JM60060-2MW12 [COOPER]

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks;
JM60060-2MW12
型号: JM60060-2MW12
厂家: COOPER BUSSMANN, INC.    COOPER BUSSMANN, INC.
描述:

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks

文件: 总9页 (文件大小:4315K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
Effective June 2016  
Technical Data 10192  
Supersedes January 2014  
Up to 400 A Class J ferrule and  
knifeblade power distribution fuse blocks  
Features and benefits:  
•ꢀ  
Combination power distribution block and fuse  
block reduces wire connections and total panel  
components, using up to 65 percent less panel  
space and reducing installation time and labor  
by an average of 33 percent when compared  
with traditional fuse block/power distribution  
block solutions.  
•ꢀ  
A 200,000 amp withstand rating helps achieve  
a higher assembly short-circuit current rating  
(SCCR) for compliance with NEC® sections  
110.10, 409.110(4), 409.22, 440.4(B), 670.3(A)(4)  
and 670.5.  
30 and 60 amp modular ferrule  
blocks.  
100, 200 and 400 amp  
modular knifeblade blocks.  
•ꢀ  
Optional see-through cover enhances safety  
with IP20 finger-safe protection, lockout/tagout  
capability and open circuit indication.  
•ꢀ  
•ꢀ  
Available in 1-, 2- and 3-pole configurations to  
meet stocking requirements.  
To reduce inventory, assembly time and labor,  
modular single-pole blocks snap-together for  
tool-less assembly of multiple poles at point of  
use.  
Catalog symbols:  
•ꢀ  
Blocks rated up to 60 amps feature DIN-Rail  
and panel mount versatility, which allows one  
product to be used for multiple applications  
without incurring additional inventory cost.  
•ꢀ  
JM60030-_MW_  
•ꢀ  
JM60060-_MW_  
•ꢀ  
JM60100-_MW_  
•ꢀ  
JM60200-_MW_  
•ꢀ  
JM60400-_MW_  
Description:  
Bussmann® series Class J fuse block features  
power distribution capability.  
This patented design simplifies panel layouts  
and uses up to 65 percent less panel space.  
Additionally, it lowers inventory costs while  
reducing installation time and labor by an average  
of 33 percent.  
Furthermore, this design uses fewer wire  
connections, reducing watts loss and overall  
operating temperature of the panel.  
Technical Data 10192  
Class J ferrule and knifeblade power distribution fuse blocks  
Effective June 2016  
Operating and storage temperature range  
Specifications:  
•ꢀ  
Blocks: -40°C to +120°C  
Fuse class  
•ꢀ  
Covers:  
•ꢀ  
Class J  
•ꢀ Non-indicating -40°C to +120°C  
•ꢀ Indicating -20°C to +90°C  
Ratings  
•ꢀ  
Volts: 600 V  
Materials  
•ꢀ  
Amps: up to 400 A  
•ꢀ  
Base: Thermoplastic  
•ꢀ  
Withstand rating (SCCR): 200 kA Sym RMS  
•ꢀ  
Terminals: Tin-plated aluminum  
Agency information  
Conductors  
•ꢀ  
Blocks:  
•ꢀ UL® Listed E14853 – IZLT  
•ꢀ  
75°C/90°C Cu/Al (unless otherwise noted)  
•ꢀ CSA® Certified 47235 — 6225-01  
Accessories:  
•ꢀ  
Covers: UL Listed UL E58836 – JDVS  
•ꢀ  
Optional IP20 finger-safe covers in indicating and non-indicating  
•ꢀ  
RoHS compliant  
versions. Order one for each pole.  
•ꢀ  
Poles  
Universal marker labels for 30 and 60 amp blocks, Bussmann  
series catalog number TM26CB.  
•ꢀ  
1-, 2-, 3-pole  
•ꢀ  
DIN-Rail end stops for blocks rated up to 60 A, Bussmann series  
catalog numbers BRKT-ND or BRKT-NDSCRW2.  
Mounting  
•ꢀ  
30 and 60 amp blocks DIN-Rail and panel mount  
Recommended fuses (order separately)  
•ꢀ  
100, 200 and 400 amp blocks panel mount only  
Description  
Amps  
Data sheet no.  
1006  
Flammability ratings  
up to 60  
70 to 600  
up to 60  
70 to 600  
