700-SE10GZZ05 [ALLEN-BRADLEY]
Solid-State Relays; 固态继电器型号: | 700-SE10GZZ05 |
厂家: | Allen-Bradley |
描述: | Solid-State Relays |
文件: | 总5页 (文件大小:463K) |
中文: | 中文翻译 | 下载: | 下载PDF数据表文档文件 |
Bulletin 700-SE
Solid-State Relays
Overview/Product Selection
Table Of Contents
Bulletin 700-SE
Product Selection . . . . . . . .42
Accessories. . . . . . . . . . . . .43
Specifications . . . . . . . . . . .44
Approximate
•
•
•
•
•
•
20 A (resistive) Max. Continuous Load (Output) Current with Heat Sink
264V AC Max. Load Voltage Range
5,12, or 24V DC Control/Input Voltage
Built-in Varistor Helps Absorb Most Electrical Surges
Low Profile (Flat Pack) Design
Quick-Connect #110 Input and #250 Output Terminals
Dimensions . . . . . . . . . . . . .46
Factory-
stocked
Item
(single
pack)
Input-to-
Output
Isolation
Method
Rated Output (Load)
Max. Current and
Voltage Range ➊
ZeroCross
Function
LED
Indicator
Rated Input
Control Voltage
Cat. No.
5V DC
12V DC
24V DC
5V DC
700-SE05GZZ05
700-SE05GZZ12
700-SE05GZZ24
700-SE10GZZ05
700-SE10GZZ12
700-SE10GZZ24
700-SE20GZZ05
700-SE20GZZ12
700-SE20GZZ24
700-SE05GNZ05
700-SE05GNZ12
700-SE05GNZ24
700-SE10GNZ05
700-SE10GNZ12
700-SE10GNZ24
700-SE20GNZ05
700-SE20GNZ12
700-SE20GNZ24
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
5 A at 100…240V AC
10 A at 100…240V AC
20 A at 100…240V AC
5 A at 100…240V AC
10 A at 100…240V AC
20 A at 100…240V AC
Yes
12V DC
24V DC
5V DC
12V DC
24V DC
5V DC
Phototriac
No
12V DC
24V DC
5V DC
No
12V DC
24V DC
5V DC
12V DC
24V DC
➊ Maximum load current when mounted on a heat sink.
42
Bulletin 700-SE
Solid-State Relays
Accessories
Description
Pkg. Quantity
Cat. No.
Factory-stocked Item
1
700-S10
➊
Heat Sink — Panel or DIN Rail Mount ➊
Cat No. 700-S10
1
700-S20
➊
Heat Sink — Panel or DIN Rail Mount ➊
Cat No. 700-S20
DIN Rail Mounting Pack
Standard 35 x 7.5 mm DIN Rail, 1 meter long,
10 rails per package. Order must be for 10
rails or multiples of 10.
10
199-DR1
➊
Cat No. 199-DR1
➊ Refer to "Load Current Vs. Ambient Temperature Characteristics" page 45 for information about how to select the correct size of heat sink for your application
( cat. no. 700-S10, 700-S20).
43
Bulletin 700-SE
Solid-State Relays
Specifications
Control/Input Ratings ➊
Input Impedance
Control Voltage Levels
Rated
Control
Voltage
Operating Control
Voltage Range
Without Zero
Cross
Cat. No.
With Zero
Cross Function
Pick-up Voltage
Drop-out Voltage
Function
700-SE_ _ _Z05
700-SE_ _ _Z12
700-SE_ _ _Z24
5V DC
12V DC
24V DC
4…6V DC
250 Ω ± 20%
600 Ω ± 20%
300 Ω ± 20%
800 Ω ± 20%
4V DC max.
9.6V DC max.
19.2V DC max.
9.6…14.4V DC
19.2…28.8V DC
1V DC min.
1.6k Ω ± 20%
Load/Output Ratings
Applicable Load
Continuous Load Current (Resistive)
With Heat Sink ➊ Without Heat Sink ➊
Min. Max.
Cat. No.
Max. Inrush Current
Rated Load Voltage
Load Voltage Range
➊
Min.
Max.
5 A
60 A (@50/60 Hz,
1 cycle)
700-SE05…
700-SE10…
700-SE20…
0.1 A
0.1 A
0.1 A
5 A
10 A
20 A
0.1 A
150 A (@50/60 Hz,
1 cycle)
100…240V AC
75…264V AC
0.1 A
0.1 A
5 A
5 A
220 A (@50/60 Hz,
1 cycle)
Characteristics
700-SE_ _ _Z…
Item
700-SE_ _ _N…
Load Switching Method/Device
Pick-up time
Triac
1/2 of load power source cycle + 1 ms max.
1 ms max.
Drop-out time
1/2 of load power source cycle + 1 ms max.
1.6 V (RMS) max.
Output ON voltage drop
5 mA max. (at 100V AC)
10 mA max. (at 200V AC)
Output Leakage current
Output VDRM VCEO (V)
Output di/dt (A/uS)
600
600
SE05GZ=100
SE05GN=100
SE10 GN & SE20GN =50
SE10GZ & SE20 GZ =50
SE05GN =200, SE10GN =500, SE20GN
=100
Output dv/dt (V/uS)
SE05GZ=200, SE10GZ=500, SE20GZ=100
2
Output I t (A2S)
SE05GZ =24.5, SE10GZ =60, SE20GZ =260
125
SE05GN =24.5, SE10GN =60, SE20GN =260
125
Output Tj (°C) max.
