Digital DC Drive  
Available in either regenerative or non-regenerative configurations, the  
1397 family of digital DC drives employs advanced microprocessor  
technology to help deliver performance, flexibility and  
communications options in a complete, economical drive package.  
To help achieve accurate setup, precise control and flexible operation,  
all 1397 DC drives are digitally programmable. Each drive may be  
programmed locally from a front mounted control panel, or from an  
external Allen-Bradley PLC® or SLC®.  
Contents  
Description  
Page(s)  
1397 Product Selection  
Factory Installed Options  
User Installed Options  
2
4
5
Conformity to Standards  
The 1397 conforms to the following:  
Conforms to:  
UL Listed  
Standard Product  
CSA Certified (C-UL)  
CE Approved  
Allen-Bradley  
1
1397  
Digital DC Drive  
1397 Product Selection  
The 1397 product program includes standard 1397 DC drives rated  
from (1.1-448 kW) 1.5-600Hp, offered in both regenerative and non-  
regenerative configurations. All drives are supplied chassis mounted –  
IP 00 (open) – for user installation. There is a limited offering of  
factory mounted options along with a larger offering of option kits for  
user installation. All standard products in this program are predefined  
and not generally subject to modification. For special requirements  
consult Allen-Bradley.  
230V AC Input Product Selection  
1397  
Bulletin Number  
- A001N  
Rating Type  
(must be specified)  
- HA2  
- DS050 -  
AC Line Disconnect  
(optional)  
PE  
Pulse Encoder Interface  
(optional)  
Control Interface  
(must be specified)  
Nominal  
Drive Rating 230V AC Drives — IP 00 (Open) — No Enclosure  
230V AC Rated240VDC Rated150VDC Rated✔  
kW (Hp) Code  
Line Amps  
Armature Amps Field Amps  
1.2 (1.5)  
1.5 (2)  
2.2 (3)  
A001__✔  
10  
11  
7
10  
10  
10  
10  
10  
10  
10  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
A002__✔  
A003__✔  
A005__✔  
A007__✔  
A010__✔  
A015__✔  
A020__✔  
A025__✔  
A030__✔  
A040__✔  
A050__✔  
A060__✔  
A075__✔  
A100__✔  
A125__✔  
A150__✔  
9
12  
13  
3.7 (5)  
19  
20  
5.5 (7.5)  
7.5 (10)  
11 (15)  
15 (20)  
18.5 (25)  
22 (30)  
30 (40)  
37 (50)  
45 (60)  
56 (75)  
75 (100)  
93 (125)  
112 (150)  
26  
29  
33  
38  
48  
63  
55  
73  
80  
93  
94  
110  
146  
180  
218  
265  
360  
434  
521  
125  
154  
186  
226  
307  
370  
443  
Either an “N” (non-regenerative) or an “R” (regenerative) drive must be specified.  
At least one of either a Human Interface Module (HIM) or Option 1203-GD2 using DriveTools32™  
will be required to program the drive. Chosen option(s) may be ordered factory installed (if  
available) or as user installed kits.  
kW ratings are based on rated input voltage.  
Consult factory for alternate voltages.  
For special field voltage requirements refer to the Enhanced Field Supply Option.  