up to 600  
Ultimate protection Low-Peak™ LPJ  
time-delay fuses  
•ꢀ  
Blocks: UL 94V0, self-extinguishing  
1007  
•ꢀ  
Covers: UL 94HB, self-extinguishing  
1026  
Advanced protection Limitron™ JKS  
fast-acting fuses  
1027  
High speed Class J DFJ drive fuses  
1048  
Finger grips on cover  
for easy removal  
Lockout/tagout feature  
improves safety  
Optional see-through, snap-on  
cover for easy visual inspection  
Available two-port lineside lug  
for easy daisy-chain wiring  
configuration. See catalog  
number table for applicable  
catalog numbers.  
Probe holes for easy testing  
without removing cover  
Vent slots improve cooling  
(no fuse derating necessary)  
Standard phase barriers  
for additional safety  
Optional open fuse indication  
speeds troubleshooting  
Tool-less interlocking modular design  
for easy point-of-use assembly  
DIN-Rail or panel mounting on each  
pole provides installation flexibility  
(DIN-Rail mounting applies to 30  
and 60 A blocks only)  
Marker label provision  
for easy circuit  
identification (applies to  
30 and 60 A blocks only)  
Multi-port loadside lug  
for power distribution to  
multiple branch circuit  
connections  
Ports on power distribution lugs rated  
for dual-wire application, increasing the  
number of branch circuit connections  
(see catalog number table for details)  
2
Eaton.com/bussmannseries  
Class J ferrule and knifeblade power distribution fuse blocks  
Technical Data 10192  
Effective June 2016  
Catalog numbers:  
Lineside (conductors per port)  
Fuse  
Loadside (conductors per port)  
Ports/ Torque  
pole AWG  
Cu (1) 8  
Optional  
covers*  
amp  
range  
Ports/  
pole  
N•m  
(lb-in)  
N•m  
(lb-in)  
Catalog no.  
Poles Conductors  
Torque AWG  
Conductors  
JM60030-1MW14  
JM60030-2MW14  
1
2-3  
4-6  
8
5.6 (50)  
5.1 (45)  
4.5 (40)  
4.0 (35)  
5.6 (50)  
4.5 (40)  
3.4 (30)  
Cu (1) 8-14  
2
Cu (1) 10-14 2.8 (25)  
Cu (2) 12-14 3.4 (30)  
Cu 2-14  
Al 2-8  
Cu (2) 12-14***  
Al (1) 8 Str  
N/A  
up to 30  
1
4
1
4
4
4
Al (1) 10 Sol  
JM60030-3MW14  
3
10-14  
2-4  
6-10  
Al (1) 8-10  
2-3  
3.4 (30)  
5.6 (50)  
5.1 (45)  
4.5 (40)  
4.0 (35)  
3.4 (30)  
JM60060-1MW12†  
JM60060-2MW12†  
1
2
4-6  
Cu 2-14  
Al 2-8  
Cu 2-14  
Al 2-8  
2
1
2
1
8
JM60060-3MW12†  
3
12-14  
1.7 (15)  
10-14  
Cu (1) 8  
JM60060-1MW14†  
JM60060-2MW14†  
1
2
2-3  
4-6  
8
5.6 (50)  
5.1 (45)  
4.5 (40)  
4.0 (35)  
5.6 (50)  
4.5 (40)  
Cu (1) 8-14  
Cu (1) 10-14 2.8 (25)  
Cu (2) 12-14 3.4 (30)  
CVR-J-60060  
Cu 2-14  
Al 2-8  
Cu (2) 12-14***  
Al (1) 8 Str  
35 - 60  
CVRI-J-60060**  
Al (1) 10 Sol  
JM60060-3MW14†  
3
10-14  
2-4  
6-10  
Al (1) 8-10  
Cu (1) 8  
3.4 (30)  
3.4 (30)  
JM60060-1MW24  
JM60060-2MW24  
1
2
Cu (1) 8-14  
Cu (1) 10-14 2.8 (25)  
Cu (2) 12-14 3.4 (30)  
Cu 2-14  
Al 2-8  
Cu (2) 12-14***  
Al (1) 8 Str  
Al (1) 10 Sol  
JM60060-3MW24  
3
12-14  
1.7 (15)  
Al (1) 8-10  
4-6  
3.4 (30)  
4.0 (35)  
2.8 (25)  
2.3 (20)  
3.4 (30)  
4.0 (35)  
2.8 (25)  
2.3 (20)  
3.4 (30)  
JM60100-1MW14  
JM60100-2MW14  
1
2
1/0-3; Cu (2) 4-6 5.6 (50)  
4-6; Cu (2) 8 5.0 (45)  
8; Cu (2) 10-14 4.5 (40)  
Cu (1) 4-14  
Al (1) 4-8  
Cu (2) 10-14***  
8
CVR-J-60100-M  
Cu 1/0-14  
Al 1/0-12  
70 - 100  
110-200  
CVRI-J-60100-M**  
Cu 10-14  
(2) 10-14  
4-6  
JM60100-3MW14  
3
10-14  
4.0 (35)  
JM60200-1MW16  
JM60200-2MW16  
1
2
250kcmil-1  
42 (375)  
Cu (1) 4-14  
Al (1) 4-8  
Cu (2) 10-14***  
8
Cu/Al (1) 250kcmil-6  
Cu (2) 2-6  
CVR-J-60200-M  
1
1
6
6
CVRI-J-60200-M**  
10-14  
(2) 10-14  
JM60200-3MW16  
3
2-6  
31 (275)  
