA10S-5)
¡
OVERCURRENT CHARACTERISTICS (LCA10S-5)
¡
DERATING CURVE
¡
June 29, 2011
LCA-3
Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LC
A
15
S
-5
-O
6
LCA15S
1
2
3
4
5
1Series name
Recommended EMI/EMC Filter
NAC-06-472
R
2100/120V input
3Output wattage
4Single output
5Output voltage
6Optional *3
C :with Coating
G :Low leakage current
Y :with Potentiometer
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL
LCA15S-5
15
LCA15S-12
LCA15S-15
15
LCA15S-24
16.8
MAX OUTPUT WATTAGE[W]
DC OUTPUT
15.6
5V 3A
12V 1.3A
15V 1A
24V 0.7A
SPECIFICATIONS
MODEL
LCA15S-5
LCA15S-12
LCA15S-15
LCA15S-24
VOLTAGE[V]
CURRENT[A]
AC85 - 132 1 or DC110 - 170
f
(
)
ACIN 100V 0.4typ Io=100%
FREQUENCY[Hz]
INPUT
47 - 440 or DC
72typ
EFFICIENCY[%]
75typ
75typ
78typ
(
) (
)
INRUSH CURRENT[A] ACIN 100V 20typ Io=100% At cold start
(
,
,
)
LEAKAGE CURRENT[mA] 0.5max 60Hz According to UL CSA and DEN-AN
LCA
VOLTAGE[V]
CURRENT[A]
5
3
12
15
24
1.3
1
0.7
LINE REGULATION[mV] 20max
LOAD REGULATION[mV] 40max
48max
100max
120max
160max
150max
180max
120max
48max
60max
120max
120max
160max
150max
180max
150max
60max
96max
150max
120max
160max
150max
180max
240max
96max
1
*
1
*
1
*
1
*
0 to +50
80max
C
RIPPLE[mVp-p]
-10 - 0
140max
120max
160max
C
0 to +50
C
OUTPUT
RIPPLE NOISE[mVp-p]
-10 - 0
C
TEMPERATURE REGULATION[mV] 50max
2
*
DRIFT[mV]
20max
(
,
)
START-UP TIME[ms]
HOLD-UP TIME[ms]
100max ACIN 85V Io=100%
(
,
)
(
,
)
10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100%
(
,
,
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] Fixed "Y"which can be adjusted the output is available as optional:5V -5 to +10% : 12 15 24V 10%
t
OUTPUT VOLTAGE SETTING[V] 4.9 - 5.3
11.5 - 12.5
14.4 - 15.6
23.0 - 25.0
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
,
OVERVOLTAGE PROTECTION Works over 115% of rating by zener diode clamping
PROTECTION
CIRCUIT AND OPERATING INDICATION Not provided
OTHERS
REMOTE SENSING
REMOTE ON/OFF
INPUT-OUTPUT
Not provided
Not provided
,
,
,
(
)
)
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , (
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
ISOLATION INPUT-FG
OUTPUT-FG
,
,
(
)
AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
,
,
,
(
) (
),
,
(
,
)
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60
20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
,
(
),
,
(
,
)
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75
20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
,
(
),
,
,
VIBRATION
10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
IMPACT
196.1m/s2 20G 11ms once each X Y and Z axis
(
),
,
,
SAFETY AND
NOISE
,
UL60950-1 CSA C22.2 No.60950-1 Complies with DEN-AN
AGENCY APPROVALS
CONDUCTED NOISE
CASE SIZE/WEIGHT
COOLING METHOD
,
Complies with FCC-B VCCI-B
REGULATIONS
(
)
H D / 80g max
X X
50 17 115mm W
X
X
OTHERS
Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN : RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C with the input voltage held constant at the rated input/output.
*3 Please contact us about safety approvals for the model with option.
*
Avoid prolonged use under over-load.