2
Allen-Bradley  
1397  
Digital DC Drive  
380/415V AC Product Selection  
1397  
Bulletin Number  
- U55FN  
Rating Type  
(must be specified)  
- HA2  
- DS050 -  
AC Line Disconnect  
(optional)  
PE  
Pulse Encoder Interface  
(optional)  
Control Interface  
(must be specified)  
380/415V AC Drives — IP 00 (Open) — No Enclosure  
380V AC Input 415V AC Input  
380/415V AC  
Rated Line Amps Armature Amps  
400/460V DC Rated 250/270V DC Rated  
Field Amps  
kW (Hp)  
kW (Hp)  
Code  
1.8 (2.4)  
9 (12)  
2.1(2.8)  
U7F__✔  
10  
26  
7
29  
10  
10  
10  
15  
20  
10.3(13.8)  
20.8(27.6)  
41.2(55.2)  
102.9(138)  
U29F__✔  
U55F__✔  
U110F__✔  
U265F__✔  
17.9 (24)  
35.8 (48)  
89.5 (120)  
48  
55  
94  
110  
265  
226  
460V AC Product Selection  
1397  
Bulletin Number  
- B003N  
Rating Type  
(must be specified)  
- HA2  
Control Interface  
(must be specified)  
- DS050 -  
AC Line Disconnect  
(optional)  
PE  
Pulse Encoder Interface  
(optional)  
Nominal  
Drive Rating 460V AC Drives — IP 00 (Open) — No Enclosure  
460V AC Rated500VDC Rated300VDC Rated✔  
kW (Hp) ✔  
Code  
Line Amps  
Armature Amps Field Amps  
2.2 (3)  
B003__✔  
B005__✔  
B007__✔  
B010__✔  
B015__✔  
B020__✔  
B025__✔  
B030__✔  
B040__✔  
B050__✔  
B060__✔  
B075__✔  
B100__✔  
B125__✔  
B150__✔  
B200__✔  
B250__✔  
B300__✔  
B400__✔  
B500__✔  
B600__✔  
10  
12  
6
10  
10  
10  
10  
10  
10  
10  
10  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
15  
3.7 (5)  
10  
5.5 (7.5)  
7.5 (10)  
11 (15)  
15  
14  
18  
19  
24  
31  
27  
35  
15 (20)  
18.5 (25)  
22 (30)  
39  
45  
45  
52  
30 (40)  
63  
73  
37 (50)  
45 (60)  
74  
86  
86  
100  
129  
167  
207  
250  
330  
412  
495  
667  
800  
960  
56 (75)  
110  
143  
177  
213  
281  
351  
421  
567  
680  
816  
75 (100)  
93 (125)  
112 (150)  
149 (200)  
187 (250)  
224 (300)  
298 (400)  
373 (500)  
448 (600)  
Either an “N” (non-regenerative) or an “R” (regenerative) drive must be specified.  
At least one of either a Human Interface Module (HIM) or Option 1203-GD2 using DriveTools32™  
will be required to program the drive. Chosen option(s) may be ordered factory installed (if  
available) or as user installed kits.  
kW ratings are based on rated input voltage.  
Consult factory for alternate voltages.  
For special field voltage requirements refer to the Enhanced Field Supply Option.  
Inverting fault protection must be separately supplied external to drive on 400-600 Hp negative.  
See user installed option 1397-IFB600.  
Allen-Bradley  
3
1397  
Digital DC Drive  
Factory Installed Options  
Control Options  
Description  
Used With . . .  
Option Code  
AC Line Disconnect  
230V Rating ✔  
All Drives  
460V Rating ✔  
kW  
(Hp)  
kW  
(Hp)  
1.2-18.5  
22  
(1.5-25)  
(30)  
2.3-37  
45  
(3-50)  
-DS050  
-DS060  
-DS125  
-DS150  
-DS200  
-DS300  
-DS500  
-DS600  
(60)  
(75-125)  
(150)  
30-45  
56  
(40-60)  
(75)  
56-93  
112  
75  
92-112  
(100)  
(125-150)  
149  
(200)  
187-224  
298-373  
448  
(250-300)  
(400-500)  
(600)  
Blower Motor Starter - Current Rated  
All Drives  
Blower Motor Amp Current Rating  
0.4-0.63  
-MB006  
-MB010  
-MB014  
-MB018  
-MB024  
-MB031  
-MB040  
-MB050  
-MB065  
-MB085  
-MB110  
-PE  
0.63-1.0  
1.0-1.4  
1.4-1.8  
1.7-2.4  
2.2-3.1  
2.8-4.0  
3.5-5.0  
4.5-6.5  
6.0-8.5  
7.5-11.0  
Pulse Encoder Interface  
AC Tachometer Interface  
Fixed Field Supply  
Enhanced Field Supply - Current Rated  
- Provides field preweakening for gear-in.  
All Drives  
All Non-Regen Drives -AC  
All Drives  
All Drives  
✔✔  
- Provides 2 240V DC field on 230V AC rated drives  
for textile and MG set replacement applications.  