57 (500)  
51 (450)  
600kcmil  
JM60400-1MW16  
JM60400-2MW16  
1
2
2-3  
5.6 (50)  
4-6  
8
(2) 8  
5.0 (45)  
4.5 (40)  
4.5 (40)  
Cu (1) 2-14  
Al (1) 2-8  
500kcmil-4  
Cu/Al (1) 600kcmil-4  
Cu/Al (2) 3/0-4  
Cu (2) 8-14***  
JM60400-3MW16  
3
57 (500)  
34 (300)  
10-14  
4.0 (35)  
Cu (2) 3/0-4  
Al (2) (3/0-4  
CVR-J-60400-M  
CVRI-J-60400-M**  
225-400  
(2) 10-14  
4.5 (40)  
JM60400-1MW26  
JM60400-2MW26  
1
2
2-3  
4-6  
8
5.6 (50)  
5.0 (45)  
4.5 (40)  
350kcmil-1  
2-6  
42 (375)  
31 (275)  
Cu (1) 2-14  
Al (1) 2-8  
Cu (2) 8-14***  
(2) 8  
4.5 (40)  
4.0 (35)  
4.5 (40)  
Cu/Al 350kcmil-6  
2
6
JM60400-3MW26  
3
10-14  
(2) 10-14  
*
Order one cover per pole.  
** With open fuse indication. 90 V minimum and closed circuit required for illumination.  
*** Dual wire rated lugs with same wire size and stranding.  
Rated for 75°C Cu/Al conductors. Conductors with higher ratigns may be used with appropriate derating.  
Eaton.com/bussmannseries  
3
Technical Data 10192  
Class J ferrule and knifeblade power distribution fuse blocks  
Effective June 2016  
30 A dimensions — mm (in)  
Catalog nos. JM60030-(poles)MW14 — One port in, four ports out (covers not available)  
27.7  
1.09  
17.2  
.68  
12.4  
.49  
R2.9  
.11  
R2.5  
.10  
89.2  
3.51  
6.2  
.24  
87.0  
3.43  
29.0  
1.14  
56.7  
2.23  
84.3  
3.32  
6.5  
.26  
58.2  
2.29  
46.2  
1.82  
16.2  
.64  
30.2  
1.19  
4
Eaton.com/bussmannseries  
Class J ferrule and knifeblade power distribution fuse blocks  
Technical Data 10192  
Effective June 2016  
60 A dmensions — mm (in)  
Catalog nos. JM60060-(poles)MW12 Two ports in, one port out  
25  
.98  
12.7  
.50  
31.3  
1.23  
19.8  
.78  
9
.35  
9
.35  
R2.9  
.11  
6.5  
.26  
5.3  
.21  
R2.5  
.10  
93.7  
3.69  
38.9  
1.53  
76.6  
3.02  
114.3  
4.50  
65.3  
2.57  
53.3  
2.10  
18.3  
.72  
15.8  
.62  
37.7  
1.48  
With optional cover, see catalog number table on page three for available versions  
119 [4.7]  
Eaton.com/bussmannseries  
5
Technical Data 10192  
Class J ferrule and knifeblade power distribution fuse blocks  
Effective June 2016  
60 A dimensions — mm (in)  
Catalog nos. JM60060-(poles)MW14 — One port in, four ports out  
37.7  
1.48  
18.3  
.72  
9
.35  
9
.35  
19.8  
.78  
6.5  
.26  
R2.9  
.11  
95.1  
3.74  
5.3  
.21  
R2.5  
.10  
93.7  
3.69  
76.6  
3.02  
114.3  
4.50  
38.9  
1.53  
6.5  
.26  
65.3  
2.57  
53.3  
2.10  
15.8  
.62  
31.3  
1.23  
8
.31  
29.7  
1.17  
With optional cover, see catalog number table on page three for available versions  
119 [4.7]  
6
Eaton.com/bussmannseries  
Class J ferrule and knifeblade power distribution fuse blocks  
Technical Data 10192  
Effective June 2016  
60 A dimensions — mm (in)  
Catalog nos. JM60060-(poles)MW24 Two ports in, four ports out  
25  
.98  
12.7  
.50  
31.3  
1.23  
9
.35  
9
.35  
19.8  
.78  
R2.9  
.11  
6.5  
.26  
95.1  
3.74  
5.3  
.21  
R2.5  
.10  
93.7  
3.69  
76.6  
3.02  
38.9  
1.53  
114.3  
4.50  
6.5  
.26  
65.3  
2.57  
53.3  
2.10  
31.3  
1.23  
15.8  
.62  
8
.31  
29.7  
1.17  
With optional cover, see catalog number table on page three for available versions  
119 [4.7]  
Eaton.com/bussmannseries  
7
Technical Data 10192  
Class J ferrule and knifeblade power distribution fuse blocks  
Effective June 2016  
100, 200 and 400 A dimensions — mm (in)  
Catalog nos. JM60100-(poles)MW14 (100 A), JM60200-(poles)MW16 (200 A) and JM60400-(poles)MW16/26 (400 A)  
C
B
A
100 A block  
mounting holes  
ØN  
ØO  
ØN  
ØO  
M
M
D
L
L
J
K
J
F
I
E
H
G
Block size  
A
B
C
D
