Bulletin 700-SE  
Solid-State Relays  
Overview/Product Selection  
Table Of Contents  
Bulletin 700-SE  
Product Selection . . . . . . . .42  
Accessories. . . . . . . . . . . . .43  
Specifications . . . . . . . . . . .44  
Approximate  
20 A (resistive) Max. Continuous Load (Output) Current with Heat Sink  
264V AC Max. Load Voltage Range  
5,12, or 24V DC Control/Input Voltage  
Built-in Varistor Helps Absorb Most Electrical Surges  
Low Profile (Flat Pack) Design  
Quick-Connect #110 Input and #250 Output Terminals  
Dimensions . . . . . . . . . . . . .46  
Factory-  
stocked  
Item  
(single  
pack)  
Input-to-  
Output  
Isolation  
Method  
Rated Output (Load)  
Max. Current and  
Voltage Range ➊  
ZeroCross  
Function  
LED  
Indicator  
Rated Input  
Control Voltage  
Cat. No.  
5V DC  
12V DC  
24V DC  
5V DC  
700-SE05GZZ05  
700-SE05GZZ12  
700-SE05GZZ24  
700-SE10GZZ05  
700-SE10GZZ12  
700-SE10GZZ24  
700-SE20GZZ05  
700-SE20GZZ12  
700-SE20GZZ24  
700-SE05GNZ05  
700-SE05GNZ12  
700-SE05GNZ24  
700-SE10GNZ05  
700-SE10GNZ12  
700-SE10GNZ24  
700-SE20GNZ05  
700-SE20GNZ12  
700-SE20GNZ24  
5 A at 100…240V AC  
10 A at 100…240V AC  
20 A at 100…240V AC  
5 A at 100…240V AC  
10 A at 100…240V AC  
20 A at 100…240V AC  
Yes  
12V DC  
24V DC  
5V DC  
12V DC  
24V DC  
5V DC  
Phototriac  
No  
12V DC  
24V DC  
5V DC  
No  
12V DC  
24V DC  
5V DC  
12V DC  
24V DC  
Maximum load current when mounted on a heat sink.  
42  
Bulletin 700-SE  
Solid-State Relays  
Accessories  
Description  
Pkg. Quantity  
Cat. No.  
Factory-stocked Item  
1
700-S10  
Heat Sink — Panel or DIN Rail Mount ➊  
Cat No. 700-S10  
1
700-S20  
Heat Sink — Panel or DIN Rail Mount ➊  
Cat No. 700-S20  
DIN Rail Mounting Pack  
Standard 35 x 7.5 mm DIN Rail, 1 meter long,  
10 rails per package. Order must be for 10  
rails or multiples of 10.  
10  
199-DR1  
Cat No. 199-DR1  
Refer to "Load Current Vs. Ambient Temperature Characteristics" page 45 for information about how to select the correct size of heat sink for your application  
( cat. no. 700-S10, 700-S20).  
43  
Bulletin 700-SE  
Solid-State Relays  
Specifications  
Control/Input Ratings ➊  
Input Impedance  
Control Voltage Levels  
Rated  
Control  
Voltage  
Operating Control  
Voltage Range  
Without Zero  
Cross  
Cat. No.  
With Zero  
Cross Function  
Pick-up Voltage  
Drop-out Voltage  
Function  
700-SE_ _ _Z05  
700-SE_ _ _Z12  
700-SE_ _ _Z24  
5V DC  
12V DC  
24V DC  
4…6V DC  
250 Ω ± 20%  
600 Ω ± 20%  
300 Ω ± 20%  
800 Ω ± 20%  
4V DC max.  
9.6V DC max.  
19.2V DC max.  
9.6…14.4V DC  
19.2…28.8V DC  
1V DC min.  
1.6k Ω ± 20%  
Load/Output Ratings  
Applicable Load  
Continuous Load Current (Resistive)  
With Heat Sink Without Heat Sink ➊  
Min. Max.  
Cat. No.  
Max. Inrush Current  
Rated Load Voltage  
Load Voltage Range  
Min.  
Max.  
5 A  
60 A (@50/60 Hz,  
1 cycle)  
700-SE05…  
700-SE10…  
700-SE20…  
0.1 A  
0.1 A  
0.1 A  
5 A  
10 A  