- Provides a means to match many different field  
voltages without requiring a transformer  
DC Amp Current Rating  
10  
20  
-FS3010  
-FS3020  
All Drives  
All Drives  
Regulated Field Supply - Current Rated  
Provides field weakening and field current regulation  
DC Amp Current Rating  
4
-FS2004  
-FS2010  
-FS2015  
-L11  
10  
15  
I/O Expansions Card  
Provides additional I/O structure  
(5) Digital Outputs  
(2) Analog Inputs  
(1) Frequency Input  
(2) Digital Outputs  
(2) Analog Outputs  
Frequency Output  
All options are chassis mounted unless noted. For a more functionally complete description of  
each option, refer to publication 1397-BR001.  
kW ratings are based on rated input voltage.  
Fixed Field Supply is provided with:  
230V AC drives rated 56 kW (75 Hp) and below  
380V AC drives rated 35.8 kW (48 Hp) and below  
415V AC drives rated 41.2 kW (55.2 Hp) and below  
460V AC drives rated 112 kW (150 Hp) and below.  
Regulated Field Supply is provided with:  
230V AC drives rated 75 kW (100 Hp) and above  
380V AC drives rated 89.5 kW (120 Hp)  
415V AC drives rated 102.9 kW (138 Hp)  
460V AC drives rated 149 kW (200 Hp) and above.  
Fixed Field Supply does not have field economy. Check motor requirements for applicability.  
4
Allen-Bradley  
1397  
Digital DC Drive  
HIM Options  
Description  
Used With . .  
Option Code  
IP 20 (NEMA/UL Type 1) HIM  
Blank - No Functionality  
Programmer Only  
-HAB  
-HAP  
-HA1  
-HA2  
All Drives  
Programmer/Controller w/Analog Pot  
Programmer/Controller w/Digital Pot  
User Installed Options  
Inverting Fault Breaker Kit  
Description  
Used With. . . Catalog Number  
Provides inverting fault protection for 400-600 Hp regen- 400-600 Hp  
erative drives. Trip setting adjustable for 400, 500, or 600 regenerative  
1397-IFB600  
Hp Drives. Mounts separately from the Drive Chassis.  
drives.  
240V DC Dynamic Brakes, IP00 (No Enclosure)  
Drive Output  
kW (Hp) ✔  
Used With. . . Catalog Number  
1.2 (1.5)  
1.5 2)  
2.2 (3)  
All 230VAC  
Input Drives  
1397-DB-A001L  
1397-DB-A002L  
1397-DB-A003L  
1397-DB-A005L  
1397-DB-A007L  
1397-DB-A010L  
1397-DB-A015L  
1397-DB-A020L  
1397-DB-A025L  
1397-DB-A030L  
1397-DB-A040L  
1397-DB-A060L  
1397-DB-A075L  
1397-DB-A100L  
1397-DB-A125L  
1397-DB-A150L  
3.7 (5)  
5.5 (7.5)  
7.5 (10)  
11 (15)  
15 (20)  
18.5 (25)  
22 (30)  
30 (40)  
37-45 (50-60)  
56 (75)  
75 (100)  
93 (125)  
112 (150)  
500V DC Dynamic Brakes, IP00 (No Enclosure)  
Drive Output  
kW (Hp) ✔  
Used With. . . Catalog Number  
2.2 (3)  
All 460V AC  
Input Drives  
1397-DB-B003L  
1397-DB-B005L  
1397-DB-B007L  
1397-DB-B010L  
1397-DB-B015L  
1397-DB-B025L  
1397-DB-B030L  
1397-DB-B040L  
1397-DB-B060L  
1397-DB-B075L  
1397-DB-B125L  
1397-DB-B150L  
1397-DB-B200L  
1397-DB-B250L  
1397-DB-B300L  
1397-DB-B400L  
1397-DB-B500L  
1397-DB-B600L  
3.7 (5)  
5.5 (7.5)  
7.5 (10)  
11 (15)  
15-18.5 (20-25)  
22 (30)  
30 (40)  
37-45 (50-60)  
56 (75)  
75-93 (100-125)  
112 (150)  
149 (200)  
187 (250)  
224 (300)  
298 (400)  
373 (500)  
448 (600)  
Dynamic brake hardware (DC loop contactor, control transformer & grids) mounts separately from  
the drive chassis. For a more functionally complete description of each option refer to publication  
1397-BR001. Dynamic Brake Kits 1397-DB-B400L, -B500L, and -B600L use the Drive contactor.  
kW ratings are based on rated input voltage.  
