MA0.40U [ALTECH]

Three Phase Adjustable Trip Miniature Circuit Breakers/ Manual Motor Controllers; 三相可调跳变微型断路器/手动电机控制器
MA0.40U
型号: MA0.40U
厂家: ALTECH CORPORATION    ALTECH CORPORATION
描述:

Three Phase Adjustable Trip Miniature Circuit Breakers/ Manual Motor Controllers
三相可调跳变微型断路器/手动电机控制器

断路器 电机 控制器
文件: 总3页 (文件大小:218K)
中文:  中文翻译
下载:  下载PDF数据表文档文件
MA- Series  
Three Phase Adjustable Trip  
Miniature Circuit Breakers/  
Manual Motor Controllers  
UL508 listed  
E137938  
CAN/CSA-C22.2 No.14 certified  
The MA was designed to handle the high  
inrush loads of 3 phase transformers,  
power supplies, motors, etc. The MA  
protects wiring and equipment from  
damage caused by the three major  
classes of over-current, yet greatly reduc-  
es the number of nuisance trips in high  
Type Designation  
MA RT  
starting and inrush current circuits.  
__ __  
__  
__  
An IEC device with excellent ratings under  
a UL listing at 480Y/277V (including group  
ratings) and at 500V under international  
standards, the Altech/ABL Sursum MA  
provides short and long term cost effective  
circuit protection for USA and/or export  
applications. The short term advantages  
include: (1) adjustable thermal trip allows  
finalization of initial designs before  
procurement of the load equipment is  
complete; (2) snap-on mounting for readily  
available, internationally standardized DIN  
Rail saves panel layout design time as well  
as installation and change labor; (3) large  
cage-clamp terminals with screws suitable  
to power screwdrivers, simplifies and  
speeds wiring; (4) convenient switched  
disconnect during factory testing and/or  
initial start-up saves time and aggravation.  
The key long term advantage is customer  
satisfaction and proven over-current pro-  
tection of wiring and equipment (and the  
lack of rework/repair costs).  
(a) (b) (c) (d)  
(a) = MA - Manual Motor Controller  
(b) = Rated Current  
(c) = U - US Housing  
(d) = Blank - Standard Terminal  
RT - Ring-tongue Terminal  
Voltage Rating  
480Y/277VAC  
0.16A-2.5A: 42kA; 4.0A-16A: 14kA; 20A-40A: 10kA  
AIC (Interrupt Capacity)  
Standard Short Circuit Withstand Rating 0.16A-2.5A: 42kA; 4.0A-16A: 14kA  
(UL/CSA Ratings)  
Group Short Circuit Ratings  
(UL/CSA Ratings)  
see above  
Typical Life  
6000 on/off operations with 2xRC  
25°C, +0°, -5° (77°F, +0° -9°)  
1/450g (1.0 lb.)  
Calibration Temperature  
Standard Pack and Weight  
Terminal Size Acceptability  
Top/Bottom: 18-3 AWG  
GROUP SHORT  
CIRCUIT RATING  
AT 480VAC  
3Ø HORSEPOWER RATINGS AT NOMINAL LINE VOLTAGE  
(See Note for HEA Definition)  
Type and  
Rated  
Current  
FLA Dial  
Adjustment  
Markings  
a
460-480V  
HP (HEA)  
110-120V  
HP (HEA)  
200V  
208V  
220-240V  
HP (HEA)  
(and BCP size)  
Cat. No.  
HP (HEA) HP (HEA)  
MA0.16U  
MA0.25U  
MA0.40U  
MA0.63U  
MA1.0U  
MA1.6U  
MA2.5U  
MA4.0U  
MA6.3U  
MA10U  
MA16U  
MA20U  
MA25U  
MA32U  