20 A  
0.1 A  
150 A (@50/60 Hz,  
1 cycle)  
100…240V AC  
75…264V AC  
0.1 A  
0.1 A  
5 A  
5 A  
220 A (@50/60 Hz,  
1 cycle)  
Characteristics  
700-SE_ _ _Z…  
Item  
700-SE_ _ _N…  
Load Switching Method/Device  
Pick-up time  
Triac  
1/2 of load power source cycle + 1 ms max.  
1 ms max.  
Drop-out time  
1/2 of load power source cycle + 1 ms max.  
1.6 V (RMS) max.  
Output ON voltage drop  
5 mA max. (at 100V AC)  
10 mA max. (at 200V AC)  
Output Leakage current  
Output VDRM VCEO (V)  
Output di/dt (A/uS)  
600  
600  
SE05GZ=100  
SE05GN=100  
SE10 GN & SE20GN =50  
SE10GZ & SE20 GZ =50  
SE05GN =200, SE10GN =500, SE20GN  
=100  
Output dv/dt (V/uS)  
SE05GZ=200, SE10GZ=500, SE20GZ=100  
2
Output I t (A2S)  
SE05GZ =24.5, SE10GZ =60, SE20GZ =260  
125  
SE05GN =24.5, SE10GN =60, SE20GN =260  
125  
Output Tj (°C) max.  
Insulation resistance  
Dielectric strength  
100 Mmin. (at 500V DC)  
2,000V AC, 50/60 Hz for 1 min.  
10…55 Hz, 1.5 mm double amplitude (10 G)  
1,000 m/s2 (100 G)  
Vibration resistance (max.)  
Shock resistance (max.)  
Operating: –30…80°C (–22…176°F) with no icing or condensation  
Storage: –30…100°C (–22…212°F) with no icing or condensation  
Ambient temperature  
Ambient humidity  
Standards  
Operating  
45…85% (no condensation)  
UL 508, CSA C22.2 , TUV, CE  
Approx. 37 g  
Weight  
Each 5 A, 10 A, and 20 A model has 5V DC, 12V DC, and 24V DC input versions.  
Refer to "Load Current Vs. Ambient Temperature Characteristics" graphs page 45 regarding maximum load current with and without heat sinks.  
If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 45 for more details.  
44  
Bulletin 700-SE  
Solid-State Relays  
Specifications, Continued  
Load Current vs. Ambient Temperature Characteristics  
700-SE05…  
700-SE10…  
700-SE20…  
With standard heat sink (700-S20) or  
aluminum plate measuring 300 mm x  
300 mm x 2 mm (W x H x D)  
With standard heat sink (700-S10)  
or aluminum plate measuring  
100 mm x 100 mm x 2 mm (W x H x D)  
Without heat sink  
Without heat sink  
Without heat sink  
Ambient temperature (°C)  
Ambient temperature (°C)  
Ambient temperature (°C)  
Inrush Current Resistivity➊  
700-SE05...  
700-SE10...  
700-SE20...  
Energizing time (ms)  
Energizing time (ms)  
Energizing time (ms)  
Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability  
once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.  
45  
Bulletin 700-SE  
Solid-State Relays  
Approximate Dimensions  
Mounting Considerations➊➊  
Note: All units are in millimeters unless otherwise indicated. Dimensions are not intended for manufacturing purposes.  
3.5 dia. hole  
Terminal Arrangement/  
Internal Connections  
(Top View)  
47.5  
max.  
37.5 max.  
30±0.5  
14.5  
3 +  
1
Input  
voltage  
Input  
Input  
Load  
Two #250 (t = 0.8) (Faston  
tab or equivalent)  
6.5  
4 -  
2
Two #110 (t = 0.5) (Faston tab  
or equivalent)*  
Load power  
supply  
7.1  
2.9  
7.95  