Allen-Bradley  
5
1397  
Digital DC Drive  
Line Reactors, IP00 (Open Style) – 230V, 60Hz  
Input or Output Line Reactor  
Drive  
Drive Output  
3% Impedance  
5% Impedance  
Catalog  
Number kW  
Hp  
1.5  
2
Catalog Number  
1321-3R8-A  
Catalog Number  
1321-3R8-B  
A001  
A002  
A003  
A005  
A007  
A010  
A015  
A020  
A025  
A030  
A040  
A050  
A060  
A075  
A100  
A125  
A150  
1.2  
1.5  
2.2  
3.7  
5.5  
7.5  
11  
1321-3R8-A  
1321-3R8-B  
3
1321-3R12-A  
1321-3R18-A  
1321-3R25-A  
1321-3R35-A  
1321-3R45-A  
1321-3R55-A  
1321-3R80-A  
1321-3R100-A  
1321-3R130-A  
1321-3R160-A  
1321-3R160-A  
1321-3R200-A  
1321-3RB250-A  
1321-3RB320-A  
1321-3RB400-A  
1321-3R12-B  
1321-3R18-B  
1321-3R25-B  
1321-3R35-B  
1321-3R45-B  
1321-3R55-B  
1321-3R80-B  
1321-3R100-B  
1321-3R130-B  
1321-3R160-B  
1321-3R160-B  
1321-3R200-B  
1321-3RB250-B  
1321-3RB320-B  
1321-3RB400-B  
5
7.5  
10  
15  
20  
25  
30  
40  
50  
60  
75  
100  
125  
150  
15  
18.5  
22  
30  
37  
45  
56  
75  
93  
112  
Line Reactors, IP00 (Open Style) – 460V, 60Hz  
Input or Output Line Reactor  
Drive  
Drive Output  
3% Impedance  
5% Impedance  
Catalog  
Number kW  
Hp  
3
Catalog Number  
1321-3R8-C  
Catalog Number  
1321-3R8-D  
B003  
B005  
B007  
B010  
B015  
B020  
B025  
B030  
B040  
B050  
B060  
B070  
B100  
B125  
B150  
B200  
B250  
B300  
B400  
B500  
B600  
2.2  
3.7  
5.5  
7.5  
11  
5
1321-3R8-B  
1321-3R8-C  
7.5  
10  
1321-3R12-B  
1321-3R18-B  
1321-3R25-B  
1321-3R35-B  
1321-3R35-B  
1321-3R45-B  
1321-3R55-B  
1321-3R80-B  
1321-3R80-B  
1321-3R100-B  
1321-3R130-B  
1321-3R160-B  
1321-3R200-B  
1321-3RB250-B  
1321-3RB320-B  
1321-3RB400-B  
1321-3R500-B  
1321-3R600-B  
1321-3R750-B  
1321-3R12-C  
1321-3R18-C  
1321-3R25-C  
1321-3R35-C  
1321-3R45-C  
1321-3R55-C  
1321-3R80-C  
1321-3R80-C  
1321-3R100-C  
1321-3R130-C  
1321-3R160-C  
1321-3R160-C  
1321-3R200-C  
1321-3RB250-C  
1321-3RB320-C  
1321-3RB400-C  
1321-3R500-C  
1321-3R600-C  
1321-3R750-C  
15  
15  
20  
18.5  
22  
25  
30  
30  
40  
37  
50  
45  
60  
56  
75  
75  
100  
125  
150  
200  
250  
300  
400  
500  
600  
93  
112  
149  
187  
224  
298  
373  
448  
6
Allen-Bradley  
1397  
Digital DC Drive  
Line Reactors, IP00 (Open Style) – 380V, 50Hz  
Input or Output Line Reactor  
Drive  
Catalog  
Number kW  
Drive Output  
3% Impedance  
5% Impedance  
Hp  
2.4  
12  
Catalog Number Catalog Number  
U7F  
1.8  
1321-3R8-C  
1321-3R25-B  
1321-3R45-B  
1321-3R80-A  
1321-3R200-B  
1321-3R8-D  
1321-3R25-C  
1321-3R45-C  