June 29, 2011
LCA-4
LCA15S
External view
LCA
Performance data
STATIC CHARACTERISTICS (LCA15S-5)
¡
RISE TIME & FALL TIME (LCA15S-5)
¡
OVERCURRENT CHARACTERISTICS (LCA15S-5)
¡
DERATING CURVE
¡
June 29, 2011
LCA-5
Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LC
A
30
S
-5
-O
6
LCA30S
1
2
3
4
5
1Series name
Recommended EMI/EMC Filter
NAC-06-472
R
2100/120V input
3Output wattage
4Single output
5Output voltage
6Optional *3
C :with Coating
G :Low leakage current
Y :with Potentiometer
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL
LCA30S-3
18
LCA30S-5
30
LCA30S-12
30
LCA30S-15
30
LCA30S-24
31.2
LCA30S-36
LCA30S-48
33.6
MAX OUTPUT WATTAGE[W]
DC OUTPUT
32.4
3V 6A
5V 6A
12V 2.5A
15V 2A
24V 1.3A
36V 0.9A
48V 0.7A
SPECIFICATIONS
MODEL
LCA30S-3
LCA30S-5
LCA30S-12
LCA30S-15
LCA30S-24
LCA30S-36
LCA30S-48
VOLTAGE[V]
CURRENT[A]
AC85 - 132 1 or DC110 - 170
f
(
)
ACIN 100V 0.7typ Io=100%
FREQUENCY[Hz]
INPUT
47 - 440 or DC
EFFICIENCY[%]
69typ
75typ
) (
80typ
)
81typ
82typ
80typ
80typ
(
INRUSH CURRENT[A] ACIN 100V 25typ Io=100% At cold start
(
,
,
)
LEAKAGE CURRENT[mA] 0.5max 60Hz According to UL CSA and DEN-AN
LCA
VOLTAGE[V]
CURRENT[A]
3
6
5
12
15
2
24
36
48
6
2.5
1.3
0.9
0.7
LINE REGULATION[mV] 20max
LOAD REGULATION[mV] 40max
20max
40max
80max
140max
120max
160max
50max
20max
48max
100max
120max
160max
150max
180max
120max
48max
60max
96max
150max
120max
160max
150max
180max
240max
96max
144max
240max
150max
200max
250max
300max
360max
144max
192max
300max
150max
200max
350max
400max
480max
192max
120max
120max
160max
150max
180max
150max
60max
1
*
1
*
1
*
1
*
0 to +50
80max
C
RIPPLE[mVp-p]
-10 - 0
140max
120max
160max
C
0 to +50
C
OUTPUT
RIPPLE NOISE[mVp-p]
-10 - 0
C
TEMPERATURE REGULATION[mV] 50max
2
*
DRIFT[mV]
20max
(
,
)
START-UP TIME[ms]
HOLD-UP TIME[ms]
100max ACIN 85V Io=100%
(
,
)
(
,
)
10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100%
(
,
,
,
,
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] 2.85 - 3.6
Fixed "Y"which can be adjusted the output is available as optional:5V -5 to +10% : 12 15 24 36 48V 10%
t
OUTPUT VOLTAGE SETTING[V]
4.9 - 5.3
11.5 - 12.5
14.4 - 15.6
23.0 - 25.0
34.5 - 37.5
46.0 - 50.0
xx
OVERCURRENT PROTECTION Works over 105% of rating and recovers automatically
,
Works over 115% of rating by zener diode clamping
OVERVOLTAGE PROTECTION 4.00V min
PROTECTION
CIRCUIT AND OPERATING INDICATION Not provided
OTHERS
REMOTE SENSING
REMOTE ON/OFF
INPUT-OUTPUT
Not provided
Not provided
,
,
,
(
)
)
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , (
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
ISOLATION INPUT-FG
OUTPUT-FG
,
,
(
)
AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
,
,
,
(
) (
),
,
(
,
)
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60
20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
,
(
),
,
(
,
)
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75
20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
,
(
),
,
,
VIBRATION
10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
IMPACT
196.1m/s2 20G 11ms once each X Y and Z axis
(
),
,
,
SAFETY AND
NOISE
,
UL60950-1 CSA C22.2 No.60950-1 Complies with DEN-AN
AGENCY APPROVALS
CONDUCTED NOISE
CASE SIZE/WEIGHT
COOLING METHOD
,
Complies with FCC-B VCCI-B
REGULATIONS
(
)
H D / 150g max
X
50 25 132.5mm W
X
X
X
OTHERS
Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN : RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C with the input voltage held constant at the rated input/output.
*3 Please contact us about safety approvals for the model with option.