3
11.5 max.  
6
Mounting Holes  
Two, 3.5-dia. or M3 holes  
30±0.2  
The proper mounting orientation of the heat sink is so the heat fins run perpendicular to the floor (vertical) to maximize ventilation flow. If the fins do not run perpendicular  
to the floor, a 30% current derating is required.  
When attaching a heat sink to Bulletin 700-SE, apply heat conductive grease on the heat sink to maximize heat transfer between the SSR and the heat sink.  
Recommended types: Silicon based, Toshiba YG6240; Non-silicon based, AOS company type 53300.  
Tighten the SSR’s panel/heat sink mounting screws to a torque of 0.78…0.98 Nm (6.9…8.7 lb.-in.)  
Heat Sinks  
Cat. No. 700-S10  
Mounting Holes ➊  
Weight: Approx. 200 g  
Two, M3 holes  
Two, M4 holes  
4.6 dia. hole  
Two, 3.2-dia.  
holes  
90±0.4  
44 max. 30  
47 max.  
4.5  
35 30.5±0.3  
Two, 4.4-dia.  
or M4 holes  
47.6  
5
5.6  
6
77 max.  
51 max.  
90±0.3  
35±0.2  
100 max.  
Cat. No. 700-S20  
Mounting Holes  
Weight: Approx. 400 g  
Two, M4  
holes  
Two, M3 holes  
Two, 3.2-dia. holes  
4.6 dia. hole  
35 30.5±0.3  
90±0.4  
71 max.  
75 max.  
30  
Two, 4.4-dia.  
or M4 holes  
5
5.6  
4.5  
47.6  
28  
13  
100 max.  
77 max.  
90±0.3  
35±0.2  
100 max.  
Tighten the heat sink’s panel mounting screws (M4) to a torque of 0.59…0.98 Nm (5.22…8.67 lb.-in.).  
Basic Application Considerations  
+
R
SSR  
Input  
C
Because the operation time of Bulletin 700-SE is extremely short, take measures to suppress noise induced between the input terminals. If generation of strong  
noise is expected, connect an external noise absorber such as an RC circuit.  
Do not apply excessive force to the terminals. Exercise care when pulling or inserting the terminal clips.  
Bulletin 700-SE has a built-in varistor to absorb most inrush/surge currents when operating AC inductive loads If additional suppression is required, connect an  
external varistor across the load device terminals. Select a varistor that meets the load voltage outlined in the table below.  
For additional details on applying solid-state relays, refer to pub. 700-AT001A-EN-P, "Solid-State Relay Application Guide." Document available at  
www.theautomationbookstore.com.  
Load Voltage  
100…120V AC  
200…240V AC  
380…480V AC  
Varistor Voltage  
240…270 V  
Varistor Surge Resistance  
440…470 V  
1000 A min.  
820…1000 V  
46  

相关型号:

700-SE10GZZ12

Solid-State Relays
ALLEN-BRADLEY

700-SE10GZZ24

Solid-State Relays
ALLEN-BRADLEY

700-SE20GNZ05

Solid-State Relays
ALLEN-BRADLEY

700-SE20GNZ12

Solid-State Relays
ALLEN-BRADLEY

700-SE20GNZ24

Solid-State Relays
ALLEN-BRADLEY

700-SE20GZZ05

Solid-State Relays
ALLEN-BRADLEY

700-SE20GZZ12

Solid-State Relays
ALLEN-BRADLEY

700-SE20GZZ24

Solid-State Relays
ALLEN-BRADLEY

700-SF

Solid-State Relays
ALLEN-BRADLEY

700-SFNY3Z25

Solid-State Relays
ALLEN-BRADLEY

700-SFTY3Z24

Solid-State Relays
ALLEN-BRADLEY

700-SFZY3Z25

Solid-State Relays
ALLEN-BRADLEY