1321-3R80-B  
1321-3R200-C  
U29F  
U55F  
U110F  
U265F  
9
17.9  
35.8  
89.5  
24  
48  
120  
Line Reactors, IP00 (Open Style) – 415V, 50Hz  
Input or Output Line Reactor  
Drive  
Drive Output  
3% Impedance  
5% Impedance  
Catalog  
Number kW  
Hp  
Catalog Number Catalog Number  
U7F  
2.1  
2.8  
1321-3R8-C  
1321-3R25-B  
1321-3R45-B  
1321-3R80-A  
1321-3R200-B  
1321-3R8-D  
1321-3R25-C  
1321-3R45-C  
1321-3R80-B  
1321-3R200-C  
U29F  
U55F  
U110F  
U265F  
10.3  
20.8  
41.2  
13.8  
27.6  
55.2  
102.9 138  
Allen-Bradley  
7
1397  
Digital DC Drive  
Isolation Transformers, Three-Phase – IP32, NEMA/UL Type 3R  
Transformer  
1397 Drive  
Output✔  
Output Rating Primary Voltage Secondary Voltage  
230V AC 460V AC  
Catalog Number Catalog Number  
kW (Hp)  
kVA  
Volts  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
230  
460  
1.2-2.2 (1.5-3)  
5
1321-3TW005-AA  
1321-3TW005-BA  
3.7 (5)  
7.5  
11  
1321-3TW007-AA 1321-3TW007-AB  
1321-3TW007-BA 1321-3TW007-BB  
1321-3TW011-AA 1321-3TW011-AB  
1321-3TW011-BA 1321-3TW011-BB  
1321-3TW014-AA 1321-3TW014-AB  
1321-3TW014-BA 1321-3TW014-BB  
1321-3TW020-AA 1321-3TW020-AB  
1321-3TW020-BA 1321-3TW020-BB  
1321-3TW027-AA 1321-3TW027-AB  
1321-3TW027-BA 1321-3TW027-BB  
1321-3TW034-AA 1321-3TW034-AB  
1321-3TW034-BA 1321-3TW034-BB  
1321-3TW040-AA 1321-3TW040-AB  
1321-3TW040-BA 1321-3TW040-BB  
1321-3TW051-AA 1321-3TW051-AB  
1321-3TW051-BA 1321-3TW051-BB  
1321-3TH063-AA 1321-3TH063-AB  
1321-3TH063-BA 1321-3TH063-BB  
1321-3TH075-AA 1321-3TH075-AB  
1321-3TH075-AB 1321-3TH075-BB  
1321-3TH093-AA 1321-3TH093-AB  
1321-3TH093-BA 1321-3TH093-BB  
1321-3TH118-AA 1321-3TH118-AB  
1321-3TH118-BA 1321-3TH118-BB  
1321-3TH145-AA 1321-3TH145-AB  
1321-3TH145-BA 1321-3TH145-BB  
1321-3TH175-AA 1321-3TH175-AB  
1321-3TH175-BA 1321-3TH175-BB  
1321-3TH220-AA 1321-3TH220-AB  
1321-3TH220-BA 1321-3TH220-BB  
1321-3TH275-AA 1321-3TH275-AB  
1321-3TH275-BA 1321-3TH275-BB  
1321-3TH330-AA 1321-3TH330-AB  
1321-3TH330-BA 1321-3TH330-BB  
5.5 (7.5)  
7.5 (10)  
11 (15)  
14  
20  
15 (20)  
27  
18.5 (25)  
22 (30)  
34  
40  
30 (40)  
51  
37 (50)  
63  
45 (60)  
75  
56 (75)  
93  
75 (100)  
93 (125)  
112 (150)  
149 (200)  
187 (250)  
224 (300)  
298 (400)  
373 (500)  
448 (600)  
118  
145  
175  
220  
275  
330  
440  
550  
660  
1321-3TH440-AB  
1321-3TH440-BB  
1321-3TH550-AB  
1321-3TH550-BB  
1321-3TH660-AB  
1321-3TH660-BB  
Note the discount schedule difference between Bulletin 1321 and 1397 products.  
kW ratings are based on rated input voltage.  