*
Avoid prolonged use under over-load.
June 29, 2011
LCA-6
LCA30S
External view
LCA
Performance data
STATIC CHARACTERISTICS (LCA30S-5)
¡
RISE TIME & FALL TIME (LCA30S-5)
¡
OVERCURRENT CHARACTERISTICS (LCA30S-5)
¡
DERATING CURVE
¡
June 29, 2011
LCA-7
Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LC
A
50
S
-5
-O
6
LCA50S
1
2
3
4
5
1Series name
Recommended EMI/EMC Filter
NAC-06-472
R
2100/120V input
3Output wattage
4Single output
5Output voltage
6Optional *4
C :with Coating
G :Low leakage current
Y :with Potentiometer
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
LCA50S-3
30
3V 10A
LCA50S-5
50
5V 10A
LCA50S-12 LCA50S-15 LCA50S-24 LCA50S-24-H LCA50S-36 LCA50S-48
51.6
52.5
60
60
61.2
62.4
12V 4.3A
15V 3.5A
24V 2.5A
24V 2.5A
36V 1.7A
48V 1.3A
SPECIFICATIONS
MODEL
LCA50S-3
LCA50S-5
LCA50S-12 LCA50S-15 LCA50S-24 LCA50S-24-H LCA50S-36 LCA50S-48
VOLTAGE[V]
CURRENT[A]
AC85 - 132 1 or DC110 - 170
f
(
)
ACIN 100V 1.3typ Io=100%
FREQUENCY[Hz]
INPUT
47 - 440 or DC
LCA
EFFICIENCY[%]
71typ
78typ
) (
80typ
)
,
81typ
82typ
82typ
82typ
36
82typ
(
INRUSH CURRENT[A] ACIN 100V 30typ Io=100% At cold start
LEAKAGE CURRENT[mA]
VOLTAGE[V]
(
,
)
0.5max 60Hz According to UL CSA and DEN-AN
3
5
12
4.3
15
3.5
24
2.5
24
(
48
1.3
3
*
)
CURRENT[A]
10
10
2.5 Peak 3 1.7
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
80max
140max
120max
160max
50max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
)
60max
96max
150max
120max
160max
150max
180max
240max
290max
96max
96max
144max
192max
300max
150max
200max
350max
400max
480max
600max
192max
120max
120max
160max
150max
180max
150max
180max
60max
150max
120max
160max
150max
180max
240max
290max
96max
240max
150max
200max
250max
300max
360max
450max
144max
1
1
1
1
*
*
*
*
0 to +50
C
RIPPLE[mVp-p]
-10 - 0
C
0 to +50
C
RIPPLE NOISE[mVp-p]
OUTPUT
-10 - 0
C
0 to +50
C
TEMPERATURE REGULATION[mV]
-10 to +50 60max
C
2
*
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
20max
( ,
200max ACIN 85V Io=100%
(
,
)
(
,
)
10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100%
(
,
,
,
,
,
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] 2.85 - 3.6
Fixed "Y"which can be adjusted the output is available as optional: 5 12 15 24 36 48V 10%
t
OUTPUT VOLTAGE SETTING[V]
4.9 - 5.3
11.5 - 12.5
14.4 - 15.6
23.0 - 25.0
23.0 - 25.0
34.5 - 37.5
46.0 - 50.0
xx
(
)
OVERCURRENT PROTECTION Works over 105% of rating works over 105% of peak current at option -H and recovers automatically
OVERVOLTAGE PROTECTION 4.00 - 5.25V Works at 115 - 140% of rating
PROTECTION
CIRCUIT AND OPERATING INDICATION
Not provided
Not provided
Not provided
OTHERS
REMOTE SENSING
REMOTE ON/OFF
INPUT-OUTPUT
,
,
,
(
)
)
)
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , (
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
ISOLATION INPUT-FG
OUTPUT-FG
,
,
(
AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
,
,
,
(
(
) (
),
),
,
(
,
)
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60
20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
,
,
(
,
)
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75
20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
,
(
),
,
,
VIBRATION
10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
IMPACT
196.1m/s2 20G 11ms once each X Y and Z axis
),
(
,
,
SAFETY AND
NOISE
,
UL60950-1 CSA C22.2 No.60950-1 Complies with DEN-AN
AGENCY APPROVALS
CONDUCTED NOISE
CASE SIZE/WEIGHT
COOLING METHOD
,
Complies with FCC-B VCCI-B
REGULATIONS
(
W H D
X X
)
/ 200g max
50 25 195mm
X
X
OTHERS
Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN : RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C with the input voltage held constant at the rated input/output.
