VFD 300% Gnd, 3C+IG #12 Str TC, XLPO Ins+PVC Grd, OS+TC Brd, Blk
LSZH-TS Jkt, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable
Marine Approved
Product Description
Belden 300% Ground Flexible VFD, 3 Conductor 12AWG (65x30) Tinned Copper, XLPO Insulation M4 Color Code+PVC Insulated Ground, Overall
Beldfoil®+Tinned Copper Braid(85%) Shield, Black LSZH-TS Outer Jacket, 600V TC-ER 90C Dry/Wet 1000V Flexible Motor Supply Cable Marine Approved
SUN RES OIL RES II
Technical Specifications
Product Overview
Suitable Applications:
AC Motor drives, VFD, Variable Frequency drives
Physical Characteristics (Overall)
Conductor
Element
AWG Stranding
Material
No. of Conductors
12
65x30
65x30
TC - Tinned Copper
TC - Tinned Copper
3
Ground Wire 12
Conductor Count:
3
Insulation
Material
Nominal Wall Thickness
XLPE - Cross Linked Polyethylene 0.045 in
XLP - Cross Linked Polyolefin
Color Chart
Number
Color
1
2
3
4
Black and Numbered 1
Black and Numbered 2
Black and Numbered 3
Green/Yellow
Outer Shield Material
Type Layer Material
Material Trade Name Coverage [%] Drainwire Material Drainwire AWG Drainwire Construction n x D
Tape
Braid
1
2
Aluminum/Polyester Duofoil®
TC - Tinned Copper
100 %
85 %
TC - Tinned Copper 12
65x30 mm
Outer Jacket Material
Material Nominal Diameter Nominal Wall Thickness
Haloarrest Xlink 2 0.63 in
Electrical Characteristics
Conductor DCR
0.073 in
Nominal Conductor DCR
1.6 Ohm/1000ft
Capacitance
Nom. Capacitance Conductor to Conductor Nom. Capacitance Conductor to Other Conductor to Shield
26 pF/ft
47 pF/ft
Inductance
Nominal Inductance
0.197 µH/ft
Impedance
Nominal Characteristic Impedance
71 Ohm
Current
Max. Recommended Current [A]
30 Amps per conductor @ 30°C (per NEC)
Voltage
Description
UL Voltage Rating
Voltage Rating [V]
CSA AWM I/II A/B 1000 V RMS (Flexible Motor Supply Cable) 1000 V RMS
600 V RMS (Type TC)
Temperature Range
UL Temp Rating:
Wet Temp Range:
Dry Temp Range:
90°C Dry, 90°C Wet
-40°C To +90 °C
-40°C To +90 °C
Mechanical Characteristics
Bulk Cable Weight:
250 lbs/1000ft
Max Recommended Pulling Tension: 336 lbs
Min Bend Radius/Minor Axis:
6.3 in
Standards
NEC/(UL) Specification:
CPR Euroclass:
TC-ER, Unlisted Singles, WTTC
Fca
Applicable Environmental and Other Programs
EU Directive Compliance:
EU CE Mark:
EU Directive 2003/11/EC (BFR)
Yes
Yes
Yes
CA Prop 65 (CJ for Wire & Cable):
MII Order #39 (China RoHS):
Suitability
Suitability - Burial:
Yes
Yes
Yes
Yes
Yes
Suitability - Indoor:
Suitability - Oil Resistance:
Suitability - Outdoor:
Suitability - Sunlight Resistance:
Flammability, LS0H, Toxicity Testing
UL Flammability:
CSA Flammability:
IEEE Flammability:
UL voltage rating:
UL1685 UL Loading
FT4
1202
1000 V RMS (Flexible Motor Supply Cable)
Part Number
Variants
Item #
Color
UPC
Length Footnote
29502X 0105000 Black 612825136842 5,000 ft C Z
Footnote:
Footnote:
C - CRATE REEL PUT-UP.
Z - FINAL PUT-UP MAY VARY (= OR -) 10% FOR SPOOLS OR REELS AND (+ OR -) 5% FOR UNREEL CARTONS FROM LENGTH SHOWN.
History
Update and Revision:
Revision Number: 0.198 Revision Date: 09-10-2019
© 2019 Belden, Inc
All Rights Reserved.
Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without
notice, and the listing of such information and specifications does not ensure product availability.
Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages
(including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract,
negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein.
All sales of Belden products are subject to Belden's standard terms and conditions of sale.
Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief
at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product
Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and
regulations based on their individual usage of the product.
相关型号:
©2020 ICPDF网 联系我们和版权申明