Insulation resistance
Dielectric strength
100 MΩ min. (at 500V DC)
2,000V AC, 50/60 Hz for 1 min.
10…55 Hz, 1.5 mm double amplitude (10 G)
1,000 m/s2 (100 G)
Vibration resistance (max.)
Shock resistance (max.)
Operating: –30…80°C (–22…176°F) with no icing or condensation
Storage: –30…100°C (–22…212°F) with no icing or condensation
Ambient temperature
Ambient humidity
Standards
Operating
45…85% (no condensation)
UL 508, CSA C22.2 , TUV, CE
Approx. 37 g
Weight
➊ Each 5 A, 10 A, and 20 A model has 5V DC, 12V DC, and 24V DC input versions.
➊ Refer to "Load Current Vs. Ambient Temperature Characteristics" graphs page 45 regarding maximum load current with and without heat sinks.
➊ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 45 for more details.
44
Bulletin 700-SE
Solid-State Relays
Specifications, Continued
Load Current vs. Ambient Temperature Characteristics
700-SE05…
700-SE10…
700-SE20…
With standard heat sink (700-S20) or
aluminum plate measuring 300 mm x
300 mm x 2 mm (W x H x D)
With standard heat sink (700-S10)
or aluminum plate measuring
100 mm x 100 mm x 2 mm (W x H x D)
Without heat sink
Without heat sink
Without heat sink
Ambient temperature (°C)
Ambient temperature (°C)
Ambient temperature (°C)
Inrush Current Resistivity➊
700-SE05...
700-SE10...
700-SE20...
Energizing time (ms)
Energizing time (ms)
Energizing time (ms)
➊ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability
once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
45
Bulletin 700-SE
Solid-State Relays
Approximate Dimensions
Mounting Considerations➊➊➊
Note: All units are in millimeters unless otherwise indicated. Dimensions are not intended for manufacturing purposes.
3.5 dia. hole
Terminal Arrangement/
Internal Connections
(Top View)
47.5
max.
37.5 max.
30±0.5
14.5
3 +
1
Input
voltage
Input
Input
Load
Two #250 (t = 0.8) (Faston
tab or equivalent)
6.5
4 -
2
Two #110 (t = 0.5) (Faston tab
or equivalent)*
Load power
supply
7.1
2.9
7.95
3
11.5 max.
6
Mounting Holes
Two, 3.5-dia. or M3 holes
30±0.2
➊ The proper mounting orientation of the heat sink is so the heat fins run perpendicular to the floor (vertical) to maximize ventilation flow. If the fins do not run perpendicular
to the floor, a 30% current derating is required.
➊ When attaching a heat sink to Bulletin 700-SE, apply heat conductive grease on the heat sink to maximize heat transfer between the SSR and the heat sink.
Recommended types: Silicon based, Toshiba YG6240; Non-silicon based, AOS company type 53300.
➊ Tighten the SSR’s panel/heat sink mounting screws to a torque of 0.78…0.98 Nm (6.9…8.7 lb.-in.)
Heat Sinks
Cat. No. 700-S10
Mounting Holes ➊
Weight: Approx. 200 g
Two, M3 holes
Two, M4 holes
4.6 dia. hole
Two, 3.2-dia.
holes
90±0.4
44 max. 30
47 max.
4.5
35 30.5±0.3
Two, 4.4-dia.
or M4 holes
47.6
5
5.6
6
77 max.
51 max.
90±0.3
35±0.2
100 max.
Cat. No. 700-S20
Mounting Holes
Weight: Approx. 400 g
Two, M4
holes
Two, M3 holes
Two, 3.2-dia. holes
4.6 dia. hole
35 30.5±0.3
90±0.4
71 max.
75 max.
30
Two, 4.4-dia.
or M4 holes
5
5.6
4.5
47.6
28
13
100 max.
77 max.
90±0.3
35±0.2
100 max.
➊ Tighten the heat sink’s panel mounting screws (M4) to a torque of 0.59…0.98 Nm (5.22…8.67 lb.-in.).
Basic Application Considerations
+
R
SSR
Input
C
–
•
Because the operation time of Bulletin 700-SE is extremely short, take measures to suppress noise induced between the input terminals. If generation of strong
noise is expected, connect an external noise absorber such as an RC circuit.
•
•
Do not apply excessive force to the terminals. Exercise care when pulling or inserting the terminal clips.
Bulletin 700-SE has a built-in varistor to absorb most inrush/surge currents when operating AC inductive loads If additional suppression is required, connect an
external varistor across the load device terminals. Select a varistor that meets the load voltage outlined in the table below.
For additional details on applying solid-state relays, refer to pub. 700-AT001A-EN-P, "Solid-State Relay Application Guide." Document available at
www.theautomationbookstore.com.
•
Load Voltage
100…120V AC
200…240V AC
380…480V AC
Varistor Voltage
240…270 V
Varistor Surge Resistance
440…470 V
1000 A min.
820…1000 V
46