*3 Peak load for 10 sec. or less is acceptable(The average current has to be less than the rated current).
*4 Please contact us about safety approvals for the model with option.
June 29, 2011
LCA-8
LCA50S
External view
LCA
Performance data
STATIC CHARACTERISTICS (LCA50S-5)
¡
RISE TIME & FALL TIME (LCA50S-5)
¡
OVERCURRENT CHARACTERISTICS (LCA50S-5)
¡
DERATING CURVE
¡
June 29, 2011
LCA-9
Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LC
A
75
S
-5
-O
6
LCA75S
1
2
3
4
5
1Series name
Recommended EMI/EMC Filter
NAC-06-472
R
2100/120V input
3Output wattage
4Single output
5Output voltage
6Optional *4
C :with Coating
G :Low leakage current
Y :with Potentiometer
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL
MAX OUTPUT WATTAGE[W]
DC OUTPUT
LCA75S-3
45
3V 15A
LCA75S-5
75
5V 15A
LCA75S-12 LCA75S-15 LCA75S-24 LCA75S-24-H LCA75S-36 LCA75S-48
75.6
75
76.8
76.8
75.6
76.8
12V 6.3A
15V 5A
24V 3.2A
24V 3.2A
36V 2.1A
48V 1.6A
SPECIFICATIONS
MODEL
LCA75S-3
LCA75S-5
LCA75S-12 LCA75S-15 LCA75S-24 LCA75S-24-H LCA75S-36 LCA75S-48
VOLTAGE[V]
CURRENT[A]
AC85 - 132 1 or DC110 - 170
f
(
)
ACIN 100V 1.9typ Io=100%
FREQUENCY[Hz]
INPUT
47 - 440 or DC
LCA
EFFICIENCY[%]
72typ
79typ
) (
81typ
)
,
83typ
84typ
84typ
84typ
36
84typ
(
INRUSH CURRENT[A] ACIN 100V 30typ Io=100% At cold start
LEAKAGE CURRENT[mA]
VOLTAGE[V]
(
,
)
0.5max 60Hz According to UL CSA and DEN-AN
3
5
12
6.3
15
5
24
3.2
24
(
48
1.6
3
*
)
CURRENT[A]
15
15
3.2 Peak 4.2 2.1
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
80max
140max
120max
160max
50max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
)
60max
96max
150max
120max
160max
150max
180max
240max
290max
96max
96max
144max
192max
300max
150max
200max
350max
400max
480max
600max
192max
120max
120max
160max
150max
180max
150max
180max
60max
150max
120max
160max
150max
180max
240max
290max
96max
240max
150max
200max
250max
300max
360max
450max
144max
1
1
1
1
*
*
*
*
0 to +50
C
RIPPLE[mVp-p]
-10 - 0
C
0 to +50
C
RIPPLE NOISE[mVp-p]
OUTPUT
-10 - 0
C
0 to +50
C
TEMPERATURE REGULATION[mV]
-10 to +50 60max
C
2
*
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
20max
( ,
200max ACIN 85V Io=100%
(
,
)
(
,
)
10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100%
(
,
,
,
,
,
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] 2.85 - 3.6
Fixed "Y"which can be adjusted the output is available as optional: 5 12 15 24 36 48V 10%
t
OUTPUT VOLTAGE SETTING[V]
4.9 - 5.3
11.5 - 12.5
14.4 - 15.6
23.0 - 25.0
23.0 - 25.0
34.5 - 37.5
46.0 - 50.0
xx
(
)
OVERCURRENT PROTECTION Works over 105% of rating works over 105% of peak current at option -H and recovers automatically
OVERVOLTAGE PROTECTION 4.00 - 5.25V Works at 115 - 140% of rating
PROTECTION
CIRCUIT AND OPERATING INDICATION
Not provided
Not provided
Not provided
OTHERS
REMOTE SENSING
REMOTE ON/OFF
INPUT-OUTPUT
,
,
,
(
)
)
)
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , (
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
ISOLATION INPUT-FG
OUTPUT-FG
,
,
(
AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
,
,
,
(
(
) (
),
),
,
(
,
)
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60
20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
,
,
(
,
)
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75
20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
,
(
),
,
,
VIBRATION
10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
IMPACT
196.1m/s2 20G 11ms once each X Y and Z axis
),
(
,
,
SAFETY AND
NOISE
,
UL60950-1 CSA C22.2 No.60950-1 Complies with DEN-AN
AGENCY APPROVALS
CONDUCTED NOISE
CASE SIZE/WEIGHT
COOLING METHOD
,
Complies with FCC-B VCCI-B
REGULATIONS
(
W H D
X X
)
/ 300g max
50 32 222mm
X
X
OTHERS
Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN : RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C with the input voltage held constant at the rated input/output.