MA40U  
15.901U  
15.902U  
15.903U  
15.904U  
15.905U  
15.906U  
15.907U  
15.908U  
15.909U  
15.910U  
15.911U  
15.912U  
15.913U  
15.914U  
15.915U  
0.1/ 0.12/0.14/0.16  
0.16/0.19/0.22/0.25  
0.25/0.30/0.35/0.40  
0.40/0.48/0.56/0.63  
0.63/0.75/0.87/1.0  
1.0/1.2/1.4/1.6  
1.6/1.9/2.2/2.5  
2.5/3.0/3.5/4.0  
4.0/4.8/5.6/6.3  
6.3/7.5/8.7/10  
42kARMS  
Through MA2.5U, ampere rated for motor circuits having a full-  
load-amperage (FLA) not exceeding the MA’s general purpose  
rated current (RC, equals maximum dial setting) and a locked  
rotor current not exceeding 6 times the MA’s RC.  
symmetrical  
(max. 1200A  
MCCB  
or RK5)  
14kARMS  
1/2 (4.0) 3/4 (3.2)  
3/4 (5.6) 11/2 (6.0)  
3/4  
11/2  
2
(3.1)  
(5.7)  
1
(3.6)  
2
3
5
(3.42)  
(4.8)  
(7.6)  
symmetrical  
(max. 350A  
MCCB  
11/2 (5.2)  
1
2
3
3
5
5
(7.2)  
(13.6)  
(19.2)  
(19.2)  
2
3
5
5
(7.8)  
(11.0)  
(17.5)  
(7.5)  
3
5
5
(9.6)  
10/12/14/16  
or RK5)  
3
(10.6)  
(16.7)  
(15.2) 10 (14.0)  
(15.2) 10 (14.0)  
10kARMS  
16/17/18.5/20  
5
symmetrical  
(max. 350A  
MCCB  
20/21.5/23/25  
(17.5) 71/2 (24.2) 71/2 (22.0) 15 (21.0)  
25/27/30/32  
(30.4) 71/2 (25.0) 71/2 (24.2)  
(30.4) 10 (32.0) 10 (31.0)  
10 (28.0) 20 (27.0)  
10 (28.0) 25 (34.0)  
32/34/37/40  
or RK5)  
Note: HEA - Horsepower Equivalent Amperes, the nominal amperage assigned to standard motor horsepower ratings in design guide tables such as  
NFPA-70 Tables 430-248, 430-249, 430-250; UL1077 Table 16.2; CSA - C22.2 No. 235-M89 Tables 44 and 45; CSA-C22.2 No. 14-M91 Table 19, etc. Multiply  
HEA values (in parenthesis) by 1.1 if power factor is 90%, and by 1.2 if power factor is 80%.  
a
The standard-circuit short-circuit rating is 14kA for all types. Group ratings can be used in a standard circuit (e.g., MA1.0U at 42kA), but a higher  
standard rating cannot be used in a group circuit (e.g., MA40U at 14kA only in standard circuit.)  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
3 2  
DIMENSIONS  
44mm (1.73 in.)  
120  
37.5mm (1.48 in.)  
25.5mm (1.0 in.)  
6mm (.24 in.)  
60  
40  
MA0.16U-MA16U  
MA 3 Phase Controller  
Thermal Overload (B, C, D)  
“Must Trip” Current = 115% of Dial Setting  
“Must Not Trip” > 1 hr = 105% of Dial Setting  
20  
7mm  
(.28 in.)  
10  
6
4
2
1
40  
20  
10  
6
4
2
1
0.6  
0.4  
Magnetic Trip  
Nominal 1100% of Rated Current  
0.2  
0.1  
7mm (.28 in.)  
1 1.15 1.5 2 2.3  
3
4 5 6 6.9 8 10 12 16 19  
Multiple of Dial Setting (Thermal)  
17.5mm (1.28 in.)  
Multiple of Rated Current (Magnetic Trip)  
Rated Current = Max. Dial Setting  
30.5mm  
(1.20 in.)  
3mm  
(.12 in.)  
120  
44mm (1.73 in.)  
60  
40  
MA20U-MA40U  
MA 3 Phase Controller  
Thermal Overload (B, C, D)  
“Must Trip” Current = 115% of Dial Setting  
“Must Not Trip” > 1 hr = 105% of Dial Setting  
68mm (2.68 in.)  
20  
10  
6
4
1
3
5
2
L1  
L2  
L3  
1
40  
20  
10  
6
4
12A  
10A  
14A  
16A  
40°C  
20°C  
MA.16  