8
Allen-Bradley  
1397  
Digital DC Drive  
Communication Option Kits  
Catalog Number  
(Loose Kit)  
Option Cable 1202-C03/C10/C30/C90  
Description  
Used with . . .  
Remote Mounted (DIN Rail) – 115V AC  
Requires 115V AC power supply  
Single Point Remote I/O  
All Drive Ratings  
to Drive  
to PLC  
RIO  
1203-GD1✔  
1203-GD2✔  
Comm  
Status  
RS232/422/485, DF1 and DH485 Protocol  
Remote Mounted (DIN Rail) – 24V DC  
Requires 24V DC power supply  
Single Point Remote I/O  
All Drive Ratings  
Input Voltage  
DIN Rail  
120/240V AC  
Input  
1203-GK1✔  
1203-GK2✔  
1203-GK5✔  
1203-GU6✔  
Communication Module  
RS232/422/485, DF1 and DH485 Protocol  
DeviceNet™  
GD1/GD2 – Typical Configuration  
Enhanced DeviceNet™  
ControlNet™ to SCANport Adapter✔  
Remote Mounted (DIN Rail)  
All Drive Ratings  
All Drive Ratings  
1203-CN1✔  
Requires 24VDC power supply  
SLC  
EtherNet/IP to SCANport Adapter✔  
Remote Mounted (DIN Rail), 24V DC  
Requires 24VDC power supply  
AC to DC Power Receptacle  
1203-EN1✔  
20-XCOMM-AC-PS1  
1203-SFC  
Serial Flash Cable  
All Drive Ratings  
All Drive Ratings  
ESC  
SEL  
Connects CN1, GU6 and SSS to a  
computer RS-232 port for adapter  
programming and for DriveTools32 &  
DriveExplorer™ serial interface.  
JOG  
SLC™ Communication Module  
(SLC 500 to SCANport Module)  
Provides a connection for up to 3 drive  
products.  
1203-SM1✔  
SM1 – Typical Configuration  
Smart Self-powered Serial Converter  
Includes 1203-SFC and 1202-C10 Cables  
Serial Null Modem Adapter  
All Drive Ratings  
All Drives  
1203-SSS  
1203-SNM  
1203-USB  
Universal Serial Bus™ (USB) Converter  
Includes 2m USB, 20-HIM-H10 & 22-HIM-H10  
Cables  
ESC  
SEL  
ESC  
SEL  
JOG  
JOG  
Communication Option Cable Kit  
0.33 Meters (1.1 Feet)  
1 Meter (3.3 Feet)  
All Communication  
Options Listed  
1202-C03  
1202-C10  
1202-C30  
1202-C90  
3 Meter (9.8 Feet)  
9 Meter (29.5 Feet)  
SCANport Expander Module  
One to Two  
One to Four  
All Drive Ratings  
CN1 – Typical Configuration  
1203-SG2  
1203-SG4  
1203-S03  
One to Two Port Splitter Cable  
Requires a Communication Option Cable (1202-C03/C10/C30/C90) to be functional. These units are not acceptable for NEMA/UL Type 4 door mounting or UL  
Type 4X outdoor duty.  
Adapter is programmed/configured via RS-232 using the 1203-SFC cable, (purchased separately) and using a compatible network specific software tool.  
Discount Schedule C2.  
Options mount separately from the drive chassis. For a more functionally complete description of each option, refer to publication 1397-BR001.  
Allen-Bradley  
9
1397  
Digital DC Drive  
Human Interface Module (HIM) Options  
Description  
Used With. . .  