*3 Peak load for 10 sec. or less is acceptable(The average current has to be less than the rated current).
*4 Please contact us about safety approvals for the model with option.
June 29, 2011
LCA-10
LCA75S
External view
LCA
Performance data
STATIC CHARACTERISTICS (LCA75S-5)
¡
RISE TIME & FALL TIME (LCA75S-5)
¡
OVERCURRENT CHARACTERISTICS (LCA75S-5)
¡
DERATING CURVE
¡
June 29, 2011
LCA-11
Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LC
A
100
S
-5
-O
6
LCA100S
1
2
3
4
5
1Series name
Recommended EMI/EMC Filter
NAC-06-472
R
2100/120V input
3Output wattage
4Single output
5Output voltage
6Optional *4
C :with Coating
G :Low leakage current
S :with Chassis
SN :with Chassis & cover
Y :with Potentiometer
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL
LCA100S-3 LCA100S-5 LCA100S-12 LCA100S-15 LCA100S-24 LCA100S-24-H LCA100S-36 LCA100S-48
MAX OUTPUT WATTAGE[W]
DC OUTPUT
60
3V 20A
100
5V 20A
102
12V 8.5A
105
15V 7A
103.2
24V 4.3A
103.2
24V 4.3A
108
36V 3A
105.6
48V 2.2A
SPECIFICATIONS
MODEL
LCA100S-3 LCA100S-5 LCA100S-12 LCA100S-15 LCA100S-24 LCA100S-24-H LCA100S-36 LCA100S-48
AC85 - 132 1 or DC110 - 170
VOLTAGE[V]
CURRENT[A]
f
(
)
ACIN 100V 2.5typ Io=100%
FREQUENCY[Hz]
INPUT
47 - 440 or DC
LCA
EFFICIENCY[%]
74typ
79typ
83typ
84typ
85typ
85typ
24
85typ
85typ
(
)
INRUSH CURRENT[A] ACIN 100V 15typ Io=100%
(
,
,
)
LEAKAGE CURRENT[mA]
VOLTAGE[V]
0.5max 60Hz According to UL CSA and DEN-AN
3
5
12
15
24
36
48
3
*
(
)
CURRENT[A]
20
20
8.5
7
4.3
4.3 Peak 7
3
2.2
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
80max
140max
120max
160max
50max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
)
60max
96max
150max
120max
160max
150max
180max
240max
290max
96max
96max
144max
240max
150max
200max
250max
300max
360max
450max
144max
192max
300max
150max
200max
350max
400max
480max
600max
192max
120max
120max
160max
150max
180max
150max
180max
60max
150max
120max
160max
250max
280max
240max
290max
96max
1
1
1
1
*
*
*
*
0 to +50
C
RIPPLE[mVp-p]
-10 - 0
C
0 to +50
C
RIPPLE NOISE[mVp-p]
OUTPUT
-10 - 0
C
0 to +50
C
TEMPERATURE REGULATION[mV]
-10 to +50 60max
C
2
*
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
20max
( ,
200max ACIN 85V Io=100%
(
,
)
(
,
)
10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100%
(
,
,
,
,
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] 2.85 - 3.6
4.5 - 5.5
Fixed "Y"which can be adjusted the output is available as optional: 12 15 24 36 48V 10%
t
OUTPUT VOLTAGE SETTING[V]
11.5 - 12.5
14.4 - 15.6
23.0 - 25.0
23.0 - 25.0
34.5 - 37.5
46.0 - 50.0
xx
xx
(
)
OVERCURRENT PROTECTION Works over 105% of rating works over 105% of peak current at option -H and recovers automatically
OVERVOLTAGE PROTECTION 4.00 - 5.25V Works at 115 - 140% of rating
PROTECTION
CIRCUIT AND OPERATING INDICATION
Not provided
Not provided
Not provided
OTHERS
REMOTE SENSING
REMOTE ON/OFF
INPUT-OUTPUT
,
,
,
(
)
)
)
