TCF80RN [COOPER]
Low-Peak CUBEFuse With and Without Indication; 低峰CUBEFuse有或无指示型号: | TCF80RN |
厂家: | COOPER BUSSMANN, INC. |
描述: | Low-Peak CUBEFuse With and Without Indication |
文件: | 总2页 (文件大小:269K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
®
®
Low-Peak CUBEFuse With and Without Indication
Finger-Safe, Dual-Element, Time-Delay Class J Performance Fuse, 1-100A, 600Vac/300Vdc
Catalog Numbers (amp rating)
Indicating CUBEFuse
TCF6
TCF10
TCF35
TCF80
TCF15
TCF40
TCF90
TCF17-1/
TCF45
TCF100
2
TCF20
TCF50
TCF25
TCF60
TCF30
TCF70
Non-Indicating CUBEFuse
TCF1RN TCF3RN TCF6RN TCF10RN
TCF20RN TCF25RN TCF30RN TCF35RN
TCF50RN TCF60RN TCF70RN TCF80RN
TCF15RN TCF17-1/
TCF40RN TCF45RN
TCF90RN TCF100RN
2RN
Features and Product Benefits
• The world’s first finger-safe power fuse system.
70-100A Case Size
35-60A Case Size 1-30A Case Size
• Smallest footprint of any class fuse including Class J, CC, T and RK.
• Meets Class J time-delay electrical performance requirements.
Catalog Symbols: TCF_ Indicating fuse (6-100A)
TCF_RN Non-indicating fuse (1-100A)
Dual-Element, Time-Delay Fuse: 10 Seconds Minimum Operating Time at
500% Rated Current
Ampere Rating: 1 to 100A
Voltage Rating: 600Vac/300Vdc
• Available with and without open fuse indication to meet every customer
requirement.
• The indicating version features easyID™ open fuse technology for faster
troubleshooting and reduced downtime.
• Faster response to damaging faults to help reduce destructive thermal and
magnetic forces.
Interrupting Rating: 300kA RMS Sym. (UL)
200kA RMS Sym. (CSA)
100kA DC (UL & CSA)
• True dual-element fuse construction with a minimum of 10 seconds time-
delay at 500% of rating.
Agency Information:
• UL Listed Special Purpose Fuse: Guide JFHR, File E56412
• CSA Certified Fuse: Class 1422- 02, File 53787
• CE compliance for the European Union low voltage directive
• Long time-delay minimizes nuisance circuit openings due to temporary
overloads and transient surges.
• High interrupting rating to safely interrupt faults up to 300kA.
• No venting of arc or molten metal and gases during opening.
• Robust cycling and inrush current withstand.
Other Ratings/Specifications:
Watts Loss at rated current: TCF30: 3.99W
TCF60: 6.23W
• Low let-through currents under fault conditions.
TCF100: 9.51W
• Provides Type 2 “No Damage” protection for IEC motors starters when
properly sized.
• Easy selective coordination with any other Cooper Bussmann® Low-Peak®
Class L, J and RK1 fuse with simple 2:1 amp ration between upstream and
downstream fuses.
Operating and Storage Temperature Range: 14 to 149°F(-10 to 65°C)
Material Specifications:
• Case: Glass filled PES (Polyethersulfone)
• Terminals: Copper alloy
• Terminal plating: Electroless tin
• Indicator lens: PES (Polyethersulfone)
(indicating version only)
• Indicator: Energetic chemical
CUBEFuse Holders, Disconnects and Safety Switch
The CUBEfuse is used in the following Cooper Bussmann® products.
Carton Quantity and Weight
Amp
Carton Weight Per Carton
Rating
Qty.
12
12
6
lbs
kg
TCF1-30A
TCF35-60A
TCF70-100A
1.39
1.42
1.74
0.63
0.65
0.79
TCFH_N 100, 60 & 30A Holders.
CCP_CF 1-, 2- & 3-Pole
switched disconnects
Data Sheet 1157
CCPB 1-, 2- & 3-Pole disconnects for
the Quik-Spec™ Coordination
Panelboard. Data Sheet 1160
CF_ Quik-Spec™ Safety
Switch disconnect (optional
window). Data Sheet 1156
Data Sheet 9007
0309 BU-SB09230
Page 1 of 2
Data Sheet 9000
TCF_ and TCF_RN Dimensions – in (mm)
Fuse
Dimensions - in (mm)
D
Amps
A
B
C
E
F
G
1.88
(47.75)
0.75
(19.05)
1.00
(25.40)
0.23
(5.84)
0.04
(1.02)
0.63
(15.88)
0.27
(6.86)
1-15
17.5-20
25-30
35-40
45-50
60
1.88
(47.75)
0.75)
(19.05)
1.00
(25.40)
0.27
(6.86)
0.04
(1.02)
0.63
(15.88)
0.27
(6.86)
1.88
(47.75)
0.75
(19.05)
1.00
(25.40)
0.31
(7.94)
0.04
(1.02)
0.63
(15.88)
0.27
(6.86)
2.13
(54.10)
1.00
(25.40)
1.13
(28.58)
0.36
(9.14)
0.04
(1.02)
0.63
(15.88)
0.38
(9.65)
2.13
(54.10)
1.00
(25.40)
1.13
(28.58)
0.40
(10.16)
0.04
(1.02)
0.63
(15.88)
0.38
(9.65)
2.13
(54.10)
1.00
(25.40)
1.13
(28.58)
0.44
(11.11)
0.04
(1.02)
0.63
(15.88)
0.38
(9.65)
3.01
(76.45)
1.00
(25.40)
1.26
(32.00)
0.57
(14.4)
0.06
(1.60)
0.63
(15.88)
0.39
(9.93)
70-100
Time-Current Characteristic Curves–Average Melt
Current Limitation Curves
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information con-
tained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
© 2009 Cooper Bussmann
St. Louis, MO 63178
www.cooperbussmann.com
0309 BU-SB09230
Page 1 of 2