VDE 0660 AC-3  
500V 50-60Mz  
2
1
ABL SURSUM  
0.6  
0.4  
T1  
T2  
T3  
Magnetic Trip  
2
4
6
Nominal 1100% of Rated Current  
0.2  
0.1  
11.15 1.5 2 2.3  
3
4
5
6 6.9 8 10 12 15  
12.5  
52.5mm (2.07 in.)  
Multiple of Dial Setting (Thermal)  
Multiple of Rated Current (Magnetic Trip)  
Rated Current = Max. Dial Setting  
MA/USA Manual Motor Controller  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
3 3  
Accessories can be factory or field mounted on V-EA and MA manual motor controllers for enhanced  
control and monitoring capabilities. Field mounting kits include all necessary parts and instructions.  
Accessories can be gang mounted on a single controller (the Auxiliary Switch in the outside position).  
V-EA and MA  
Circuit Breaker The mounting arrangement links the internal latch-pins for the tripping mechanisms, ensuring simul-  
taneous trips. Handles are linked to simplify manual resetting.  
Accessories  
FA - Shunt Trip  
UL508 listed  
Trip/Coil  
E137938  
Type/  
Voltage  
Max. Coil  
Current  
Cat. No.  
AC or DC  
Approvals  
U
L
FA12U  
FA24U  
FA48U  
FA110U  
12V  
24V  
1.3A  
0.6A  
U
L
U
L
48-72V  
110V/220V  
0.2A  
U
L
0.25A/0.5A  
Std.Pk.: 1  
Unit Weight: 120 grams (0.27 lb.)  
Width: 17.5mm (.689in.)  
UA - Undervoltage Trip  
Type/  
Line Voltage  
60Hz*  
Cat. No.  
UA120  
UA240  
UA277  
UA415  
UA480  
120VAC  
240VAC  
277VAC  
415VAC  
480VAC  
Std.Pk.: 1  
Unit Weight: 70 grams (0.16 lb.)  
Width: 17.5mm (.689in.)  
H - Auxiliary Switch  
Type/  
Cat. No.  
Contact  
Rating  
Wire  
Size  
Approvals  
For Use With:  
4mm2 (12 AWG)  
U
L
H11U  
10A / 220V AC  
V-EA, MA  
3A / 110V DC or pulsed  
1A / 220V DC or pulsed  
Std. Pk.: 1  
Unit Weight: 45 grams (0.12 lb.)  
Width: 9mm (.354in.)  
Lock-out **  
Cat. No. EASS  
Cooling Spacer  
Cat. No. 15.960  
Prevent inadvertent  
resetting of the V-EA or MA  
during maintenance.  
Fits 1/4” pad lock.  
*
Please consult Altech for your 50Hz application needs.  
**  
V-EA and MA can also be locked in the on and off position by simply using a common lead or meter seal, which gets fed through the hole in the handle and  
a corresponding hole in the housing.  
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490 • www.altechcorp.com  
3 4  

相关型号:

MA0.63U

Three Phase Adjustable Trip Miniature Circuit Breakers/ Manual Motor Controllers
ALTECH

MA000040544

Material Content Data Sheet
INFINEON

MA000040744

Material Content Data Sheet
INFINEON

MA000041325

Material Content Data Sheet
INFINEON

MA000041366

Material Content Data Sheet
INFINEON

MA000043159

Material Content Data Sheet
INFINEON

MA000043164

Material Content Data Sheet
INFINEON

MA000043592

Material Content Data Sheet
INFINEON

MA000043931

Material Content Data Sheet
INFINEON

MA000044377

Material Content Data Sheet
INFINEON

MA000044883

Material Content Data Sheet
INFINEON

MA000044974

Material Content Data Sheet
INFINEON