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , (
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
ISOLATION INPUT-FG
OUTPUT-FG
,
,
(
AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
,
,
,
(
(
) (
),
),
,
(
,
)
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60
20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
,
,
(
,
)
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75
20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
,
(
),
,
,
VIBRATION
10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
IMPACT
196.1m/s2 20G 11ms once each X Y and Z axis
),
(
,
,
SAFETY AND
NOISE
,
UL60950-1 CSA C22.2 No.60950-1 Complies with DEN-AN
AGENCY APPROVALS
CONDUCTED NOISE
CASE SIZE/WEIGHT
COOLING METHOD
,
Complies with FCC-B VCCI-B
REGULATIONS
( )
W H D
X X
(
)
62 32 222mm
/ 370g max without chassis and cover
X
X
OTHERS
Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN : RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C with the input voltage held constant at the rated input/output.
*3 Peak load for 20 sec. or less is acceptable(The average current has to be less than the rated current).
*4 Please contact us about safety approvals for the model with option.
*
Derating is required when operated with chassis and cover.
June 29, 2011
LCA-12
LCA100S
External view
LCA
Performance data
STATIC CHARACTERISTICS (LCA100S-5)
¡
RISE TIME & FALL TIME (LCA100S-5)
¡
OVERCURRENT CHARACTERISTICS (LCA100S-5)
¡
DERATING CURVE
¡
June 29, 2011
LCA-13
Ordering information
AC-DC Power Supplies Open Frame/Enclosed type
LC
A
150
S
-5
-O
6
LCA150S
1
2
3
4
5
1Series name
Recommended EMI/EMC Filter
NAC-06-472
R
2100/120V input
3Output wattage
4Single output
5Output voltage
6Optional *4
C :with Coating
G :Low leakage current
S :with Chassis
SN :with Chassis & cover
Y :with Potentiometer
High voltage pulse noise type : NAP series
Low leakage current type : NAM series
*The EMI/EMC Filter is recommended
*to connect with several devices.
MODEL
LCA150S-3 LCA150S-5 LCA150S-12 LCA150S-15 LCA150S-24 LCA150S-24-H LCA150S-36 LCA150S-48
MAX OUTPUT WATTAGE[W]
DC OUTPUT
90
3V 30A
150
5V 30A
150
12V 12.5A
150
15V 10A
151.2
24V 6.3A
151.2
24V 6.3A
151.2
36V 4.2A
153.6
48V 3.2A
SPECIFICATIONS
MODEL
LCA150S-3 LCA150S-5 LCA150S-12 LCA150S-15 LCA150S-24 LCA150S-24-H LCA150S-36 LCA150S-48
AC85 - 132 1 or DC110 - 170
VOLTAGE[V]
CURRENT[A]
f
(
)
ACIN 100V 3.6typ Io=100%
FREQUENCY[Hz]
INPUT
47 - 440 or DC
LCA
EFFICIENCY[%]
72typ
79typ
82typ
83typ
85typ
85typ
85typ
36
85typ
(
)
INRUSH CURRENT[A] ACIN 100V 15typ Io=100%
(
,
,
)
LEAKAGE CURRENT[mA]
VOLTAGE[V]
CURRENT[A]
0.5max 60Hz According to UL CSA and DEN-AN
3
5
12
12.5
15
10
24
6.3
24
(
48
3.2
3
*
)
30
30
6.3 Peak 10 4.2
LINE REGULATION[mV]
LOAD REGULATION[mV]
20max
40max
80max
140max
120max
160max
50max
20max
40max
80max
140max
120max
160max
50max
60max
20max
48max
100max
120max
160max
150max
180max