Catalog Number  
Human Interface Modules  
IP 20 (NEMA/UL Type 1)  
All Drives  
HIM  
Blank — No Functionality  
Programmer Only  
1201-HAB ✔  
1201-HAP ✔  
1201-HA1 ✔  
1201-HA2 ✔  
Programmer/Controller w/Analog Pot  
Programmer/Controller w/Digital Pot  
Human Interface Modules  
HIM  
Cradle  
Option Cable  
1202-H03/H10/H30/H90  
IP 66 (NEMA/UL Type 12/UL  
IP 66 (NEMA/UL Type 12/UL Type 4X Indoor) Type 4X Indoor) Enclosures  
Programmer Only  
1201-HJP ✔  
1201-HJ2 ✔  
Programmer/Controller w/ Digital Pot  
Option Cable Kit - Connect to HIM Cradle  
Port  
HIMs not mounted in the HIM  
cradle but connected to the  
HIM Cradle Port  
0.33 Meters (1.1 Feet)  
1 Meter (3.3 Feet)  
1202-H03  
1202-H10  
1202-H30  
1202-H90  
3 Meter (9.8 Feet)  
9 Meter (29.5 Feet)  
Option Cable Kit - Connect to Comm Port  
0.33 Meters (1.1 Feet)  
1 Meter (3.3 Feet)  
HIMs not mounted in the HIM  
cradle but connected to the 1202-C03  
HIM Comm Port  
1202-C10  
1202-C30  
1202-C90  
HIM  
Communication  
Port  
3 Meter (9.8 Feet)  
9 Meter (29.5 Feet)  
IP 20 (NEMA/UL Type 1) Door Mounted  
Bezel Kit  
User Supplied IP 20 (NEMA/ 1201-DMA  
UL Type 1) Enclosures and  
HIM  
Option Cable  
1202-C03/C10/C30/C90  
If this option is mounted separately or used as a hand-held device, an Option Cable Kit is required.  
10  
Allen-Bradley  
1397  
Digital DC Drive  
Accessories & Spare Parts  
Description  
Catalog Number  
1397-MB006  
1397-MB010  
1397-MB014  
1397-MB018  
1397-MB024  
1397-MB031  
1397-MB040  
1397-MB050  
1397-MB065  
1397-MB085  
1397-MB110  
1397-PE  
Blower Motor/Starter, 0.4-0.63A  
Blower Motor/Starter, 0.63-1.0A  
Blower Motor/Starter, 1.0-1.4A  
Blower Motor/Starter, 1.4-1.8A  
Blower Motor/Starter, 1.7-2.4A  
Blower Motor/Starter, 2.2-3.1A  
Blower Motor/Starter, 2.8-4.0A  
Blower Motor/Starter, 3.5-5.0A  
Blower Motor/Starter, 4.5-6.5A  
Blower Motor/Starter, 6.0-8.5A  
Blower Motor/Starter, 7.5-11.0A  
Pulse Encoder Interface  
AC Tach Interface Module  
1397-AC  
Enhanced Field Supply for 230/460V & 10A  
Enhanced Field Supply for 230/460V & 20A  
Regulated Field Supply, 4A  
Regulated Field Supply, 10A  
Regulated Field Supply, 15A  
Control Interface, 115V AC  
I/O Expansion Card  
1397-FS3010  
1397-FS3020  
1397-FS2004  
1397-FS2010  
1397-FS2015  
1397-L10  
1397-L11  
1397-FC0300V Fuse Conv., 3-60 Hp @ 460V to 1.5-30 Hp @ 230V 1397-FC030  
460V TO 230V Fuse Conv.,75-150 Hp @ 460 to 40-75 Hp @ 230  
Line Disconnect, 1.5-25 Hp @ 230V, 3-50 Hp @ 460V  
Line Disconnect, 30 Hp @ 230V, 60 Hp @ 460V  
Line Disconnect, 30-60 Hp @ 230V,75-125 Hp @ 460V  
Line Disconnect, 75 Hp @ 230V, 150 Hp @ 460  
Disconnect Switch, 200 Hp, 460V AC  
1397-FC075  
1397-DS050  
1397-DS060  
1397-DS125  
1397-DS150  
1397-DS200  
1397-DS300  
1397-DS500  
1397-DS600  
Disconnect Switch, 250-300 Hp,460V AC  
Disconnect Switch, 500 Hp @ 460V AC  
Disconnect Switch, 600 HP @ 460V AC  
Allen-Bradley  
11  

相关型号:

1397-B060N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B075N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B100N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B125N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B150N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B200N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B250N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B300N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B400N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B500N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY

1397-B600N-HA2-DS050-PE

Digital DC Drive
ALLEN-BRADLEY
ALLEN-BRADLEY