E
F
G
H
I
J
K
L
M
ØN  
0.4  
9
ØO  
0.5  
13  
2.0  
in  
4.0  
6.0  
153  
8.0  
203  
10.6  
268  
5.5  
139  
6.8  
172  
8.0  
202  
5.5  
139  
6.8  
172  
8.0  
202  
2.8  
72  
2.2  
55  
6.0  
152  
7. 3  
2.8  
72  
3.8  
97  
4.8  
121  
0.9  
22  
1.4  
35  
2.0  
50  
2.0  
51  
2.6  
67  
3.5  
88  
0.4  
10  
0.3  
8
1.1  
29  
1.3  
32  
1.6  
41  
100 A  
mm  
in  
51  
102  
5.3  
134  
7. 0  
2.6  
3.8  
97  
3.0  
75  
0.4  
9
0.7  
19  
200 A  
400 A  
mm  
in  
67  
186  
8.7  
220  
3.5  
4.8  
121  
4.1  
105  
0.3  
8
0.4  
9
0.7  
19  
mm  
88  
177  
8
Eaton.com/bussmannseries  
Technical Data 10192  
Class J ferrule and knifeblade power distribution fuse blocks  
Effective June 2016  
Installing/removing covers on 30 to 400 amp blocks  
For larger conductors, trim center tab  
at notch as show in detail A.  
Install cover:  
Position cover  
over block and  
push straight  
down until it  
snaps/clicks  
into place.  
Trim tab  
here  
A
Open cover:  
Using both  
outside handles,  
pull straight up.  
Detail A  
Installing 30 and 60 amp blocks on a 35mm DIN-Rail  
2. Rotate and push block down  
to deflect rail clips.  
1. Place one edge of DIN-Rail into  
rail clips on one side of the block.  
3. Continue rotating block  
until remaining rail clips  
snap into place.  
The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are  
by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the  
end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit  
distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once  
a product has been selected, it should be tested by the user in all possible applications.  
Eaton  
1000 Eaton Boulevard  
Cleveland, OH 44122  
For Eatons Bussmann series  
Eaton.com  
product information,  
call 1-855-287-7626 or visit:  
Eaton.com/bussmannseries  
Eaton, Bussmann, Low-Peak and Limitron are  
valuable trademarks of Eaton in the U.S. and  
other countries. You are not permitted to use  
the Eaton trademarks without prior written  
Bussmann Division  
114 Old State Road  
Ellisville, MO 63021  
United States  
consent of Eaton.  
Eaton.com/bussmannseries  
CSA is a registered trademark of the Canadian  
Standards Group.  
NEC is a registered trademark of the National  
Fire Protection Association, Inc.  
UL is a registered trademark of the  
Underwriters Laboratories, Inc.  
Follow us on social media to get the  
latest product and support information.  
© 2016 Eaton  
All Rights Reserved  
Printed in USA  
Publication No. 10192 — BU-MC16067  
June 2016  
9
Eaton.com/bussmannseries  

相关型号:

JM60060-2MW14

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
COOPER

JM60060-2MW24

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
COOPER

JM60060-3CHR

Class J modular ferrule and knifeblade fuse blocks
ETC

JM60060-3CR

Class J modular ferrule and knifeblade fuse blocks
ETC

JM60060-3MW12

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
COOPER

JM60060-3MW14

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
COOPER

JM60060-3MW24

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
COOPER

JM60100-1CR

Industrys fi rst modular fuse block simplifi es design and enhances safety
COOPER

JM60100-1MW14

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
COOPER

JM60100-2CR

Industrys fi rst modular fuse block simplifi es design and enhances safety
COOPER

JM60100-2MW14

Up to 400 A Class J ferrule and knifeblade power distribution fuse blocks
COOPER

JM60100-3CR

Industrys fi rst modular fuse block simplifi es design and enhances safety
COOPER