120max
150max
48max
)
60max
96max
150max
120max
160max
150max
180max
240max
290max
96max
96max
144max
192max
300max
150max
200max
350max
400max
480max
600max
192max
120max
120max
160max
150max
180max
150max
180max
60max
150max
120max
160max
150max
180max
240max
290max
96max
240max
150max
200max
250max
300max
360max
450max
144max
1
1
1
1
*
*
*
*
0 to +50
C
RIPPLE[mVp-p]
-10 - 0
C
0 to +50
C
RIPPLE NOISE[mVp-p]
OUTPUT
-10 - 0
C
0 to +50
C
TEMPERATURE REGULATION[mV]
-10 to +50 60max
C
2
*
DRIFT[mV]
START-UP TIME[ms]
HOLD-UP TIME[ms]
20max
( ,
200max ACIN 85V Io=100%
(
,
)
(
,
)
10typ ACIN 85V Io=100% 20typ ACIN 100V Io=100%
(
,
,
,
,
)
OUTPUT VOLTAGE ADJUSTMENT RANGE[V] 2.85 - 3.6
4.5 - 5.5
Fixed "Y"which can be adjusted the output is available as optional: 12 15 24 36 48V 10%
t
OUTPUT VOLTAGE SETTING[V]
11.5 - 12.5
14.4 - 15.6
23.0 - 25.0
23.0 - 25.0
34.5 - 37.5
46.0 - 50.0
xx
xx
(
)
OVERCURRENT PROTECTION Works over 105% of rating works over 105% of peak current at option -H and recovers automatically
OVERVOLTAGE PROTECTION 4.00 - 5.25V Works at 115 - 140% of rating
PROTECTION
CIRCUIT AND OPERATING INDICATION
Not provided
Not provided
Not provided
OTHERS
REMOTE SENSING
REMOTE ON/OFF
INPUT-OUTPUT
,
,
,
(
)
)
)
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
, , , (
AC2 000V 1minute Cutoff current = 10mA DC500V 50M min At Room Temperature
W
ISOLATION INPUT-FG
OUTPUT-FG
,
,
(
AC500V 1minute Cutoff current = 100mA DC500V 50M min At Room Temperature
W
,
,
,
(
(
) (
),
),
,
(
,
)
OPERATING TEMP. HUMID.AND ALTITUDE -10 to +60
20 - 90%RH Non condensing Refer to DERATING CURVE 3 000m 10 000feet max
C
,
,
(
,
)
STORAGE TEMP. HUMID.AND ALTITUDE -20 to +75
20 - 90%RH Non condensing 9 000m 30 000feet max
C
ENVIRONMENT
2
,
(
),
,
,
VIBRATION
10 - 55Hz 19.6m/s 2G 3minutes period 60minutes each along X Y and Z axis
IMPACT
196.1m/s2 20G 11ms once each X Y and Z axis
),
(
,
,
SAFETY AND
NOISE
,
UL60950-1 CSA C22.2 No.60950-1 Complies with DEN-AN
AGENCY APPROVALS
CONDUCTED NOISE
CASE SIZE/WEIGHT
COOLING METHOD
,
Complies with FCC-B VCCI-B
REGULATIONS
( )
W H D
X X
(
)
75 36 222mm
/ 550g max without chassis and cover
X
X
OTHERS
Convection
*1 Measured by 20MHz oscilloscope or Ripple-Noise meter(equivalent to KEISOKU-GIKEN : RM101).
*2 Drift is the change in DC output for an eight hour period after a half-hour warm-up at 25C with the input voltage held constant at the rated input/output.
*3 Peak load for 15 sec. or less is acceptable(The average current has to be less than the rated current).
*4 Please contact us about safety approvals for the model with option.
*
Derating is required when operated with chassis and cover.
June 29, 2011
LCA-14
LCA150S
External view
LCA
Performance data
STATIC CHARACTERISTICS (LCA150S-5)
¡
RISE TIME & FALL TIME (LCA150S-5)
¡
OVERCURRENT CHARACTERISTICS (LCA150S-5)
¡
DERATING CURVE
¡
June 29, 2011
LCA-15
相关型号: